2022-06-10 14:05:33 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22050714 |
| 6/8/9/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET LS.0.0: PROVIDE ON THE PLANS A LIST OF |
| SEPARATE PERMITS INCLUDING, BUT NOT LIMITED TO- POTABLE |
| WATER SERVICE AND FIRE LINE BACKFLOW PREVENTERS, FIRE |
| LINE, FIRE SPRINKLERS, FIRE PUMP, GREASE INTERCEPTOR, |
| THE WATER FEATURE, AND THE EMERGENCY GENERATOR. |
| |
| PLEASE NOTE DUE TO A CHANGE IN PROCESS, THE BACKFLOW |
| AND GREASE INTERCEPTOR PERMITS ARE REQUIRED TO BE |
| SUBMITTED PRIOR TO ISSUANCE OF THE PRIMARY PERMIT. YOU |
| CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF |
| YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A |
| COMPLETED PERMIT APPLICATION TO [email protected] |
| . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD |
| PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE |
| DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE |
| RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE |
| SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED, |
| NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS |
| TO PASS. |
| |
| 2) LS.0.0, A1.1.1, P1.01, & P1.1.1- GROUND PLUMBING |
| FIXTURE CALCULATIONS: |
| A) WHAT DOES THE SYMBOL 1(X4) INDICATE? IT IS SHOWN AS |
| THE PROVIDED NUMBER OF WATER CLOSETS AND LAVATORIES FOR |
| THE GROUND FLOOR. IS THIS SUPPOSED TO BE A (*4) SYMBOL |
| AS SHOWN IN THE FOOTNOTES? |
| B) THE CALCULATIONS DO NOT INCLUDE THE OCCUPANTS OF THE |
| LOBBY OR THE TERRACE- TABLE 403.1 FBC P. |
| C) THE CAFE APPEARS TO BE MISLABELED AS KITCHEN. A CAFE |
| TYPICALLY HAS SPACE FOR DINING AND/OR WAITING AND THE |
| PLAN APPEARS TO SHOW THE AREA WILL ACCOMMODATE MORE |
| THAN JUST 2 OCCUPANTS. PLEASE LABEL THE PLANS ACCORDING |
| TO THE USE OF THE SPACE AND REVISE THE FIXTURE |
| CALCULATIONS PER TABLE 403.1 FBC P. |
| D) ONE SINGLE OCCUPANT TOILET ROOM (115) IS SHOWN THE |
| GROUND FLOOR PLANS WHICH WILL NOT PROVIDE THE REQUIRED |
| NUMBER OF PLUMBING FIXTURES FOR THE OCCUPANTS OF ALL |
| THE GROUND FLOOR AREAS AND USES. NO INFORMATION FOR |
| FUTURE RESTROOMS HAS BEEN PROVIDED IN THE FOOTNOTES- |
| TABLE 403.1 FBC P. |
| E) PLEASE SEE SECS. 403.2 & 403.3 AND IDENTIFY TOILET |
| ROOM (115) AS MALE, FEMALE OR UNISEX, AND ALSO INDICATE |
| PUBLIC OR EMPLOYEE USE OR BOTH. THE PLAN SHOWS PUBLIC |
| ACCESS TO THE TOILET ROOM WOULD BE THROUGH A SERVICE |
| CORRIDOR WHICH APPEARS TO BE NON-COMPLIANT WITH SEC. |
| 403.3.1 FBC P. |
| G) THE FOOTNOTES INDICATE FUTURE DRINKING FOUNTAIN BUT |
| NOT THE REQUIRED SERVICE SINK. PLEASE PROVIDE THE |
| LOCATION OF THE FIXTURE ON THE PLANS- TABLE 403.1 FBC |
| P. |
| H) PLEASE PROVIDE A TARGET NOTE AT ADA (115) THAT |
| REFERENCES THE PLAN SHEET WHERE ENLARGED FBC ACC |
| DRAWINGS AND DETAILS ARE PROVIDED- SEC. 107.2.1 WPB. |
| |
| 3) LS.0.0, A1.7.1 & P1.7.1: PLEASE SHOW THE PROVIDED |
| NUMBER OF FIXTURES IN THE SCHEDULE FOR THE 6TH FLOOR- |
| TABLE 403.1 FBC P. THE FIXTURE CALCULATIONS SHOW 5 |
| WATER CLOSETS EACH REQUIRED FOR MALE AND FEMALE USE |
| HOWEVER THE FLOOR PLANS SHOW ONLY 3 FOR EACH HAS BEEN |
| PROVIDED- TABLE 403.1 FBC P. |
| A) PLEASE LABEL THE TOILET ROOMS AS EITHER MALE OR |
| FEMALE IN ACCORDANCE WITH SECTION 403.2 FBC P. |
| B) SHOW THE LOCATION OF THE REQUIRED DRINKING FOUNTAINS |
| ON THE PLANS AND PROVIDE PLUMBING PIPING DETAILS- TABLE |
| 403.1 FBC P. PLEASE NOTE THE DRINKING FOUNTAINS SHALL |
| BE ACCESSIBLE IN ACCORDANCE WITH SECS. 211.1 & 602.1 |
| FBC ACC. |
| C) A9.1.3: PLEASE CLEARLY SHOW THE CLEAR FLOOR SPACE |
| DIAGRAMS AND DIMENSIONS FOR THE ACCESSIBLE WATER |
| CLOSETS, LAVATORIES, AND SHOWERS- SECS. 604.3 & 606.2 |
| FBC ACC. |
| D) A9.1.3: PROVIDE A DETAIL SHOWING THE HEIGHTS OF THE |
| ACCESSIBLE LAVATORY SINK RIMS OR COUNTER SURFACES FROM |
| THE FINISHED FLOORS- SEC. 606.3. |
| E) A9.1.3: PROVIDE A DETAIL SHOWING THE KNEE AND TOE |
| CLEARANCES FOR THE ACCESSIBLE LAVATORIES- SEC. 606.2. |
| F) A9.1.3: SHOW THE WIDTH AND DEPTH MEASUREMENTS OF THE |
| ROLL IN SHOWERS- SEC. 608.2.2 |
| G) A9.1.3: SHOW THE HEIGHTS OF THE SHOWER CONTROLS, |
| FAUCETS AND SHOWER SPRAY UNIT MEASURED FROM THE |
| FINISHED FLOORS OF THE SHOWERS- SEC. 608.5.2. |
| H) A.9.1.3: PROVIDE A THRESHOLD DETAIL- SEC. 608.7. |
| |
| 4) A1.8.1- A1.11.1 & P1.8.1- P1.11.1: SHOW THE |
| LOCATIONS OF THE REQUIRED DRINKING FOUNTAINS ON THE |
| PLANS AND PROVIDE PLUMBING PIPING DETAILS- TABLE 403.1 |
| FBC P. PLEASE NOTE THE DRINKING FOUNTAINS SHALL BE |
| ACCESSIBLE IN ACCORDANCE WITH SECS. 211.1 & 602.1 FBC |
| ACC. |
| |
| 5) A9.2.1: SEC. 213.2(4) FBC ACC REQUIRES A MINIMUM OF |
| 50% OF THE CLUSTERED TOILET ROOMS TO BE ACCESSIBLE. THE |
| PLAN APPEARS TO SHOW 33.3% |
| |
| 6) A9.2.1: PLEASE PROVIDE THE FOLLOWING DETAILS FOR THE |
| ACCESSIBLE TOILET ROOMS PER FBC ACC. |
| A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| WATER CLOSETS- SEC. 604.3. |
| B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE |
| LAVATORIES- SEC. 606.2. |
| C) TURNING SPACE DIAMETERS- SEC. 304.3. |
| D) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| FROM THE FINISHED FLOOR- SEC. 606.3. |
| E) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SEC. |
| 606.2 |
| |
| 7) SHEETS C4.1 & P1.0.1: THE CIVIL PLAN SHOWS AN 8-INCH |
| SANITARY BUILDING DRAIN, AND THE PLUMBING PLAN SHOWS A |
| 6-INCH DRAIN. PLEASE CORRECT- SEC. 107.2.1 WPB. |
| |
| 8) P1.01: PLACE A KEYNOTE AT THE SANITARY SEWER/WATER |
| SERVICE PIPE CROSSOVER POINT INDICATING A SLEEVE WILL |
| BE PROVIDED, AND PROVIDE A DETAIL FOR THE SLEEVE- SEC. |
| 603.2 FBC P. |
| |
| 9) P1.01: PROVIDE FILL AND SUPPORT DETAILS FOR THE |
| SANITARY/STORM PIPE AND STORM/SANITARY PIPE CROSSOVERS |
| (NOTES 14 & 15)- SEC. 703.3 FBC P. |
| |
| 10) P1.01, P4.02: IT APPEARS THE ELEVATOR SUMP PUMP |
| DISCHARGES FROM (SP-1 & SP-2) WILL BE INDIRECTLY |
| DRAINING INTO THE HD-1. PLEASE PROVIDE A KEYNOTE OR |
| DETAIL TO IDENTIFY THE LOCATION- SEC. 3002.9 FBC B, AND |
| SECS. 712.3- 712.3.5 FBC P. SHOW THE INDIRECT WASTE |
| RECEPTOR FOR SP-3. |
| |
| 11) P1.01, P6.0.1: THE PLAN SHOWS BACKWATER VALVES FOR |
| THE UNDERGROUND STORM DRAINS. PLEASE INCLUDE THE VALVES |
| IN THE SCHEDULE AND PROVIDE AN INSTALLATION DETAIL. IT |
| APPEARS THE VALVES WILL NEED TO BE PROTECTED FROM |
| VEHICULAR DAMAGE WITH HEAVY DUTY TRAFFIC LID COVERS- |
| SECS. 305.7 & 714.1 FBC P |
| |
| 12) P1.01: PROVIDE A NOTE AT THE EMERGENCY FLOOR DRAINS |
| INDICATING THE TYPE OF TRAP SEAL PROTECTION TO BE |
| PROVIDED- SEC. 1002.4.1.1. PLEASE NOTE THAT |
| MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| GUIDELINES TYPICALLY PROHIBIT BARRIER-TYPE TRAPS TO BE |
| USED ON GREASE LADEN FLOORS- SEC. 1002.4.1.4 FBC P. |
| |
| 13) P1.01 & C3.2: SHOW THE MAIN 10-INCH STORM DRAIN |
| PIPING CONTINUATIONS TO THE APPROVED PLACES OF |
| DISPOSAL- SEC. 1101.2 FBC P. |
| |
| 14) P1.01: THE WATER FEATURE IS UNDER A SEPARATE PERMIT |
| HOWEVER THE CURRENT PLAN DOES NOT SHOW THE WATER |
| FEATURE WASTEWATER DRAINAGE AND DISCHARGE LOCATION. |
| PLEASE BE ADVISED THAT THE WASTEWATER SHALL NOT |
| DISCHARGE INTO THE SANITARY SYSTEM IN ACCORDANCE WITH |
| SEC. 90-126(5) WPB CODE OF ORDINANCES. REVIEW THE |
| INFORMATION BELOW: |
| |
| SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S |
| SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW |
| AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO |
| KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| INLET). |
| NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| INLET TO DISCHARGE EFFLUENT. |
| WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE ALLOWED |
| TO FILTER THROUGH GRASS AREA ON THE POOL OWNER'S |
| PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| PROPERTY. |
| FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT |
| STEPHON HARRIS AT [email protected] OR 561-822-2168. |
| FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE |
| CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| 822-2062 OR [email protected]. |
| |
| 15) P1.0.1: PLEASE RELOCATE THE DRAINAGE FROM THE FLOOR |
| DRAIN IN THE OUTDOOR STORAGE TO THE STORM SYSTEM- SEC. |
| 90-126(5) WPB CODE OF ORDINANCES. REPLACE THE FD WITH |
| AN AD. |
| |
| 16) P1.01 FOUNDATION- P1.12.1 11TH FLOOR: WFU SYMBOLS |
| ARE SHOWN CLEARLY ON THE PLAN, HOWEVER THERE ARE MANY |
| OVAL AND CIRCLED NUMBER SYMBOLS THAT ARE NOT LABELED. |
| SOME APPEAR TO BE INDICATING DFU'S. PLEASE LABEL THE |
| SYMBOLS- SEC. 107.2.1 WPB. |
| |
| 17) P1.01 NOTE 1: INDICATE THE TYPE OF BACKFLOW |
| PREVENTER ASSEMBLY TO BE INSTALLED- SEC. 608.3 FBC P, |
| AND SECS. C, D, & E WPB CROSS-CONNECTION CONTROL |
| MANUAL. PLEASE PROVIDE AN EQUIPMENT SCHEDULE AND NOTE |
| THAT IT SHALL BE INSTALLED UNDER A SEPARATE PERMIT- |
| REFERENCE COMMENT #1 ABOVE. |
| |
| 18) P1.1.5M NOTE 11, P4.1.1: PROVIDE FULL-OPEN SHUT OFF |
| VALVES AT THE BASES OF THE 2-INCH AND 3-INCH WATER |
| RISERS- SEC. 606.1(4) FBC P. |
| |
| 19) P5.01 DETAIL 7: SHEETS P1.7.1- P1.12.1 SHOW THE |
| MASTER TMV'S AND PIPING CONNECTIONS IN THE WATER HEATER |
| DETAIL AND IN THE RISER DRAWINGS- SEC. 607.2.2 FBC P. |
| A) PROVIDE HW AND HWR PIPING INSULATION DETAILS- TABLE |
| C403.2.10 FBC EC. |
| |
| 20) P1.7.1: PLEASE INCLUDE AP-1 IN THE PLUMBING FIXTURE |
| SCHEDULE- SEC. 107.2.1 WPB. |
| |
| 21) P1.7.1 & A9.1.3: PROVIDE ACCESSIBILITY DETAILS FOR |
| THE BFS-1- SEC. 211.2 FBC ACC. PLEASE SHOW THE CLEAR |
| FLOOR SPACE DIAGRAM AND DIMENSIONS FOR FORWARD OR SIDE |
| APPROACH TO THE STATION, AND AN ELEVATION DETAIL |
| SHOWING COMPLIANCE WITH SECS. 306, 308, & 309. SUBMIT |
| MANUFACTURER'S SPECIFICATIONS FOR THE STATION. |
| |
| 22) P1.7.1- P1.12.1, P4.1.1, P4.1.2, P4.1.3, P4.1.4: |
| INDICATE HOW TEMPERED WATER WILL BE DELIVERED FROM THE |
| LAVATORIES- SEC. 419.5 FBC P. PLEASE NOTE MIXING VALVES |
| FOR TEMPERED WATER SHALL BE ASSE 1070 APPROVED- SEC. |
| 607.1.2. |
| |
| 23) P1.7.1- P1.12.1: PROVIDE TRAP SEAL PROTECTION FOR |
| THE FLOOR DRAINS- SEC. 1002.4.1.1 FBC P. |
| |
| 24) P1.9.1, P1.11.1, P6.01: INDICATE THE TYPE OF |
| BACKFLOW ASSEMBLIES (BFP-1) TO BE INSTALLED AND VERIFY |
| ACCESS WILL BE PROVIDED TO THE DEVICES- TABLE 608.3 FBC |
| P. REFER TO COMMENT #1 ABOVE AND PLACE A NOTE |
| INDICATING A SEPARATE PERMIT WILL BE REQUIRED- SEC. |
| 105.1 & 107.2.1 WPB. |
| |
| 25) P1.12.1, P2.01: THE PLAN APPEARS TO SHOW FD-2 WILL |
| BE DRAINING ROOF RUNOFF/STORMWATER INTO THE SANITARY |
| SYSTEM WHICH IS PROHIBITED- SEC. 90-126(5) WPB CODE OF |
| ORDINANCES. |
| |
| 26) P1.12.1, P2.01, P4.2.1, P.4.2.2: THE STORM RISER |
| APPEARS TO SHOW AREAS H & I (204 GPM) DRAINING INTO A |
| 4-INCH VERTICAL DRAIN PIPE WHICH IS UNDERSIZED PER |
| TABLE 1106.2 FBC P. TO HELP EXPEDITE THE REVIEW ON |
| P4.2.1 PLEASE THE LABEL THE DRAINAGE AREAS SERVED AND |
| GPM FLOW AT THE TOP OF EACH INDIVIDUAL RISER, AND THE |
| ACCUMULATIVE GPM FLOW AT BASES OF THE RISERS. ON |
| P.4.2.2 PLEASE SHOW THE GPM CONTINUATIONS FROM ABOVE |
| AND THE TOTALS AT THE HORIZONTAL MAINS- SEC. 107.2.1 |
| WPB. |
| A) PLEASE PROVIDE RD-1 & 2 INSTALLATION DETAILS AND |
| SUBMIT MANUFACTURER'S SPECIFICATIONS- SEC. 1105.1 FBC |
| P. |
| B) PROVIDE THE SLOPE OF THE HORIZONTAL STORM PIPING- |
| TABLE 1106.2. |
| |
| 27) P4.01, P4.02, P4.03, P4.04: VENT STACKS ARE |
| REQUIRED FOR THE CORE DRAINAGE STACKS AND THE FUTURE |
| TENANT STACKS- SEC. 904.2 FBC P. THE STACKS SHALL |
| CONNECT AT THE BASES OF THE DRAINAGE STACKS- SEC. |
| 904.4. THE RISER VENTING APPEARS TO BE NON-COMPLIANT. |
| A) CONCERNING THE 4-INCH STACKS FOR THE FUTURE TENANTS, |
| STACK-TYPE AIR ADMITTANCE VALVES SHALL BE PROHIBITED |
| FROM SERVING AS THE VENT TERMINALS FOR VENT STACKS OR |
| STACK VENTS THAT SERVE DRAINAGE STACKS HAVING MORE THAN |
| SIX BRANCH INTERVALS- SEC. 918.3.2 FBC P. |
| |
| 28) P1.01, P1.8.1, P1.10.1, P4.03, P4.04: PA-1 VALVES |
| ARE SHOWN ON THE CORE RISERS AT THE 1ST, 7TH, AND 9TH |
| LEVELS. PLEASE SHOW THEIR LOCATIONS ON SHEETS P.01, |
| P1.8.1 & P1.10.1 AND VERIFY ACCESS WILL BE PROVIDED- |
| SEC. 918.5 FBC P. |
| A) PLEASE EXPLAIN THE PURPOSES OF THE PA-1 VALVE |
| INSTALLATIONS ON THE CORE SANITARY STACKS- SEC. 107.2.1 |
| WPB. |
| |
| 29) P1.7.1, P1.11.1: SHOW THE LOCATIONS OF THE PA-1 AND |
| SV-1 VALVES AND VERIFY THAT ACCESS WILL BE PROVIDED- |
| SEC. 918.5 FBC P. PLEASE EXPLAIN THE PURPOSES OF THE |
| PA-1 VALVE INSTALLATIONS ON THE FUTURE TENANT STACKS- |
| SEC. 107.2.1 WPB. |
| |
| 30) P2.01, P4.03, P4.04: PLEASE SHOW THE LOCATIONS OF |
| THE VENT STACK TERMINATIONS ON THE ROOF PLAN- SEC 904.3 |
| FBC P. |
| |
| 31) P4.02, P6.01: THE SE-50 LABEL AT THE FPL SUMP PIT |
| (SP-3) DOES NOT MATCH THE FIXTURE SCHEDULE- PLEASE |
| CORRECT- SEC. 107.2.1 WPB. |
| |
| 32) P2.01: SHOW THE 2-INCH WATER RISER LOCATION FOR THE |
| SUPPLY LINE TO THE CHILLER, AND THE TYPE OF BACKFLOW |
| PREVENTER TO BE INSTALLED TO PROTECT THE POTABLE WATER- |
| SEC. 608.3 FBC P, AND SECS. C, D, & E WPB CROSS- |
| CONNECTION CONTROL MANUAL. REFER TO COMMENT #1 FOR |
| PERMITTING REQUIREMENTS. |
| |
| 33) DEFERRED SUBMITTALS: PLEASE PROVIDE A LIST OF |
| DEFERRED SUBMITTALS INCLUDING, BUT NOT LIMITED TO WATER |
| HEATERS, EXPANSION TANKS, RECIRCULATION PUMPS, SUMP |
| PUMPS, MASTER AND POINT OF USE THERMOSTATIC MIXING |
| VALVES, TEMPERED WATER MIXING VALVES, INLINE BACKFLOW |
| PREVENTERS, TRAP PRIMERS, WATER HAMMER ARRESTORS, |
| ACCESSIBLE PLUMBING FIXTURES, AND ROOF AND OVERFLOW |
| DRAINS- SEC. 107.3.4.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |