Date |
Text |
2022-09-23 15:19:18 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT- 22050714 |
| 9/23/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. COMMENTS REMAINING FROM |
| 1ST REVIEW ARE LISTED BELOW. |
| |
| 1) SHEET LS.0.0: SECOND REQUEST- DUE TO A CHANGE IN |
| PROCESS, THE BACKFLOW AND OIL/SAND INTERCEPTOR PERMITS |
| ARE REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE |
| PRIMARY PERMIT. YOU CAN SUBMIT AN APPLICATION "TBD" (TO |
| BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED |
| BY EMAILING A COMPLETED PERMIT APPLICATION TO |
| [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| CHANGE THE REVIEW STATUS TO PASS. |
| |
| 1A) P1.01 NEW COMMENT BASED ON RESUBMITTED PLANS |
| SHOWING THE OIL/SAND INTERCEPTOR. A SEPARATE PERMIT, |
| PLANS AND SPECIFICATIONS ARE REQUIRED HOWEVER A REVIEW |
| OF THE SYSTEM UNDER THE MAIN PERMIT IS ALSO REQUIRED. |
| THE REVIEW AND ITEMS A-D BELOW CAN BE DEFERRED HOWEVER |
| PLEASE NOTE THE CURRENT PLUMBING PLANS SHOW THE TANK |
| VENTING IS NON-COMPLIANT. A) SUBMIT MANUFACTURER???S |
| SPECIFICATIONS FOR THE UNIT INDICATING THE MODEL |
| NUMBER, CAPACITY, AND LISTING NUMBER- SEC.1003.4.2 FBC |
| P. B) UNLISTED INTERCEPTORS SHALL COMPLY WITH SECS. |
| 1003.2.4.1 & 1003.4.2.2. AND DETAILS SHALL BE PROVIDED |
| INDICATING THE UNIT HAS A DEPTH OF 2 FT. BELOW THE |
| INVERT, NOT LESS THAN AN 18-INCH WATER SEAL, AND SHALL |
| HAVE A CAPACITY NOT LESS THAN 6 CU. FT. FOR THE FIRST |
| 100 SQ. FT. OF AREA TO BE DRAINED PLUS 1 CU. FT. FOR |
| EACH ADDITIONAL 100 SQ. FT. C) PLEASE PROVIDE AN |
| ENLARGED PIPING AND INSTALLATION DIAGRAM SHOWING THE |
| LOCATIONS OF CLEANOUTS, VENTS, AND SAMPLING PORT- SEC. |
| 1003.9. PLEASE NOTE THAT THE ISOMETRIC DRAWING ON SHEET |
| P4.0.2 APPEARS TO SHOW THE SEPARATOR IS BEING VENTED |
| USING A STUDOR VENT WHICH IS NOT ALLOWED- SEC. 918.8 |
| FBC P. D) PROVIDE INTERCEPTOR INSTALLATION DETAILS |
| INCLUDING AN ELEVATION VIEW SHOWING THE BURIAL DEPTH, |
| FOUNDATION BASE MATERIAL, AND BACKFILLING FOR SUPPORT |
| AND STABILIZATION OF THE TANK. |
| |
| |
| 2) LS.0.0, A1.1.1, P1.01, & P1.1: SECOND REQUEST TO |
| SHOW DRINKING FOUNTAINS FOR THE GROUND FLOOR LOBBY, |
| OFFICE AND STORAGE AREAS, AND TO PROVIDE PLUMBING |
| PIPING AND ACCESSIBILITY COMPLIANCE DETAILS. PLEASE |
| NOTE THE REQUIRED DRINKING FOUNTAINS CANNOT BE MORE |
| THAN ONE STORY ABOVE THE TENANT SPACE- TABLE 403.1 & |
| SEC. 403.5 FBC P, SEC. 211.1 & 602.1 FBC ACC. |
| |
| 3) LS.0.0, LS.07.1, A1.7.1 & P1.7.1: SECOND REQUEST TO |
| SHOW THE DRINKING FOUNTAIN LOCATIONS ON THE 6TH FLOOR |
| AND TO PROVIDE PLUMBING PIPING AND ACCESSIBILITY |
| COMPLIANCE DETAILS-- TABLE 403.1 & SEC. 403.5 FBC P, |
| SEC. 211.1 & 602.1 FBC ACC. IF THE FIXTURES WILL BE |
| INSTALLED BY FUTURE TENANT PLEASE PLACE A NOTE ON THE |
| PLAN. |
| |
| 4) A1.8.1- A1.11.1 & P1.8.1- P1.11.1: SECOND REQUEST TO |
| SHOW THE LOCATIONS OF THE REQUIRED DRINKING FOUNTAINS |
| LOCATIONS ON THE PLANS FOR THE 7TH- 11TH FLOORS AND |
| PROVIDE PLUMBING PIPING AND ACCESSIBILITY COMPLIANCE |
| DETAILS- - TABLE 403.1 & SEC. 403.5 FBC P, SEC. 211.1 & |
| 602.1 FBC ACC. IF THE FIXTURES WILL BE INSTALLED BY |
| FUTURE TENANT PLEASE PLACE A NOTE ON THE PLAN. |
| |
| 5) A9.2.1: SECOND REQUEST- SEC. 213.2(4) FBC ACC |
| REQUIRES A MINIMUM OF 50% OF THE CLUSTERED TOILET ROOMS |
| FOR EACH USE TO BE ACCESSIBLE. THE PLAN SHOWS TWO |
| ACCESSIBLE SINGLE USER TOILET ROOMS FOR FAMILY USE |
| WHICH ARE ACCEPTABLE SUBSTITUTIONS FOR MALE AND FEMALE |
| USE HOWEVER THREE WATER CLOSETS FOR EACH SEX ARE |
| REQUIRED BY THE CALCULATIONS. THERE ARE SIX SINGLE USER |
| TOILET ROOMS IN THE CLUSTER BUT ONLY .33 % ARE |
| ACCESSIBLE. WHERE MULTIPLE SINGLE USER TOILET ROOMS ARE |
| CLUSTERED AT A SINGLE LOCATION, NO MORE THAN 50 PERCENT |
| OF THE SINGLE USER TOILET ROOMS FOR EACH USE AT EACH |
| CLUSTER SHALL BE REQUIRED TO COMPLY WITH 603. THE |
| FAMILY |
| |
| 10) P1.01, P4.02: SECOND REQUEST. ELEVATOR SUMP PUMP |
| DISCHARGES SHALL BE INDIRECTLY CONNECTED TO THE |
| PLUMBING SYSTEM- SEC. 3002.9 FBC B, SEC. 712.3.5 FBC P. |
| AN INDIRECT WASTE RECEPTOR IS REQUIRED FOR INDIRECT |
| WASTE DISPOSAL- SEC. 802.3 FBC P. IT DOES NOT APPEAR |
| THAT THE WASTE RECEPTOR FD-2 IS IN PROXIMITY OF THE |
| INDIRECT WASTE PIPE OUTLETS TO PREVENT SPLASHING OR |
| FLOODING OF THE ROOM- SEC. 802.4.1 FBC P. |
| |
| 12) P1.01: SECOND REQUEST. QUAD CLOSE BARRIER-TYPE TRAP |
| SEALS ARE SPECIFIED ON SHEET P5.02. PLEASE CORRECT THE |
| PLUMBING EQUIPMENT SCHEDULE ON P6.0.1 SPECIFYING MIFAB. |
| |
| 14) P1.01: SECOND REQUEST. POOL WASTEWATER DISCHARGING |
| INTO HD-1 SHALL BE DECHLORINATED AND THEN BE DRAINED |
| VIA HD-1 INTO THE STORM SYSTEM. THE WATER FEATURE IS |
| UNDER A SEPARATE PERMIT HOWEVER THE CURRENT PLAN DOES |
| NOT SHOW THE WATER FEATURE WASTEWATER DRAINAGE AND |
| DISCHARGE LOCATION. PLEASE BE ADVISED THAT THE |
| WASTEWATER SHALL NOT DISCHARGE INTO THE SANITARY SYSTEM |
| IN ACCORDANCE WITH SEC. 90-126(5) WPB CODE OF |
| ORDINANCES. REVIEW THE INFORMATION BELOW: |
| SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S |
| SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW |
| AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO |
| KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| INLET). |
| NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| INLET TO DISCHARGE EFFLUENT. |
| WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE ALLOWED |
| TO FILTER THROUGH GRASS AREA ON THE POOL OWNER'S |
| PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| PROPERTY. |
| FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT |
| STEPHON HARRIS AT [email protected] OR 561-822-2168. |
| FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE |
| CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| 822-2062 OR [email protected]. |
| |
| 17) P1.01 NOTE 1: SECOND REQUEST TO INDICATE THE TYPE |
| OF BACKFLOW PREVENTER ASSEMBLY TO BE INSTALLED- SEC. |
| 608.3 FBC P, AND SECS. C, D, & E WPB CROSS-CONNECTION |
| CONTROL MANUAL. PLEASE PROVIDE AN EQUIPMENT SCHEDULE |
| AND NOTE THAT IT SHALL BE INSTALLED UNDER A SEPARATE |
| PERMIT- REFERENCE COMMENT #1 ABOVE. PLEASE NOTE BF1 IN |
| THE SCHEDULE IS A DCVA AND NOT AN RPZ REQUIRED FOR |
| POTABLE WATER SERVICE. |
| |
| 18) P1.1.5M NOTE 11, P4.1.1: SECOND REQUEST TO PROVIDE |
| FULL-OPEN SHUT OFF VALVES AT THE BASES OF THE 2-INCH |
| AND 3-INCH WATER RISERS- SEC. 606.1(4) FBC P. PLEASE |
| SEE SHEET P4.1.2 AND PROVIDE BV-1 SYMBOL AT THE BASES |
| OF THE 3-INCH AND 1-INCH CW RISERS. PLEASE SUBMIT SHEET |
| P4.1.5 CALLED OUT AT THE TOP OF THE 3-INCH RISER. |
| |
| 19A) SECOND REQUEST TO PROVIDE HW AND HWR PIPING |
| INSULATION DETAILS- TABLE C403.2.10 FBC EC. NO |
| SPECIFICATIONS HAVE BEEN PROVIDED. |
| |
| 21) P1.7.1 & A9.1.3: SECOND REQUEST TO PROVIDE |
| ACCESSIBILITY DETAILS FOR THE BFS-1- SEC. 211.2 FBC |
| ACC. PLEASE SHOW THE CLEAR FLOOR SPACE DIAGRAM AND |
| DIMENSIONS FOR FORWARD OR SIDE APPROACH TO THE STATION, |
| AND AN ELEVATION DETAIL SHOWING COMPLIANCE WITH SECS. |
| 306, 308, & 309. SUBMIT MANUFACTURER'S SPECIFICATIONS |
| FOR THE STATION. |
| |
| 24) P1.9.1, P1.11.1, P6.01: SECOND REQUEST TO INDICATE |
| THE TYPE OF BACKFLOW ASSEMBLIES (BFP-1) TO BE INSTALLED |
| AND VERIFY ACCESS WILL BE PROVIDED TO THE DEVICES- |
| TABLE 608.3 FBC P. REFER TO COMMENT #1 ABOVE AND PLACE |
| A NOTE INDICATING A SEPARATE PERMIT WILL BE REQUIRED- |
| SEC. 105.1 & 107.2.1 WPB. THE REVISED P6.0.1 PLAN |
| INDICATES A DCVA, HOWEVER AN RPZ IS REQUIRED PER SEC D |
| OF THE WPB CROSS CONNECTION MANUAL- IRRIGATION SYSTEMS |
| ARE CONSIDERED HIGH HAZARD TO THE POTABLE WATER SYSTEM. |
| |
| 25) P1.12.1, P2.01: SECOND REQUEST. THE PLAN APPEARS TO |
| SHOW FD-2 WILL BE DRAINING ROOF RUNOFF/STORMWATER INTO |
| THE SANITARY SYSTEM WHICH IS PROHIBITED- SEC. 90-126(5) |
| WPB CODE OF ORDINANCES. PLEASE PROVIDE A DETAIL SHOWING |
| THE COVERED FD-2. AND CLARIFY WHAT LIQUIDS/WASTES WILL |
| BE DRAINING INTO THE SANITARY VIA THE DRAIN- SEE SECS. |
| 803.1 & 803.2 FBC P. |
| |
| 27) P4.01, P4.02, P4.03, P4.04: SECOND REQUEST TO |
| PROVIDE VENT STACKS FOR THE CORE DRAINAGE STACKS (SEE |
| OVERALL SANTARY RISER- 1/P4.0.3) - SEC. 904.2 FBC P. |
| THE STACKS SHALL CONNECT AT THE BASES OF THE DRAINAGE |
| STACKS- SEC. 904.4. |
| |
| 32) P2.01: SECOND REQUEST TO SHOW THE TYPE OF BACKFLOW |
| PREVENTER TO BE INSTALLED ON THE MAKEUP WATER SUPPLY |
| LINE TO PROTECT THE POTABLE WATER- SEC. 608.3 FBC P, |
| AND SECS. C, D, & E WPB CROSS- CONNECTION CONTROL |
| MANUAL. REFER TO COMMENT #1 FOR PERMITTING |
| REQUIREMENTS. |
| |
| NEW COMMENT- SHEET P4.03: PROVIDE A VENT FOR THE 4-INCH |
| DRAINAGE STACK OFFSET- PLEASE SEE SECS. 907.1, 907.2 & |
| P07.3 FOR COMPLIANCE INFORMATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |