Plan Review Notes
Plan Review Notes For Permit 22050916
Permit Number 22050916
Review Stop B
Sequence Number 3
Notes
Date Text
2022-12-08 17:47:54RESIDENTIAL(R3) ADDITION/ALTERATION THIRD BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22050916
 372 FOREST HILL BLVD
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 ARCHITECTS WITH RESPECT TO EVALUATION OF DESIGN
 PROFESSIONALS DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT
 NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH THE
 FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW
  
  
 PREVIOUS RESPONSE COMMENT:
 1- BASED ON DRAWINGS SUBMITTED, 12" DEEP FOOTINGS DON'T
 PROVIDE 12" MINIMUM FOOTING DEPTH. SEE SECTION 1 ON
 SHEET S-200. ALSO, ENGINEER AND ARCHITECT OF RECORD
 NEED TO COORDINATE PLANS TO SHOW COMPLIANCE WITH THE
 MINIMUM FOOTING DEPTH AND CLEARANCE FOR TERMITE
 INSPECTION AS REQUIRED BY SEC. R403.1.4 FBC-RESIDENTIAL
 AND SEC. R318.7 FBC-RESIDENTIAL.
 ALSO, ARCHITECT AND ENGINEER NEED TO COORDINATE TYPE OF
 FOOTING. ARCHITECT SHOWS A DIFFERENT FOOTING TYPE ON
 SHEET A1-4.2.
  
 NEW RESPONSE TO ENGINEERS LETTER DATED OCTOBER 22,
 2022:
 ENGINEER'S RESPONSE LETTER STATES: "SECTION R403.1.4
 APPLIES TO ISOLATED AND STRIP FOOTINGS. THIS IS A
 MONOLITHIC FOOTING."
 THIS IS INCORRECT. SECTION R403.1.4 APPLIES TO "ALL
 EXTERIOR FOOTINGS". THERE ARE NO EXCEPTIONS. SEE
 SECTION R403.1.4 AND REVISE ALL DETAILS AND
 SPECIFICATIONS AS REQUIRED.
 ALSO, PROVIDE DETAIL/SPECIFICATIONS SHOWING COMPLIANCE
 WITH THE MINIMUM FOOTING DEPTH AND CLEARANCE FOR
 TERMITE INSPECTION AS REQUIRED BY SEC. R403.1.4
 FBC-RESIDENTIAL AND SEC. R318.7 FBC-RESIDENTIAL.
  
  
 ORIGINAL COMMENT:
 9- BUILDING THERMAL ENVELOPE. DESIGNER OF RECORD NEEDS
 TO DEPICT THE BUILDING THERMAL ENVELOPE. NEED TO
 SPECIFY INSULATION MATERIALS AND THEIR R-VALUES.(ROOF,
 WALLS, RAISED FLOOR ABOVE GARAGE, ETC.) AS REQUIRED BY
 SEC. R103.2 FBC-ENERGY CONSERVATION.
 NOTE: KEEP IN MIND THERE ARE FLAT ROOFS AND PITCHED
 ROOFS. AND, COORDINATE WITH ENERGY CALCULATIONS TO
 AVOID CONFLICTS/DELAYS.
  
 RESPONSE:
 PROPOSED SECTION 01/A1-4.3 ON SHEET A1-4.3 SHOWS
 ICYNENE INSULATION IN THE PITCHED AND FLAT ROOF AREAS.
 IT LOOKS LIKE ARCHITECT IS DESIGNING AN UNVENTED ATTIC.
 IF SPECIFYING UNVENTED ATTIC THEN ARCHITECT TO CLARIFY
 WHY SPECIFYING ROOF ATTIC VENTILATION ON DETAIL
 03/A1-4.3 AND DETAIL 04/A1-4.3 ON THE SAME SHEET?
 PROVIDE ICYNENE INSULATION ICC EVALUATION REPORT.
 ARCHITECT TO REVIEW AND APPROVE EVALUATION REPORT PRIOR
 TO SUBMITTAL. (NOTE: THIS REPORT MAY BE SUBMITTED LATER
 AFTER THE PERMIT IS ISSUED BUT BEFORE INSTALLATION)
  
 NOTE: THERE IS A CONFLICT WITH SUBMITTED REVISED
 DRAWINGS. IT LOOKS LIKE THE NUMBER OF THE DRAWINGS WERE
 REVISED BY THE ARCHITECT. FOR EXAMPLE ORIGINAL PROPOSED
 ELEVATIONS WAS DRAWING A1-4.1. REVISED PROPOSED
 ELEVATIONS DRAWING NUMBER WAS CHANGED TO DRAWING
 A1-4.2. THIS CREATES A CONFLICT BECAUSE THE PREVIOUS
 PROPOSED ELEVATIONS DRAWING WAS VERSIONED WITH THE
 REVISED PROPOSED ELEVATIONS. NOW THE FILE NAME DOESN'T
 MATCH THE REVISED DRAWING NUMBER.
 NEED TO COORDINATE WITH THE PERMIT LIBRARIAN TO GET THE
 CORRECT FILE NAME AND DRAWING NUMBER.
 THIS APPLIES TO FILE #008 ALSO. THE FILE NAME AND THE
 DRAWING NUMBER DON'T MATCH). COORDINATE FILE #007, #008
 AND #009 TO MATCH FILE NAME AND DRAWING NUMBER.
  
 ORIGINAL COMMENT:
 10- ROOF WITH LESS THAN 6" EAVES REQUIRES GUTTERS WITH
 DOWNSPOUTS AS REQUIRED BY SEC. R318.5 FBC-RESIDENTIAL.
 SPECIFY GUTTERS ON PLANS. PROVIDE DETAILS AND
 SPECIFICATIONS, INCLUDING TERMINATION OF DOWNSPOUTS.
  
 RESPONSE:
 REVISE PROPOSED ROOF PLAN (SHEET A1-4.1). THERE IS A
 FLAT ROOF (REAR AND FRONT AREAS). NEED TO SPECIFY
 SCUPPERS AT THE PERIMETER OF THE ROOF WHERE THE EAVE IS
 LESS THAN 6". THE ONLY EXCEPTION WHERE GUTTER IS NOT
 REQUIRED IS FOR GABLE ROOFS.
  
 ORIGINAL COMMENT:
 12- DESIGNER OF RECORD OF RECORD TO SPECIFY ROOF
 VENTILATION AS REQUIRED BY SEC. R806 FBC-RESIDENTIAL.
 SPECIFY VENT SIZE AND LOCATION.
 NOTE: THERE ARE FLAT AND PITCHED ROOFS. IF DESIGNING
 UNVENTED ATTICS, THEN SPECIFY HOW COMPLYING WITH SEC.
 R806.5 FBC-RESIDENTIAL.
  
 RESPONSE:
 RESPONSE LETTER STATES: "PLEASE SEE REVISED SHEET
 A1-4.1 INDICATING ROOF PITCH".
 THIS IS INCORRECT. THE REQUEST WAS TO SPECIFY ROOF
 VENTILATION NOT ROOF PITCH. READ SEC. R806
 FBC-RESIDENTIAL AND PROVIDE THE REQUIRED INFORMATION
 FOR CROSS VENTILATION FOR ALL ROOF AREAS. (SEE NOTE ON
 ITEM #12 ABOVE. ALSO, COORDINATE WITH ITEM #9 ABOVE).
  
 13- DEFERRED SUBMITTAL: PRODUCT APPROVALS (NOTE:
 PROVIDE COMPLETE INFORMATION FOR REVIEW AFTER PERMIT
 ISSUANCE BUT PRIOR TO INSTALLATION TO AVOID
 CONFLICTS/DELAYS. ALL PRODUCT APPROVALS NEED TO BE
 APPROVED IN WRITING BY DESIGNER OF RECORD PRIOR TO
 SUBMITTAL:
 A)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 D)INSWING ENTRY DOOR AS SHOWN ON PLANS. (NOTE: FLOOR
 PLAN ON SHEET A1-4. WAS CHANGED SHOWING AN OUTSWING
 DOOR BUT PROPOSED WINDOWS & DOORS FLOOR PLAN ON SHEET
 A1-4.3 WAS NOT REVISED. NEED TO REVISE BOTH PLANS TO
 MATCH AVOID CONFLICTS/DELAYS).
  
 E)HORIZONTAL SLIDING WINDOWS.
 F)FIXED WINDOWS.
 G) REAR SWING DOOR.
 H)SLIDING GLASS DOOR.
  
 14- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 ORIGINAL COMMENT:
 15- BEDROOM #3 WINDOW W-11: PROVIDE MANUFACTURER'S
 SPEC'S SHOWING COMPLIANCE WITH THE EGRESS REQUIREMENTS
 OF SEC. R310.2.1 FBC-RESIDENTIAL. NEED TO VERIFY CLEAR
 WIDTH OPENING ON SPECIFIED SIZE WITH 4 PANELS.
  
 RESPONSE:
 RESPONSE LETTER STATES "WINDOW TO BE REPLACED WITH
 3-EQUAL SIZE PANELS".
 WINDOW SCHEDULE WAS NOT REVISED TO REFLECT THIS CHANCE.
 ALSO, ARCHITECT'S RESPONSE LETTER IS REFERENCING SEC.
 R310.2.5 REPLACEMENT WINDOWS. BEDROOM #3 NEEDS TO
 COMPLY WITH THE EMERGENCY EGRESS REQUIREMENTS,
 ACCORDING TO CITY RECORDS, THIS ROOM IS A CHANGE OF
 OCCUPANCY. THIS ROOM WAS EITHER A GARAGE OR CARPORT AND
 THERE ARE NO CITY RECORDS FOR THE CONVERSION OF THIS
 ROOM TO LIVABLE AREA.
  
 17- REVISE ENERGY CALCULATIONS SUBMITTED:
  
 A)
  
 ORIGINAL COMMENT:
 B)CEILING INFORMATION NEED TO BE COORDINATED WITH ITEM
 #9 ABOVE. PLANS NEED TO SHOW THE THERMAL ENVELOPE AND
 SPECIFY IF DESIGNING VENTED OR UNVENTED ATTICS. NOTE:
 THERE ARE SOME FLAT ROOFS IN THIS PROJECT THAT NEED TO
 BE CONSIDERED ALSO. SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 RESPONSE:
 THIS NEEDS TO BE COORDINATED WITH THE DESIGNER OF
 RECORD TO AVOID MORE CONFLICTS/DELAYS. ARCHITECT OF
 RECORD IS SPECIFYING ICYNENE ATTIC INSULATION. IT LOOKS
 LIKE ARCHITECT IS DESIGNING UNVENTED ATTICS. ITEM
 #11(B) SPECIFIES A VENTED ATTIC. REVISE AS REQUIRED TO
 MATCH PLANS. COORDINATE WITH ITEM #9 ABOVE.
  
 C)
  
 ORIGINAL COMMENT:
 D) REVISE ATTIC INFORMATION ON PAGE 3. COORDINATE WITH
 ITEM (B) ABOVE.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
 NOTE: TYPICALLY THE VENT RATIO (WHEN PROVIDED) IS AT
 LEAST 1/150.
 IF ENGINEER PREPARING THE ENERGY CALCULATIONS WANTS TO
 USE 1/300 VENT RATIO, THEN NEED TO PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE WITH THIS
 RATIO. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT REVISED.
 NOTE: COORDINATE WITH ITEM #17(B) ABOVE.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved