2022-09-26 14:18:38 | NEW HI RISE OFFICE BLDG. |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| |
| 1) GROUND FLOOR AND MEZZANINE PARKING - PLEASE SHOW |
| PARKING GARAGE OPEN OR CLOSED AND PROVIDE THE |
| CALCULATIONS (EACH TIER) FOR THE OPEN GARAGE FBC |
| 406.5.2 OPENINGS. |
| FOR NATURAL VENTILATION PURPOSES, THE EXTERIOR SIDE OF |
| THE STRUCTURE SHALL HAVE UNIFORMLY DISTRIBUTED OPENINGS |
| ON TWO OR MORE SIDES. THE AREA OF SUCH OPENINGS IN |
| EXTERIOR WALLS ON A TIER SHALL BE NOT LESS THAN 20 |
| PERCENT OF THE TOTAL PERIMETER WALL AREA OF EACH TIER. |
| THE AGGREGATE LENGTH OF THE OPENINGS CONSIDERED TO BE |
| PROVIDING NATURAL VENTILATION SHALL BE NOT LESS THAN 40 |
| PERCENT OF THE PERIMETER OF THE TIER. INTERIOR WALLS |
| SHALL BE NOT LESS THAN 20 PERCENT OPEN WITH UNIFORMLY |
| DISTRIBUTED OPENINGS. |
| |
| 2) BUILDING SOUTH ELEVATION - PLEASE SHOW THE ALLOWABLE |
| EXTERIOR WALL OPENING PROTECTION CALCULATIONS (EACH |
| STORY) ( SOLID WALLS VS DOOR, LOUVERS, OPEN AREAS AT |
| GARAGE AND WINDOWS ETC.) PER FBC 705.8.1 ALLOWABLE AREA |
| OF OPENINGS. |
| THE MAXIMUM AREA OF UNPROTECTED AND PROTECTED OPENINGS |
| PERMITTED IN AN EXTERIOR WALL IN ANY STORY OF A |
| BUILDING SHALL NOT EXCEED THE PERCENTAGES SPECIFIED IN |
| TABLE 705.8. |
| |
| 3) BUILDING WEST ELEVATION - GROUND FLOOR SHOWS A DOOR, |
| LOUVERS WHICH ARE NOT SHOWN ON YOUR CALCULATIONS. - |
| (EACH STORY) PLEASE SHOW THE ALLOWABLE EXTERIOR WALL |
| OPENING PROTECTION CALCULATIONS ( SOLID WALLS VS DOOR, |
| LOUVERS, OPEN AREAS AT GARAGE AND WINDOWS ETC.) PER FBC |
| 705.8.1 ALLOWABLE AREA OF OPENINGS. |
| THE MAXIMUM AREA OF UNPROTECTED AND PROTECTED OPENINGS |
| PERMITTED IN AN EXTERIOR WALL IN ANY STORY OF A |
| BUILDING SHALL NOT EXCEED THE PERCENTAGES SPECIFIED IN |
| TABLE 705.8. |
| |
| 4) ELEVATOR HOISTWAY FOR ELEVATOR #3 AND #4 REQUIRES |
| HOISTWAY PROTECTION ( A SINGLE SHAFT WHICH APPEARS TO |
| RUN FROM GROUND TO THE 11TH FLOOR) FBC 3006.2 |
| |
| 5) DRAWING LS.20.1 - DETAIL 2 - SHOULD SAY EAST TO |
| WEST. |
| |
| 6) PLEASE SHOW THE PASSENGER LOADING LOCATIONS PER FBC |
| ACCESSIBILITY 209.2.1 PASSENGER LOADING ZONES. |
| PASSENGER LOADING ZONES, EXCEPT THOSE REQUIRED TO |
| COMPLY WITH 209.2.2 AND 209.2.3, SHALL PROVIDE AT LEAST |
| ONE PASSENGER LOADING ZONE COMPLYING WITH 503 IN EVERY |
| CONTINUOUS 100 LINEAR FEET (30 M) OF LOADING ZONE |
| SPACE, OR FRACTION THEREOF. FBC A 503.2 VEHICLE PULL-UP |
| SPACE. |
| PASSENGER LOADING ZONES SHALL PROVIDE A VEHICULAR |
| PULL-UP SPACE 96 INCHES (2440 MM) WIDE MINIMUM AND 20 |
| FEET (6100 MM) LONG MINIMUM. |