2022-07-27 18:18:07 | RESIDENTIAL(R3) ADDITION/ALTERATION BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22050916 372 FOREST HILL BLVD |
| |
| NOTE: |
| ADDITIONS SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1 |
| FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| NOTE: |
| LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING. |
| SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3 |
| FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| |
| 1- FOUNDATION PLAN SHEET S-1.00: |
| A)PROPOSED FOOTINGS DON'T MATCH FOOTING RECOMMENDATIONS |
| SPECIFIED ON THE GEO-TECHNICAL REPORT SUBMITTED. |
| ENGINEER OF RECORD TO REVIEW GEO-TECHNICAL REPORT AND |
| ADJUST FOOTINGS ACCORDINGLY OR PROVIDE WRITTEN RESPONSE |
| SHOWING WHY NOT FOLLOWING THE GEOTECHNICAL ENGINEER |
| RECOMMENDATIONS. SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| B)SPECIFIED FOOTING SIZES DON'T COMPLY WITH THE MINIMUM |
| FOOTING DEPTH REQUIRED BY SEC. R403.1.4 |
| FBC-RESIDENTIAL. REVISE FOOTING SIZE AS REQUIRED. |
| COORDINATE WITH TYPICAL WALL SECTION. |
| NOTE: SHOW THE CLEARANCE FOR TERMITE INSPECTION ON THE |
| WALL SECTION AS REQUIRED BY SEC. R318.7 INSPECTION FOR |
| TERMITES. |
| |
| 2- DETAIL 3 ON SHEET S-2.01. BOTTOM CHORD OF ROOF |
| RAFTERS IS REMOVED AND RELOCATED. TYPICALLY TOP AND |
| BOTTOM CHORD ARE TIED TOGETHER TO ACT AS ONE STRUCTURAL |
| MEMBER. CONNECTION IS ALTERED WITH THE REMOVAL OF THE |
| BOTTOM CHORD. DETAIL IS MISSING INFORMATION OF HOW THE |
| REMAINING CONNECTION BETWEEN THE TOP CHORD AND THE |
| MASONRY WALL IS REINFORCED TO RESIST CURRENT LOADS. |
| PROVIDE INFORMATION. SEC. 107.2.1.2 CITY AMENDMENTS. |
| SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 3- SHEET S-0.00. ENGINEER TO REVISE THE DESIGN WIND |
| LOADS. THE WIND SPEED FOR CITY IS 170 MPH AS REQUIRED |
| BY SEC. 120 CITY AMENDMENTS NOT 168 MPH. REVISE |
| ULTIMATE AND NOMINAL WIND LOADS ACCORDINGLY. |
| |
| 4- SHEET S-0.01: |
| A)ACCORDING TO TABLE R301.2(2)FBC-RESIDENTIAL, THE |
| COMPONENTS AND CLADDING DESIGN PRESSURES FOR WALLS AND |
| ROOF ARE TOO LOW. REVISE AS REQUIRED OR PROVIDE ACTUAL |
| CALCULATIONS. |
| NOTE: COORDINATE WITH COMMENT (B) BELOW. |
| |
| B)ENGINEER SPECIFIED "PRESSURES ARE DERIVED FROM ASCE |
| 7-10". THE CURRENT ASCE REFERENCED IN THE 2020 FBC IS |
| THE ASCE 7-16. REVISE AS REQUIRED AND COORDINATE WITH |
| ITEM (A) ABOVE. |
| |
| C)REVISE ROOF DIAGRAM TO REFLECT THE REVISED ROOF ZONES |
| ON CURRENT CODE FIGURE R301.2(7) FBC-RESIDENTIAL. |
| |
| D)REVISE ROOF AND WALL DIMENSION OF THE END SECTION. |
| ACCORDING TO FOOTNOTE "A" ON FIGURE R301.2(7) |
| FBC-RESIDENTIAL, THE MINIMUM DIMENSION IS 4'-0". |
| |
| 5- SHEET S-1.20: |
| A)ENGINEER TO CLARIFY WHY USING WOOD TO WOOD CONNECTOR |
| LSTA16 AT THE ENDS OF (3)2?X12? WOOD BEAM LOCATED |
| BETWEEN THE EXISTING PITCHED ROOF AND THE PROPOSED FLAT |
| ROOF. THIS CONNECTOR IS USUALLY USED FOR TENSION |
| BETWEEN TWO WOOD MEMBERS. PROVIDE CALCULATIONS SHOWING |
| IT WILL MEET ALL THE UPLIFT AND LATERAL LOADS. ALSO, |
| PROVIDE DETAIL SHOWING PROPOSED INSTALLATION. SEC. |
| 107.2.1.2 CITY AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| B) ROOF FRAMING PLAN SHOWS A ?BUTT JOINT? WITH TENSION |
| STRAP LAST16 CONNECTION ALONG THE SPAN OF THE (3)2?X12 |
| WOOD BEAM MENTIONED ABOVE. ENGINEER TO PROVIDE COMPLETE |
| DETAIL AND SPECIFICATIONS FOR PROPOSED ?BUTT JOINT? |
| SHOWING HOW THIS JOINT WILL SUPPORT ALL THE LIVE AND |
| DEAD LOADS. SEC. 107.2.1.2 CITY AMENDMENTS. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| C)ENGINEER IS SPECIFYING VTCR CONNECTORS TO RECEIVE |
| EXISTING ROOF JOISTS RESTING ON THE OF (3)2?X12? WOOD |
| BEAM. THESE CONNECTORS ARE VALLEY TRUSS CLIPS. ENGINEER |
| TO PROVIDE COMPLETE ENGINEERING ANALYSIS SHOWING HOW |
| THESE CONNECTORS WILL WORK TO SUPPORT ALL THE LOADS AND |
| PROVIDE COMPLETE INSTALLATION DETAILS. SEC. 107.2.1.2 |
| CITY AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| D)ENGINEER TO SPECIFY CONNECTORS AT BOTH ENDS OF SINGLE |
| 2X12 JOISTS LOCATED BETWEEN (3)2?X12? WOOD BEAM AND |
| INTERMEDIATE MASONRY WALL. |
| ALSO, CLARIFY HOW DOUBLE 2X12 JOISTS AND THE SINGLE |
| 2X12 JOISTS WILL BE ANCHORED TO THE MASONRY WALL. SEC. |
| 107.2.1.2 CITY AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| E)ENGINEER TO CLARIFY WHY SPECIFYING MASONRY TO WOOD |
| CONNECTOR MTSM16 FOR ROOF JOISTS RESTING ON THE NEW |
| (3)2X6 WOOD BEAM LOCATED AT THE NORTH WEST CORNER OF |
| THE ROOF PLAN. THERE IS NOT MASONRY WALL BELOW THIS |
| BEAM. SEC. 107.2.1.2 CITY AMENDMENTS. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| F) CROSS SECTION DETAIL 3/S2.01 SHOWN ON THE RIGHT HAND |
| SIDE OF THE ROOF FRAMING PLAN. THIS DETAIL SHOWS |
| EXISTING BOTTOM CHORD TO BE REMOVED AND RELOCATED. |
| ENGINEER TO PROVIDE DETAIL/SPECIFICATIONS SHOWING HOW |
| THE CONNECTION AT THE ROOF JOIST AND TOP OF MASONRY |
| WALL IS REINFORCED |
| |
| G) SPECIFY SPACING OF CONNECTOR ?H? SPECIFIED ON THE |
| BEAM & JOIST ANCHOR SCHEDULE FOR END JOISTS PARALLEL TO |
| THE WALL BELOW. |
| |
| 6- SHEET S-2.00: |
| A)DETAIL 11 IS MISSING THE SPECIFICATIONS FOR THE TIE |
| BEAM. PROVIDE COMPLETE SPECIFICATIONS. COORDINATE WITH |
| TYPICAL MASONRY WALL CONSTRUCTION DETAIL #7 ON SAME |
| SHEET. SEC. 107.2.1.2 CITY AMENDMENTS. SEC. R301.1 |
| FBC-RESIDENTIAL. |
| |
| B)SPECIFY HOW THE CONCRETE CAP SPECIFIED ON DETAIL 11 |
| IS ANCHORED TO THE TIE BEAM. SEC. 107.2.1.2 CITY |
| AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 7- ENGINEER TO PROVIDE SPECIFICATIONS SHOWING HOW |
| COMPLYING WITH THE NEW 2020 CODE REQUIREMENT FOR |
| ROOFING UNDERLAYMENT. (PITCHED ROOF TO RECEIVE NEW |
| METAL ROOFING) SEC. R905.1.1.1 FBC-RESIDENTIAL. |
| NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1 |
| FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE |
| PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001. |
| COORDINATE WITH TYPE OF ROOFING MATERIAL SPECIFIED ON |
| PLANS. |
| |
| 8 ENGINEER TO PROVIDE DOOR AND WINDOW STRUCTURAL BUCK |
| DETAIL SHOWING COMPLIANCE WITH SEC. R609.7.2.1 |
| FBC-RESIDENTIAL. SPECIFY STRUCTURAL BUCK SIZE AND |
| FASTENING. |
| NOTE: STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO |
| THE DOOR FRAME AS REQUIRED BY SEC. R609.7.2.1 |
| FBC-RESIDENTIAL. |
| |
| 9- BUILDING THERMAL ENVELOPE. DESIGNER OF RECORD NEEDS |
| TO DEPICT THE BUILDING THERMAL ENVELOPE. NEED TO |
| SPECIFY INSULATION MATERIALS AND THEIR R-VALUES.(ROOF, |
| WALLS, RAISED FLOOR ABOVE GARAGE, ETC.) AS REQUIRED BY |
| SEC. R103.2 FBC-ENERGY CONSERVATION. |
| NOTE: KEEP IN MIND THERE ARE FLAT ROOFS AND PITCHED |
| ROOFS. AND, COORDINATE WITH ENERGY CALCULATIONS TO |
| AVOID CONFLICTS/DELAYS. |
| |
| 10- ROOF WITH LESS THAN 6" EAVES REQUIRES GUTTERS WITH |
| DOWNSPOUTS AS REQUIRED BY SEC. R318.5 FBC-RESIDENTIAL. |
| SPECIFY GUTTERS ON PLANS. PROVIDE DETAILS AND |
| SPECIFICATIONS, INCLUDING TERMINATION OF DOWNSPOUTS. |
| |
| 11- ROOF FRAMING PLAN. SPECIFY ROOF PITCH AS REQUIRED |
| BY SEC. R905.11.1 SLOPE. |
| MODIFIED BITUMEN MEMBRANE ROOFS SHALL HAVE A DESIGN |
| SLOPE OF NOT LESS THAN ONE-FOURTH UNIT VERTICAL IN 12 |
| UNITS HORIZONTAL (2-PERCENT SLOPE) FOR DRAINAGE |
| |
| 12- ENGINEER OF RECORD TO SPECIFY ROOF VENTILATION AS |
| REQUIRED BY SEC. R806 FBC-RESIDENTIAL. SPECIFY VENT |
| SIZE AND LOCATION. |
| NOTE: THERE ARE FLAT AND PITCHED ROOFS. IF DESIGNING |
| UNVENTED ATTICS, THEN SPECIFY HOW COMPLYING WITH SEC. |
| R806.5 FBC-RESIDENTIAL |
| |
| 13-PRODUCT APPROVALS. PROVIDE PRODUCT APPROVAL AS |
| REQUIRED BY FAC 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| |
| A)METAL ROOF AS SPECIFIED ON PLANS. |
| |
| B)ROOFING UNDERLAYMENT SPECIFIED ON PLANS. |
| |
| C)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| RAS 117 CALCULATIONS ARE REQUIRED. |
| |
| D)INSWING ENTRY DOOR AS SHOWN ON PLANS. |
| |
| E)HORIZONTAL SLIDING WINDOWS. |
| |
| F)FIXED WINDOWS. |
| |
| G) REAR SWING DOOR. |
| |
| H)SLIDING GLASS DOOR. |
| |
| 14- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 15- BEDROOM #3 WINDOW W-11: PROVIDE MANUFACTURER'S |
| SPECS'S SHOWING COMPLIANCE WITH THE EGRESS REQUIREMENTS |
| OF SEC. R310.2.1 FBC-RESIDENTIAL. NEED TO VERIFY CLEAR |
| WIDTH OPENING ON SPECIFIED SIZE WITH 4 PANELS. |
| |
| 16- NEED BATHROOM WITH MAXIMUM POSSIBLE PRIVACY AND A |
| DOOR THAT PROVIDES 29" MIN. CLEAR OPENING AS REQUIRED |
| BY SEC. R320.1.1 FBC-RESIDENTIAL. |
| NOTE: PLANS DON'T SPECIFY SIZE OF BATHROOM DOORS. NEED |
| THIS INFORMATION. |
| |
| 17- REVISE ENERGY CALCULATIONS SUBMITTED: |
| A)PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING OWNER NAME(NOT N/A), BUILDER NAME, PERMIT |
| OFFICE AND JURISDICTION NUMBER (THIS IS JURISDICTION |
| 604700). SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| B)CEILING INFORMATION NEED TO BE COORDINATED WITH ITEM |
| #9 ABOVE. PLANS NEED TO SHOW THE THERMAL ENVELOPE AND |
| SPECIFY IF DESIGNING VENTED OR UNVENTED ATTICS. NOTE: |
| THERE ARE SOME FLAT ROOFS IN THIS PROJECT THAT NEED TO |
| BE CONSIDERED ALSO. SEC. R101.5.1.1.2 FBC- ENERGY |
| CONSERVATION. |
| |
| C)REVISE NUMBER OF OCCUPANTS SPECIFIED ON PAGE 2 UNDER |
| SPACES. OCCUPANTS WERE COUNTED TWICE. OCCUPANTS CAN NOT |
| BE IN THE BEDROOM AND IN THE LIVING AREA AT THE SAME |
| TIME. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC- ENERGY |
| CONSERVATION. |
| |
| D) REVISE ATTIC INFORMATION ON PAGE 3. COORDINATE WITH |
| ITEM (B) ABOVE. |
| SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| NOTE: TYPICALLY THE VENT RATIO (WHEN PROVIDED) IS AT |
| LEAST 1/150. |
| IF ENGINEER PREPARING THE ENERGY CALCULATIONS WANTS TO |
| USE 1/300 VENT RATIO, THEN NEED TO PROVIDE COMPLETE |
| DETAILS AND SPECIFICATIONS SHOWING COMPLIANCE WITH THIS |
| RATIO. SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| E)WINDOWS OVERHANG DEPTH AND SEPARATION DON'T MATCH |
| PLANS. REVISE AS REQUIRED. SEC. R101.5.1.1.2 FBC- |
| ENERGY CONSERVATION. |
| |
| F)BUILDER TO COMPLETE THE ENERGY PERFORMANCE LEVEL |
| (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| CONSERVATION. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |