Plan Review Notes
Plan Review Notes For Permit 22050916
Permit Number 22050916
Review Stop B
Sequence Number 1
Notes
Date Text
2022-07-27 18:18:07RESIDENTIAL(R3) ADDITION/ALTERATION BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22050916 372 FOREST HILL BLVD
  
 NOTE:
 ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- FOUNDATION PLAN SHEET S-1.00:
 A)PROPOSED FOOTINGS DON'T MATCH FOOTING RECOMMENDATIONS
 SPECIFIED ON THE GEO-TECHNICAL REPORT SUBMITTED.
 ENGINEER OF RECORD TO REVIEW GEO-TECHNICAL REPORT AND
 ADJUST FOOTINGS ACCORDINGLY OR PROVIDE WRITTEN RESPONSE
 SHOWING WHY NOT FOLLOWING THE GEOTECHNICAL ENGINEER
 RECOMMENDATIONS. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 B)SPECIFIED FOOTING SIZES DON'T COMPLY WITH THE MINIMUM
 FOOTING DEPTH REQUIRED BY SEC. R403.1.4
 FBC-RESIDENTIAL. REVISE FOOTING SIZE AS REQUIRED.
 COORDINATE WITH TYPICAL WALL SECTION.
 NOTE: SHOW THE CLEARANCE FOR TERMITE INSPECTION ON THE
 WALL SECTION AS REQUIRED BY SEC. R318.7 INSPECTION FOR
 TERMITES.
  
 2- DETAIL 3 ON SHEET S-2.01. BOTTOM CHORD OF ROOF
 RAFTERS IS REMOVED AND RELOCATED. TYPICALLY TOP AND
 BOTTOM CHORD ARE TIED TOGETHER TO ACT AS ONE STRUCTURAL
 MEMBER. CONNECTION IS ALTERED WITH THE REMOVAL OF THE
 BOTTOM CHORD. DETAIL IS MISSING INFORMATION OF HOW THE
 REMAINING CONNECTION BETWEEN THE TOP CHORD AND THE
 MASONRY WALL IS REINFORCED TO RESIST CURRENT LOADS.
 PROVIDE INFORMATION. SEC. 107.2.1.2 CITY AMENDMENTS.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 3- SHEET S-0.00. ENGINEER TO REVISE THE DESIGN WIND
 LOADS. THE WIND SPEED FOR CITY IS 170 MPH AS REQUIRED
 BY SEC. 120 CITY AMENDMENTS NOT 168 MPH. REVISE
 ULTIMATE AND NOMINAL WIND LOADS ACCORDINGLY.
  
 4- SHEET S-0.01:
 A)ACCORDING TO TABLE R301.2(2)FBC-RESIDENTIAL, THE
 COMPONENTS AND CLADDING DESIGN PRESSURES FOR WALLS AND
 ROOF ARE TOO LOW. REVISE AS REQUIRED OR PROVIDE ACTUAL
 CALCULATIONS.
 NOTE: COORDINATE WITH COMMENT (B) BELOW.
  
 B)ENGINEER SPECIFIED "PRESSURES ARE DERIVED FROM ASCE
 7-10". THE CURRENT ASCE REFERENCED IN THE 2020 FBC IS
 THE ASCE 7-16. REVISE AS REQUIRED AND COORDINATE WITH
 ITEM (A) ABOVE.
  
 C)REVISE ROOF DIAGRAM TO REFLECT THE REVISED ROOF ZONES
 ON CURRENT CODE FIGURE R301.2(7) FBC-RESIDENTIAL.
  
 D)REVISE ROOF AND WALL DIMENSION OF THE END SECTION.
 ACCORDING TO FOOTNOTE "A" ON FIGURE R301.2(7)
 FBC-RESIDENTIAL, THE MINIMUM DIMENSION IS 4'-0".
  
 5- SHEET S-1.20:
 A)ENGINEER TO CLARIFY WHY USING WOOD TO WOOD CONNECTOR
 LSTA16 AT THE ENDS OF (3)2?X12? WOOD BEAM LOCATED
 BETWEEN THE EXISTING PITCHED ROOF AND THE PROPOSED FLAT
 ROOF. THIS CONNECTOR IS USUALLY USED FOR TENSION
 BETWEEN TWO WOOD MEMBERS. PROVIDE CALCULATIONS SHOWING
 IT WILL MEET ALL THE UPLIFT AND LATERAL LOADS. ALSO,
 PROVIDE DETAIL SHOWING PROPOSED INSTALLATION. SEC.
 107.2.1.2 CITY AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL.
  
 B) ROOF FRAMING PLAN SHOWS A ?BUTT JOINT? WITH TENSION
 STRAP LAST16 CONNECTION ALONG THE SPAN OF THE (3)2?X12
 WOOD BEAM MENTIONED ABOVE. ENGINEER TO PROVIDE COMPLETE
 DETAIL AND SPECIFICATIONS FOR PROPOSED ?BUTT JOINT?
 SHOWING HOW THIS JOINT WILL SUPPORT ALL THE LIVE AND
 DEAD LOADS. SEC. 107.2.1.2 CITY AMENDMENTS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 C)ENGINEER IS SPECIFYING VTCR CONNECTORS TO RECEIVE
 EXISTING ROOF JOISTS RESTING ON THE OF (3)2?X12? WOOD
 BEAM. THESE CONNECTORS ARE VALLEY TRUSS CLIPS. ENGINEER
 TO PROVIDE COMPLETE ENGINEERING ANALYSIS SHOWING HOW
 THESE CONNECTORS WILL WORK TO SUPPORT ALL THE LOADS AND
 PROVIDE COMPLETE INSTALLATION DETAILS. SEC. 107.2.1.2
 CITY AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL.
  
 D)ENGINEER TO SPECIFY CONNECTORS AT BOTH ENDS OF SINGLE
 2X12 JOISTS LOCATED BETWEEN (3)2?X12? WOOD BEAM AND
 INTERMEDIATE MASONRY WALL.
 ALSO, CLARIFY HOW DOUBLE 2X12 JOISTS AND THE SINGLE
 2X12 JOISTS WILL BE ANCHORED TO THE MASONRY WALL. SEC.
 107.2.1.2 CITY AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL.
  
 E)ENGINEER TO CLARIFY WHY SPECIFYING MASONRY TO WOOD
 CONNECTOR MTSM16 FOR ROOF JOISTS RESTING ON THE NEW
 (3)2X6 WOOD BEAM LOCATED AT THE NORTH WEST CORNER OF
 THE ROOF PLAN. THERE IS NOT MASONRY WALL BELOW THIS
 BEAM. SEC. 107.2.1.2 CITY AMENDMENTS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 F) CROSS SECTION DETAIL 3/S2.01 SHOWN ON THE RIGHT HAND
 SIDE OF THE ROOF FRAMING PLAN. THIS DETAIL SHOWS
 EXISTING BOTTOM CHORD TO BE REMOVED AND RELOCATED.
 ENGINEER TO PROVIDE DETAIL/SPECIFICATIONS SHOWING HOW
 THE CONNECTION AT THE ROOF JOIST AND TOP OF MASONRY
 WALL IS REINFORCED
  
 G) SPECIFY SPACING OF CONNECTOR ?H? SPECIFIED ON THE
 BEAM & JOIST ANCHOR SCHEDULE FOR END JOISTS PARALLEL TO
 THE WALL BELOW.
  
 6- SHEET S-2.00:
 A)DETAIL 11 IS MISSING THE SPECIFICATIONS FOR THE TIE
 BEAM. PROVIDE COMPLETE SPECIFICATIONS. COORDINATE WITH
 TYPICAL MASONRY WALL CONSTRUCTION DETAIL #7 ON SAME
 SHEET. SEC. 107.2.1.2 CITY AMENDMENTS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 B)SPECIFY HOW THE CONCRETE CAP SPECIFIED ON DETAIL 11
 IS ANCHORED TO THE TIE BEAM. SEC. 107.2.1.2 CITY
 AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL.
  
 7- ENGINEER TO PROVIDE SPECIFICATIONS SHOWING HOW
 COMPLYING WITH THE NEW 2020 CODE REQUIREMENT FOR
 ROOFING UNDERLAYMENT. (PITCHED ROOF TO RECEIVE NEW
 METAL ROOFING) SEC. R905.1.1.1 FBC-RESIDENTIAL.
 NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1
 FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001.
 COORDINATE WITH TYPE OF ROOFING MATERIAL SPECIFIED ON
 PLANS.
  
 8 ENGINEER TO PROVIDE DOOR AND WINDOW STRUCTURAL BUCK
 DETAIL SHOWING COMPLIANCE WITH SEC. R609.7.2.1
 FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK SIZE AND
 FASTENING.
 NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO
 THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1
 FBC-RESIDENTIAL.
  
 9- BUILDING THERMAL ENVELOPE. DESIGNER OF RECORD NEEDS
 TO DEPICT THE BUILDING THERMAL ENVELOPE. NEED TO
 SPECIFY INSULATION MATERIALS AND THEIR R-VALUES.(ROOF,
 WALLS, RAISED FLOOR ABOVE GARAGE, ETC.) AS REQUIRED BY
 SEC. R103.2 FBC-ENERGY CONSERVATION.
 NOTE: KEEP IN MIND THERE ARE FLAT ROOFS AND PITCHED
 ROOFS. AND, COORDINATE WITH ENERGY CALCULATIONS TO
 AVOID CONFLICTS/DELAYS.
  
 10- ROOF WITH LESS THAN 6" EAVES REQUIRES GUTTERS WITH
 DOWNSPOUTS AS REQUIRED BY SEC. R318.5 FBC-RESIDENTIAL.
 SPECIFY GUTTERS ON PLANS. PROVIDE DETAILS AND
 SPECIFICATIONS, INCLUDING TERMINATION OF DOWNSPOUTS.
  
 11- ROOF FRAMING PLAN. SPECIFY ROOF PITCH AS REQUIRED
 BY SEC. R905.11.1 SLOPE.
 MODIFIED BITUMEN MEMBRANE ROOFS SHALL HAVE A DESIGN
 SLOPE OF NOT LESS THAN ONE-FOURTH UNIT VERTICAL IN 12
 UNITS HORIZONTAL (2-PERCENT SLOPE) FOR DRAINAGE
  
 12- ENGINEER OF RECORD TO SPECIFY ROOF VENTILATION AS
 REQUIRED BY SEC. R806 FBC-RESIDENTIAL. SPECIFY VENT
 SIZE AND LOCATION.
 NOTE: THERE ARE FLAT AND PITCHED ROOFS. IF DESIGNING
 UNVENTED ATTICS, THEN SPECIFY HOW COMPLYING WITH SEC.
 R806.5 FBC-RESIDENTIAL
  
 13-PRODUCT APPROVALS. PROVIDE PRODUCT APPROVAL AS
 REQUIRED BY FAC 61G20-3.001 FOR:
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)METAL ROOF AS SPECIFIED ON PLANS.
  
 B)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
  
 C)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 D)INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 E)HORIZONTAL SLIDING WINDOWS.
  
 F)FIXED WINDOWS.
  
 G) REAR SWING DOOR.
  
 H)SLIDING GLASS DOOR.
  
 14- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 15- BEDROOM #3 WINDOW W-11: PROVIDE MANUFACTURER'S
 SPECS'S SHOWING COMPLIANCE WITH THE EGRESS REQUIREMENTS
 OF SEC. R310.2.1 FBC-RESIDENTIAL. NEED TO VERIFY CLEAR
 WIDTH OPENING ON SPECIFIED SIZE WITH 4 PANELS.
  
 16- NEED BATHROOM WITH MAXIMUM POSSIBLE PRIVACY AND A
 DOOR THAT PROVIDES 29" MIN. CLEAR OPENING AS REQUIRED
 BY SEC. R320.1.1 FBC-RESIDENTIAL.
 NOTE: PLANS DON'T SPECIFY SIZE OF BATHROOM DOORS. NEED
 THIS INFORMATION.
  
 17- REVISE ENERGY CALCULATIONS SUBMITTED:
 A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM,
 INCLUDING OWNER NAME(NOT N/A), BUILDER NAME, PERMIT
 OFFICE AND JURISDICTION NUMBER (THIS IS JURISDICTION
 604700). SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 B)CEILING INFORMATION NEED TO BE COORDINATED WITH ITEM
 #9 ABOVE. PLANS NEED TO SHOW THE THERMAL ENVELOPE AND
 SPECIFY IF DESIGNING VENTED OR UNVENTED ATTICS. NOTE:
 THERE ARE SOME FLAT ROOFS IN THIS PROJECT THAT NEED TO
 BE CONSIDERED ALSO. SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 C)REVISE NUMBER OF OCCUPANTS SPECIFIED ON PAGE 2 UNDER
 SPACES. OCCUPANTS WERE COUNTED TWICE. OCCUPANTS CAN NOT
 BE IN THE BEDROOM AND IN THE LIVING AREA AT THE SAME
 TIME. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY
 CONSERVATION.
  
 D) REVISE ATTIC INFORMATION ON PAGE 3. COORDINATE WITH
 ITEM (B) ABOVE.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
 NOTE: TYPICALLY THE VENT RATIO (WHEN PROVIDED) IS AT
 LEAST 1/150.
 IF ENGINEER PREPARING THE ENERGY CALCULATIONS WANTS TO
 USE 1/300 VENT RATIO, THEN NEED TO PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE WITH THIS
 RATIO. SEC. 107.2.1.2 CITY AMENDMENTS.
  
 E)WINDOWS OVERHANG DEPTH AND SEPARATION DON'T MATCH
 PLANS. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC-
 ENERGY CONSERVATION.
  
 F)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL
 (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  