2022-10-18 15:09:38RESIDENTIAL(R3) ADDITION/ALTERATION SECOND BUILDING
 REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22050916
 372 FOREST HILL BLVD
  
 1- OK.
  
 ORIGINAL COMMENT:
 B)SPECIFIED FOOTING SIZES DON'T COMPLY WITH THE MINIMUM
 FOOTING DEPTH REQUIRED BY SEC. R403.1.4
 FBC-RESIDENTIAL. REVISE FOOTING SIZE AS REQUIRED.
 COORDINATE WITH TYPICAL WALL SECTION.
 NOTE: SHOW THE CLEARANCE FOR TERMITE INSPECTION ON THE
 WALL SECTION AS REQUIRED BY SEC. R318.7 FBC-RESIDENTIAL
 INSPECTION FOR TERMITES.
  
 RESPONSE:
 BASED ON DRAWINGS SUBMITTED, 12" DEEP FOOTINGS DON'T
 PROVIDE 12" MINIMUM FOOTING DEPTH. SEE SECTION 1 ON
 SHEET S-200. ALSO, ENGINEER AND ARCHITECT OF RECORD
 NEED TO COORDINATE PLANS TO SHOW COMPLIANCE WITH THE
 MINIMUM FOOTING DEPTH AND CLEARANCE FOR TERMITE
 INSPECTION AS REQUIRED BY SEC. R318.7 FBC-RESIDENTIAL.
 ALSO, ARCHITECT AND ENGINEER NEED TO COORDINATE TYPE OF
 FOOTING. ARCHITECT SHOWS A DIFFERENT FOOTING TYPE ON
 SHEET A1-4.2.
  
 2- OK.
 3- OK.
  
 4- SHEET S-0.01:
  
 ORIGINAL COMMENT:
 A)ACCORDING TO TABLE R301.2(2)FBC-RESIDENTIAL, THE
 COMPONENTS AND CLADDING DESIGN PRESSURES FOR WALLS AND
 ROOF ARE TOO LOW. REVISE AS REQUIRED OR PROVIDE ACTUAL
 CALCULATIONS.
  
 RESPONSE:
 PARTIALLY DONE. DESIGN PRESSURES WERE UPDATED BUT ROOF
 ZONES WHERE NOT. SEE COMMENT 4(C) BELOW.
  
 B)OK.
  
 ORIGINAL COMMENT:
 C)REVISE ROOF DIAGRAM TO REFLECT THE REVISED ROOF ZONES
 ON CURRENT CODE FIGURE R301.2(7) FBC-RESIDENTIAL.
  
 RESPONSE:
 (1)PARTIALLY DONE. NEED TO IDENTIFY ALL ROOF ZONES. FOR
 EXAMPLE ZONE 2E, 2R, ZONE 3E, RR, ETC. SEE REVISED ROOF
 ZONES ON CURRENT CODE FIGURE R301.2(7) FBC-RESIDENTIAL.
  
 (2)ROOF ZONES SHOWN ON THE GABLE ROOF DON'T MATCH
 FIGURE R301.2(7) FBC-RESIDENTIAL. MISSING ZONES 2R, 2N
 AND R3.
  
 (3)CORNER OF FLAT ROOF ABOVE DOOR BY THE KITCHEN AREA
 ON THE SOUTH SIDE SEEM TO BE A ZONE 3 NOT A ZONE 2.
 REVISE AS REQUIRED. FIGURE R301.2(7) FBC-RESIDENTIAL.
  
 5-OK.
 6-OK.
 7- OK.
 8-OK.
  
 ORIGINAL COMMENT:
 9- BUILDING THERMAL ENVELOPE. DESIGNER OF RECORD NEEDS
 TO DEPICT THE BUILDING THERMAL ENVELOPE. NEED TO
 SPECIFY INSULATION MATERIALS AND THEIR R-VALUES.(ROOF,
 WALLS, RAISED FLOOR ABOVE GARAGE, ETC.) AS REQUIRED BY
 SEC. R103.2 FBC-ENERGY CONSERVATION.
 NOTE: KEEP IN MIND THERE ARE FLAT ROOFS AND PITCHED
 ROOFS. AND, COORDINATE WITH ENERGY CALCULATIONS TO
 AVOID CONFLICTS/DELAYS.
  
 RESPONSE:
 NOT ADDRESSED. INFORMATION WAS NOT PROVIDED. EITHER THE
 ENGINEER OR THE ARCHITECT NEEDS TO PROVIDE THIS
 INFORMATION.
  
 ORIGINAL COMMENT:
 10- ROOF WITH LESS THAN 6" EAVES REQUIRES GUTTERS WITH
 DOWNSPOUTS AS REQUIRED BY SEC. R318.5 FBC-RESIDENTIAL.
 SPECIFY GUTTERS ON PLANS. PROVIDE DETAILS AND
 SPECIFICATIONS, INCLUDING TERMINATION OF DOWNSPOUTS.
  
 RESPONSE:
 NOT ADDRESSED. INFORMATION WAS NOT PROVIDED. EITHER THE
 ENGINEER OR THE ARCHITECT NEEDS TO PROVIDE THIS
 INFORMATION.
  
 ORIGINAL COMMENT:
 11- ROOF FRAMING PLAN. SPECIFY ROOF PITCH AS REQUIRED
 BY SEC. R905.11.1 SLOPE.
 MODIFIED BITUMEN MEMBRANE ROOFS SHALL HAVE A DESIGN
 SLOPE OF NOT LESS THAN ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) FOR DRAINAGE.
  
 RESPONSE:
 NOT ADDRESSED. INFORMATION WAS NOT PROVIDED. EITHER THE
 ENGINEER OR THE ARCHITECT NEEDS TO PROVIDE THIS
 INFORMATION.
  
 ORIGINAL COMMENT:
 12- ENGINEER OF RECORD TO SPECIFY ROOF VENTILATION AS
 REQUIRED BY SEC. R806 FBC-RESIDENTIAL. SPECIFY VENT
 SIZE AND LOCATION.
 NOTE: THERE ARE FLAT AND PITCHED ROOFS. IF DESIGNING
 UNVENTED ATTICS, THEN SPECIFY HOW COMPLYING WITH SEC.
 R806.5 FBC-RESIDENTIAL.
  
 RESPONSE:
 NOT ADDRESSED. INFORMATION WAS NOT PROVIDED. EITHER THE
 ENGINEER OR THE ARCHITECT NEEDS TO PROVIDE THIS
 INFORMATION.
  
 13-PRODUCT APPROVALS. PROVIDE PRODUCT APPROVAL AS
 REQUIRED BY FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL. PLEASE ADVISE IF
 SUBMITTING NOW OR IF SUBMITTING LATER AS DEFERRED
 SUBMITTAL.):
  
 A)OK
 B)OK.
  
 C)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 D)INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 E)HORIZONTAL SLIDING WINDOWS.
  
 F)FIXED WINDOWS.
  
 G) REAR SWING DOOR.
  
 H)SLIDING GLASS DOOR.
  
 ORIGINAL COMMENT:
 14- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 15- BEDROOM #3 WINDOW W-11: PROVIDE MANUFACTURER'S
 SPEC???S SHOWING COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL. NEED TO
 VERIFY CLEAR WIDTH OPENING ON SPECIFIED SIZE WITH 4
 PANELS.
  
 RESPONSE:
 NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 16- NEED BATHROOM WITH MAXIMUM POSSIBLE PRIVACY AND A
 DOOR THAT PROVIDES 29" MIN. CLEAR OPENING AS REQUIRED
 BY SEC. R320.1.1 FBC-RESIDENTIAL.
 NOTE: PLANS DON'T SPECIFY SIZE OF BATHROOM DOORS. NEED
 THIS INFORMATION.
  
 RESPONSE:
 NOT ADDRESSED.
  
 ORIGINAL COMMENT:
 17- REVISE ENERGY CALCULATIONS SUBMITTED:
  
 RESPONSE:
 REPEAT COMMENTS. NOT ADDRESSED. SEE COMMENTS BELOW AND
 REVISE AS REQUIRED.
  
 A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER NAME(NOT N/A), BUILDER NAME, PERMIT
 OFFICE AND JURISDICTION NUMBER (THIS IS JURISDICTION
 604700). SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 B)CEILING INFORMATION NEED TO BE COORDINATED WITH ITEM
 # 8 ABOVE. PLANS NEED TO SHOW THE THERMAL ENVELOPE AND
 SPECIFY IF DESIGNING VENTED OR UNVENTED ATTICS. NOTE:
 THERE ARE SOME FLAT ROOFS IN THIS PROJECT THAT NEED TO
 BE CONSIDERED ALSO. SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 C)REVISE NUMBER OF OCCUPANTS SPECIFIED ON PAGE 2 UNDER
 SPACES. OCCUPANTS WERE COUNTED TWICE. OCCUPANTS CAN NOT
 BE IN THE BEDROOM AND IN THE LIVING AREA AT THE SAME
 TIME. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 D) REVISE ATTIC INFORMATION ON PAGE 3. COORDINATE WITH
 ITEM (B) ABOVE.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
 NOTE: TYPICALLY THE VENT RATIO (WHEN PROVIDED) IS AT
 LEAST 1/150.
 IF ENGINEER PREPARING THE ENERGY CALCULATIONS WANTS TO
 USE 1/300 VENT RATIO, THEN NEED TO PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE WITH THIS
 RATIO. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 E)WINDOWS OVERHANG DEPTH AND SEPARATION DON'T MATCH
 PLANS. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 F)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  