Plan Review Notes
Plan Review Notes For Permit 22050714
Permit Number 22050714
Review Stop B
Sequence Number 2
Notes
Date Text
2022-09-26 14:18:38NEW HI RISE OFFICE BLDG.
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
  
 1) GROUND FLOOR AND MEZZANINE PARKING - PLEASE SHOW
 PARKING GARAGE OPEN OR CLOSED AND PROVIDE THE
 CALCULATIONS (EACH TIER) FOR THE OPEN GARAGE FBC
 406.5.2 OPENINGS.
 FOR NATURAL VENTILATION PURPOSES, THE EXTERIOR SIDE OF
 THE STRUCTURE SHALL HAVE UNIFORMLY DISTRIBUTED OPENINGS
 ON TWO OR MORE SIDES. THE AREA OF SUCH OPENINGS IN
 EXTERIOR WALLS ON A TIER SHALL BE NOT LESS THAN 20
 PERCENT OF THE TOTAL PERIMETER WALL AREA OF EACH TIER.
 THE AGGREGATE LENGTH OF THE OPENINGS CONSIDERED TO BE
 PROVIDING NATURAL VENTILATION SHALL BE NOT LESS THAN 40
 PERCENT OF THE PERIMETER OF THE TIER. INTERIOR WALLS
 SHALL BE NOT LESS THAN 20 PERCENT OPEN WITH UNIFORMLY
 DISTRIBUTED OPENINGS.
  
 2) BUILDING SOUTH ELEVATION - PLEASE SHOW THE ALLOWABLE
 EXTERIOR WALL OPENING PROTECTION CALCULATIONS (EACH
 STORY) ( SOLID WALLS VS DOOR, LOUVERS, OPEN AREAS AT
 GARAGE AND WINDOWS ETC.) PER FBC 705.8.1 ALLOWABLE AREA
 OF OPENINGS.
 THE MAXIMUM AREA OF UNPROTECTED AND PROTECTED OPENINGS
 PERMITTED IN AN EXTERIOR WALL IN ANY STORY OF A
 BUILDING SHALL NOT EXCEED THE PERCENTAGES SPECIFIED IN
 TABLE 705.8.
  
 3) BUILDING WEST ELEVATION - GROUND FLOOR SHOWS A DOOR,
 LOUVERS WHICH ARE NOT SHOWN ON YOUR CALCULATIONS. -
 (EACH STORY) PLEASE SHOW THE ALLOWABLE EXTERIOR WALL
 OPENING PROTECTION CALCULATIONS ( SOLID WALLS VS DOOR,
 LOUVERS, OPEN AREAS AT GARAGE AND WINDOWS ETC.) PER FBC
 705.8.1 ALLOWABLE AREA OF OPENINGS.
 THE MAXIMUM AREA OF UNPROTECTED AND PROTECTED OPENINGS
 PERMITTED IN AN EXTERIOR WALL IN ANY STORY OF A
 BUILDING SHALL NOT EXCEED THE PERCENTAGES SPECIFIED IN
 TABLE 705.8.
  
 4) ELEVATOR HOISTWAY FOR ELEVATOR #3 AND #4 REQUIRES
 HOISTWAY PROTECTION ( A SINGLE SHAFT WHICH APPEARS TO
 RUN FROM GROUND TO THE 11TH FLOOR) FBC 3006.2
  
 5) DRAWING LS.20.1 - DETAIL 2 - SHOULD SAY EAST TO
 WEST.
  
 6) PLEASE SHOW THE PASSENGER LOADING LOCATIONS PER FBC
 ACCESSIBILITY 209.2.1 PASSENGER LOADING ZONES.
 PASSENGER LOADING ZONES, EXCEPT THOSE REQUIRED TO
 COMPLY WITH 209.2.2 AND 209.2.3, SHALL PROVIDE AT LEAST
 ONE PASSENGER LOADING ZONE COMPLYING WITH 503 IN EVERY
 CONTINUOUS 100 LINEAR FEET (30 M) OF LOADING ZONE
 SPACE, OR FRACTION THEREOF. FBC A 503.2 VEHICLE PULL-UP
 SPACE.
 PASSENGER LOADING ZONES SHALL PROVIDE A VEHICULAR
 PULL-UP SPACE 96 INCHES (2440 MM) WIDE MINIMUM AND 20
 FEET (6100 MM) LONG MINIMUM.