2023-04-05 11:38:26ELECTRIC REVIEW FAILED
  
 1) PLEASE DETAIL THE REQUIRED RECEPTACLE WITHIN 3 FEET
 OF SECON SINK IN GUEST BATH. NEC 210.52 D BATHROOMS
 2) PLEASE PROVIDE AN ELECTRICAL DRAWING FOR THE MASTER
 BATHROOM. FBC 107.2
 3) PLEASE ADD A NOTE TO PLANS THAT SMOKE ALARMS EXIST
 OR WILL BE INSTALLED AS PER FBC R 314.3
 4) IF NEW SMOKE ALARMS ARE TO BE INSTALLED ADD A NOTE
 TO PLANS THAT THE WIRING WILL BE ARC FAULT PROTECTED AS
 REQUIRED IN ACCORDANCE WITH NEC 210.12
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  