Plan Review Notes
Plan Review Notes For Permit 22050823
Permit Number 22050823
Review Stop B
Sequence Number 2
Notes
Date Text
2022-06-22 10:24:03PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 SOW: PER NOTE ON PAGE A-1 FLOOR PLAN: "INSTALL NEW
 ENGINEERED WOOD FLOORING"
  
 NOTICE:
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
  
 1. FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR
 TILE, STONE, MARBLE, VINYL (LYT/ LYP), LAMINATE
 FLOORING AND WOOD FLOORING ALL NEED TO HAVE HAD THE
 SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE
 FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS LISTED
 UNDER EACH OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR
 ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
 (TEST SUBMITTED FOR REVIEW IS FOR TILE. PROVIDE TEST
 FOR ENGINEERED WOOD/UNDERLAYMENT ASSEMBLY).
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
 (TEST SUBMITTED FOR REVIEW IS FOR TILE. PROVIDE TEST
 FOR ENGINEERED WOOD/UNDERLAYMENT ASSEMBLY).
  
 1C) FLAME SPREAD- (ASTM E-84 WAS TESTED USING PROFLEX
 SUPER SIM-90. THIS TEST IS ACCEPTABLE IF THE SAME
 UNDERLAYMENT IS USED FOR ASTM E-492 AND E-90.
 IF ANOTHER UNDERLAYMENT IS USED FOR THE TWO SOUND
 TEST'S, PROVIDE A COPY OF THE E-84 FOR THAT
 UNDERLAYMENT).
  
 NEW COMMENTS:
  
 I HAVE RESEARCHED THE CITY'S LIBRARY OF ASTM TEST
 REPORTS AND COULD NOT LOCATE ANY FOR ENGINEERED WOOD
 FLOORING. REQUEST THESE REPORTS FROM YOUR SUPPLIER AND
 SUBMIT FOR REVIEW.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  