Plan Review Notes
Plan Review Notes For Permit 22050714
Permit Number 22050714
Review Stop P
Sequence Number 3
Notes
Date Text
2022-10-10 08:14:08PROVISOS FOR 22050714
 1. PAGE P1.0.1 - OIL/WATER/SAND SEPARATOR REQUIRES
 SEPARATE PERMIT. SPECS TO BE SUBMITTED WITH MASTER
 PERMIT AS WELL AS STAND ALONE PERMIT.
 2. PAGE P1.0.1; P4.0.2 - THE VENTING FOR THE
 OIL/WATER/SAND SEPARATOR CANNOT USE AIR ADMITTANCE
 VALVES. (2020 FPC 918.8) AN ENLARGED DETAIL IS
 REQUIRED.
 3. PAGE A9.2.1 - 2020 FAC SEC. 213.2(4) - A MINIMUM OF
 50% OF THE CLUSTERED BATHROOMS FOR EACH USE SHALL BE
 ACCESSIBLE. REVISION TO BE MADE TO MEET MINIMUM
 STANDARDS.
 4. P1.01; P4.02 - ELEVATOR SUMP DISCHARGE TO BE
 INDIRECTLY CONNECTED TO SANITARY WASTE. DISCHARGE NOT
 IN THE VICINITY OF SUMP DISCHARGE OUTLETS. WASTE
 RECEPTOR TO BE PROVIDED.
 5. P5.0.2; P6.0.1 - QUAD CLOSE TRAP SEAL DETAIL ON PAGE
 P5.0.2 AND EQUIPMENT SCHEDULE ON PAGE P6.0.1 FOR TD-1
 SHOWING MIFAB MI-GARD DO NOT MATCH.
 6. PAGE P1.0.1 - POOL WASTEWATER DISCHARGING INTO HD-1
 SHALL BE DECHLORINATED TO MEET CITY???S STANDARDS THEN
 DISCHARGED INTO STORM SYSTEM. DICHLORINATION DETAILS TO
 BE PROVIDED AND APPROVED BY CITY???S STORMWATER
 DEPARTMENT.
 7. PROVIDE DETAILS ON MASTER FOR CITY???S REQUIRED
 BACKFLOW PROTECTION PER UTILITY DEPARTMENT???S
 REQUIREMENTS.
 8. PAGE P4.1.2 - PROVIDE PAGE 4.1.5 AS CALLED OUT AT
 THE TOP OF THE RISER ON PAGE P4.1.2
 9. HOT WATER AND HOT WATER RETURN PIPING INSULATION
 DETAILS TO BE PROVIDED.
 10. PAGE P6.0.1 - ISOLATION BACKFLOW PREVENTION DEVICES
 TO BE LISTED ON SCHEDULE
 11. PAGE P1.12.1, P2.01 - FD-2 APPEARS TO BE COLLECTING
 STORM WATER AND DISCHARGING TO THE SANITARY. DETAILS TO
 BE SHOWN TO CLARIFY.
 12. P4.01, P4.02, P4.03, P4.04: THE VENT STACKS SHALL
 CONNECT TO THE BASE OF STACKS (SEE OVERALL SANITARY
 RISER - (1/P4.0.3)) - 2020 FPC 904.4
 13. PAGE P4.03 - DETAILS TO BE ADDED SHOWING VENTS FOR
 THE STACK OFFSETS (2020 FPC 711)
 14. PAGE P4.1.4 AND DETAILS PAGES - TO BE ADDED TO THE
 PLUMBING DETAILS AND THE DOMESTIC RISERS SHOWING
 COMPLIANCE WITH 607.1.1 AND 613.1. THE THERMOSTAT ON
 THE WATER HEATER CANNOT BE THE LIMIT FOR HOT OR
 TEMPERED WATER DELIVERY AND THE DEVICE SHALL BE
 INSTALLED AT THE HOT WATER SOURCE.