Notes
Date Text
2022-06-07 12:42:41THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SMOKE CONTROL RATIONAL ANALYSIS AND SEQUENCE OF
 OPERATION ARE NOT ATTACHED
  
 NFPA 101 CH 11
  
 11.8.2.3 ALL NEW VERTICAL EXIT ENCLOSURES SERVING THE
 HIGH-RISE PORTION
 OF THE BUILDING SHALL BE SMOKEPROOF ENCLOSURES IN
 ACCORDANCE WITH 7.2.3.
  
 9.3 SMOKE CONTROL
 9.3.1 INSTALLATION. WHERE REQUIRED BY ANOTHER SECTION
 OF THIS CODE,
 SMOKE CONTROL SYSTEMS SHALL BE DESIGNED, INSTALLED,
 INSPECTED, TESTED,
 AND MAINTAINED IN ACCORDANCE WITH NFPA 92, NFPA 204, OR
 NATIONALLY
 RECOGNIZED STANDARDS, ENGINEERING GUIDES, OR
 RECOMMENDED PRACTICES,
 AS APPROVED BY THE AUTHORITY HAVING JURISDICTION
  
 PLEASE PROVIDE SPECIFIC DETAILS.
  
  
  
 2) SHEET LS 01.1 - THE FIRE COMMAND CENTER DOES NOT
 HAVE ACCESS FROM AN EXTERIOR WALL.
  
 THE FIRE COMMAND CENTER SHOULD HAVE DIRECT UNIMPEDED
 ACCESS FROM AN EXTERIOR WALL AND IN A LOCATION APPROVED
 BY THE AHJ
  
 PER NFPA 101 CH 11
  
 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED
 IN A LOCATION
 APPROVED BY THE FIRE DEPARTMENT.
  
  
 PLEASE REVIEW AND CORRECT WITH COORDINATION WITH THE
 OFFICE OF THE FIRE MARSHAL.
  
  
  
 3) SHEET LS 01.1 - THERE IS AN INDICATION OF EXIT
 TRAVEL ACCESS DOOR THROUGH AN OUTDOOR STORAGE AREA, #
 113 AND OUTDOOR TERRACE # 112
  
 IT DOES INDICATE THAT AREA LEADS TO A PUBLIC WAY NOR
 EXIT SIGNAGE FROM THAT AREA.
  
 PER NFPA 101 CH 7
  
 7.5 ARRANGEMENT OF MEANS OF EGRESS
 7.5.1 GENERAL.
 7.5.1.1 EXITS SHALL BE LOCATED, AND EXIT ACCESS SHALL
 BE ARRANGED, SO THAT
 EXITS ARE READILY ACCESSIBLE AT ALL TIMES.
 7.5.1.1.1* WHERE EXITS ARE NOT IMMEDIATELY ACCESSIBLE
 FROM AN OPEN
 FLOOR AREA, CONTINUOUS PASSAGEWAYS, AISLES, OR
 CORRIDORS LEADING DIRECTLY
 TO EVERY EXIT SHALL BE MAINTAINED AND SHALL BE ARRANGED
 TO PROVIDE ACCESS
 FOR EACH OCCUPANT TO NOT LESS THAN TWO EXITS BY
 SEPARATE WAYS OF TRAVEL,
 UNLESS OTHERWISE PROVIDED IN 7.5.1.1.3 AND 7.5.1.1.4
  
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY VISIBLE
 SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE
 EXIT IS NOT READILY
 APPARENT TO THE OCCUPANTS
  
 7.7 DISCHARGE FROM EXITS
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC
 WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE
 PROVIDED IN 7.7.1.2
 THROUGH 7.7.1.4.
  
  
 PLEASE REVIEW AND CORRECT OR BETTER DEFINE THE EIXT
 PATH TO THE PUBLIC WAY.
  
  
 3A) SHEET LS 01.1 - THERE IS AN INDICATION OF EXIT
 STAIRS INTO THE OUTDOOR TERRACE # 112
  
 THE EXIT STARI DISCHARGE IS TO LEAD TO A PUBLIC WAY OR
 TO A PROTECTED AREA LEADING TO A PUBLIC WAY.
  
 IT DOES INDICATE THAT AREA LEADS TO A PUBLIC WAY NOR
 EXIT SIGNAGE FROM THAT AREA.
  
 PER NFPA 101 CH 7
  
 7.2.3.5 DISCHARGE.
 7.2.3.5.1 EVERY SMOKEPROOF ENCLOSURE SHALL DISCHARGE
 INTO A PUBLIC WAY,
 INTO A YARD OR COURT HAVING DIRECT ACCESS TO A PUBLIC
 WAY, OR INTO AN EXIT
 PASSAGEWAY. SUCH EXIT PASSAGEWAYS SHALL BE WITHOUT
 OPENINGS, OTHER
 THAN THE ENTRANCE TO THE SMOKEPROOF ENCLOSURE AND THE
 DOOR OPENING TO
 THE OUTSIDE YARD, COURT, OR PUBLIC WAY. THE EXIT
 PASSAGEWAY SHALL BE
 SEPARATED FROM THE REMAINDER OF THE BUILDING BY A
 2-HOUR FIRE RESISTANCE
 RATING.
 7.2.3.5.2 THE SMOKEPROOF ENCLOSURE SHALL BE PERMITTED
 TO DISCHARGE
 THROUGH INTERIOR BUILDING AREAS, PROVIDED THAT ALL OF
 THE FOLLOWING CRITERIA
 ARE MET:
 (1) THE BUILDING SHALL BE PROTECTED THROUGHOUT BY AN
 APPROVED, SUPER VISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7.
 (2) THE DISCHARGE FROM THE SMOKEPROOF ENCLOSURE SHALL
 LEAD TO A FREE
 AND UNOBSTRUCTED WAY TO AN EXTERIOR EXIT, AND SUCH WAY
 SHALL BE
 READILY VISIBLE AND IDENTIFIABLE FROM THE POINT OF
 DISCHARGE FROM
 THE SMOKEPROOF ENCLOSURE.
 (3) NOT MORE THAN 50 PERCENT OF THE REQUIRED NUMBER AND
 CAPACITY OF
 EXITS COMPRISED OF SMOKEPROOF ENCLOSURES SHALL
 DISCHARGE THROUGH
 INTERIOR BUILDING AREAS IN ACCORDANCE WITH 7.7.2.
  
 7.7 DISCHARGE FROM EXITS
 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE
 DIRECTLY, AT A PUBLIC
 WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE
 PROVIDED IN 7.7.1.2
 THROUGH 7.7.1.4.
  
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY VISIBLE
 SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE
 EXIT IS NOT READILY
 APPARENT TO THE OCCUPANTS
  
 PLEASE REVIEW AND CORRECT OR BETTER DEFINE THE EIXT
 PATH TO THE PUBLIC WAY.
  
  
  
  
  
 4) THERE ARE INDICATIONS OF CARD READERS/ACCESS CONTROL
 THROUGHOUT THE OCCUPANCY.
  
 ALL CARD READER/ACCESS CONTROL SHALL BE INSTALLED UNDER
 SEPARATE PERMIT & SHOP DRAWINGS AND COMPLY WITH NFPA
 101, CH 7 AS APPLICABLE.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT ON
 THE LIFE SAFETY & ELECTICAL NOTE SHEETS.
  
  
  
  
 5) SHEET LS 06.1 - THERE IS EXIT DOOR (STAIR B) FROM
 THE PARKING GARAGE ENTERING INTO THE EXIT PASSAGE WAY.
 TO AVOID EXIT CONFUSION THERE SHOULD BE A SING ON THE
 WALL OPPOSITE THAT EXIT DOOR STATING EXIT DOWN(OR
 EQUAL) WITH AN ARROW POINTING IN THE DIRECTION OF THE
 STAIR.
  
 PER NFPA 101 CH 7 MEANS OF EGRESS
  
 7.10.1.5 EXIT ACCESS.
 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED,
 READILY VISIBLE
 SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE
 EXIT IS NOT READILY
 APPARENT TO THE OCCUPANTS
  
 THIS WOULD REDUCE THE CONFUSION OF GOING THE WRONG WAY
 DOWN THE EXIT PASSAGE WAY AND UP TO ANOTHER FLOOR
 LEVEL.
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT ON
 THE LIFE SAFETY SHEET.
  
  
  
 6) SHEET LS 08.1 - THERE APPEARS TO BE A SINGLE
 EXIT/SIGN FROM THE COMMON TERRACE # 813 AREA.
  
 AS THIS IS AN ASSEMBLY OCCUPANCY SPACE, TWO EXITS ARE
 REQUIRED PER NFPA 101, CH 12 & CH 7 REMOTELY LOCATED
 FROM EACH OTHER.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC
 NARRATIVE AND CODE REFERENCES.
  
  
  
  
 7) SHEET E 1.1.3 & E 4.0.2 - THE ARE INDICATIONS OF
 FAAP HOWEVER, THERE IS NO INDICATION OF THE FACP THAT
 IS REQUIRED TO BE THE FIRE COMMAND CENTER
  
 SHEET E 4.0.2 SHOWS LIMITED EQUIPMENT.
  
 PER NFPA 1 & 101
  
 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY
 COMMAND CENTER.
  
 (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT.
  
 11.8.6* EMERGENCY COMMAND CENTER.
  
 (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION
 PANELS
  
 PLEASE REVIEW AND CORRECT OR PROVIDE A NOTE OF
 ACKNOWLEDGMENT
  
  
  
 7A) SHEET E 1.1.3 - THERE ARE NO INDICATIONS OF ANY
 EQUIPMENT WITHIN THE FIRE COMMAND CENTER.
  
 THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1,
 CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN
 THE FOLLOWING FEATURES:
 11.9.1 THE LOCATION, DESIGN, CONTENT, AND FIRE
 DEPARTMENT ACCESS OF THE EMERGENCY COMMAND CENTER SHALL
 BE APPROVED BY THE FIRE DEPARTMENT.
  
 11.9.2 THE EMERGENCY COMMAND CENTER SHALL BE SEPARATED
 FROM THE REMAINDER OF THE BUILDING BY A FIRE BARRIER
 HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 1
 HOUR.
  
 11.9.3 THE EMERGENCY COMMAND CENTER ROOM SHALL BE A
 MINIMUM OF 200 FT2 (19 M2) WITH A MINIMUM DIMENSION OF
 10 FT (3050 MM).
  
 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY
 COMMAND CENTER.
 (1) THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM.
 (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE PUBLIC TELEPHONE SYSTEM
 (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL
 FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF
 EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING
 EQUIPMENT AND FIRE DEPARTMENT ACCESS
 (4) WORK TABLE.
 (5) IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN
 FOR THE BUILDING.
 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING DEVICES
 OR FUNCTIONS SHALL BE PROVIDED WITHIN THE EMERGENCY
 COMMAND CENTER.
 (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM
 CONTROL UNIT.
 (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT.
 (3) ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION
 OF THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL
 (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING
 SYSTEMS.
 (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS
 SIMULTANEOUSLY
 (6) SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY
 PANELS
 (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS
 (8) FIRE PUMP STATUS INDICATORS
 (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND
 TRANSFER FEATURES.
 (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED
 BY OTHER SECTIONS OF THIS CODE
 (11) CONTROLS REQUIRED FOR SMOKE CONTROL
  
 NFPA 101
  
 11.8.6* EMERGENCY COMMAND CENTER.
 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED
 IN A
 LOCATION APPROVED BY THE FIRE DEPARTMENT.
 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE
 FOLLOWING:
 (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS
 (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION
 SERVICE
 PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION
 OF THIS
 CODE
 (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION
 PANELS
 (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS
 (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME
 A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS
 (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE
 PROVIDED
 IN ACCORDANCE WITH ASME A17.1/CSA B44
 (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS
 (8) EMERGENCY GENERATOR STATUS INDICATORS
 (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING
 SYSTEM
 (10) FIRE PUMP STATUS INDICATORS
 (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED
 ACCESS TO THE
 PUBLIC TELEPHONE SYSTEM
 (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY
 11.8.8
  
 PLEASE REVIEW AND ENSURE COMPLIANCE TO INSTALL.
  
 PROVIDE A NOTE OF ACKNOWLEDGMENT
  
  
  
 8) SHEET E 6.0.5 - THERE ARE INDICATIONS OF A BDA TYPE
 2-WAY COMMUNCATIONS SYSTEM.
  
 ANY BDA SYSTEM SHALL BE INSTALLED UNDER SEPARATE
 PERMIT.
  
 THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL
 STRENGTH OF THE RADIO SYSTEM USED BY WEST PALM BEACH
 FIRE DEPARTMENT. TESTING SHALL BE BY AN ACCEPTABLE
 NATIONAL STANDARD DOCUMENTING PERCENTAGES NOTED ABOVE
 AND BY ACTUAL RADIO TESTING BY FIRE PERSONNEL. IF THE
 MINIMUM CANNOT BE MAINTAINED, A BI-DIRECTIONAL
 AMPLIFIED SYSTEM SHALL BE INSTALLED WITH A MINIMUM
 2-HOUR RUN TIME BATTERY BACK-UP.
  
 HOWEVER, A SYSTEM MAY NOT BE REQUIRED.
  
 PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC
 SAFETY RADIO SYSTEMS MANAGER, [email protected],
 561-233-0837; AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR
 DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS.
  
 BEFORE SUBMITTING FOR A PERMIT, PLEASE PROVIDE ALL THE
 TESTING DATA TO MR. FILLA AND THE OFFICE OF THE FIRE
 MARSHAL FOR REVIEW.
  
 PROVIDE A NOTE OF ACKNOWLEDGMENT
  
  
 9) SHEET E 0.1.1 - THERE ARE INDICATIONS OF A FIRE
 ALARM SYSTEM AND EQUIPMENT.
  
 THE FIRE ALARM SYSTEM SHALL BE MAINTAINED THROUGHOUT
 DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE ALARM, SHALL BE DONE UNDER
 SEPARATE PERMITS & SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT
  
  
  
 10) SHEET F 0.0.1 - THERE ARE INDICATIONS OF A FIRE
 SPRINKLER SYSTEM AND EQUIPMENT.
  
 THE FIRE SPRINKLER SYSTEM SHALL BE MAINTAINED
 THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKER SYSTEM, SHALL BE DONE
 UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
 PER NFPA 14
 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED
 NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE
 HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT
  
  
  
 11) SHEET E 5.0.1 - THERE IS AN INDICATION OF A
 GENERATOR EXHAUST PIPING DIAGRAM.
  
 PER NFPA 110 AND 37
  
 PLEASE CONFIRM THE GENERATOR CLASS/TYPE, FUEL SOURCE
 AND THAT THE ELECTRIC FIRE PUMP IS CONNECTED TO THE
 GENERATOR WITH AN AUTOMATIC TRANSFER SWITCH.
  
  
  
 11A) PER NFPA 110 AND 37, PLEASE ENSURE THAT THE
 GENERATOR EXHAUST IS LOCATED TO AN AREA THAT THE FUMES
 DONOT REENTER THE BUILDING THROUGH NEARBY WINDOWS,
 DOORS, OR INTAKES OF ANY KIND.
  
 PROVIDE DETAILS INCLUDING APPLICABLE DIMENSIONS
  
  
 12) SHEET C 4.1 - THERE IS AN INDICATION OF AN 8" FIRE
 LINE THAT APPEARS TO GO UNDER THE FOOT PRINT OF THE
 BUILDING.
  
 PER NFPA 24
  
 10.1.4.1* UNDERGROUND PIPING SHALL BE PERMITTED TO
 EXTEND
 INTO THE BUILDING THROUGH THE SLAB OR WALL NOT MORE
 THAN 24 IN.
 (600 MM).
  
 10.4.3 PRIVATE FIRE SERVICE MAINS UNDER BUILDINGS.
 EXCEPT AS
 ALLOWED BY 10.4.3, PRIVATE FIRE SERVICE MAINS SHALL NOT
 BE AL LOWED TO RUN UNDER BUILDING
  
 10.4.3.1* PRIVATE FIRE SERVICE MAINS SUPPLYING FIRE
 PROTECTION
 SYSTEMS WITHIN THE BUILDING SHALL BE PERMITTED TO
 EXTEND NO
 MORE THAN 10 FT (3.0 M), AS MEASURED FROM THE OUTSIDE
 OF THE
 BUILDING, UNDER THE BUILDING TO THE RISER LOCATION
  
 10.4.3.1.1* PIPE JOINTS SHALL NOT BE LOCATED DIRECTLY
 UNDER
 FOUNDATION FITTINGS.
 10.4.3.1.2* PIPING SHALL BE INSTALLED A MINIMUM OF 12
 IN.
 (300 MM) BELOW THE BOTTOM OF BUILDING FOUNDATIONS OR
 FOOTERS.
  
 10.4.3.2* WHERE APPROVED, PRIVATE FIRE SERVICE MAINS
 SUPPLY ING SYSTEMS WITHIN THE BUILDING SHALL BE
 PERMITTED TO EXTEND
 MORE THAN 10 FT (3.0 M) UNDER THE BUILDING WHEN ALL THE
 RE QUIREMENTS OF 10.4.3.2.1, THROUGH 10.4.3.2.4 ARE
 MET.
 10.4.3.2.1 WHERE THE PIPING IS INSTALLED UNDER THE
 BUILDING, ALL
 FOUNDATIONS OR FOOTERS OVER THE PRIVATE FIRE SERVICE
 MAIN SHALL BE
 ARCHED TO CREATE A MINIMUM OF 24 IN (600 MM) CLEARANCE.
 10.4.3.2.2 IT SHALL BE ACCEPTABLE TO INSTALL THE PIPING
 IN COV ERED TRENCHES WHERE THE TRENCHES ARE ACCESSIBLE
 FROM WITHIN
 THE BUILDING
  
 PLEASE REVIEW AND PROVIDE DEAILS IN COMPLIANCE.
  
  
 13A) THERE IS A FDC LOCATED ALONG BANYAN BLVD WWITH
 INDICATIONS OF TWO EXISTING HYDRANT LOCATIONS
  
 THERE ARE NO DIMENSIONS TO THOS EXISTING FIRE HYDRANTS
 SHOWING COMPLIANCE WITH NFPA 14.
  
 PER NFPA 14
 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED
 NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE
 HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY.
  
  
 PLEASE PROVIDE THE DIMENSIONS AND CORRECT THE FDC
 LOCATION AS APPLICABLE.
  
  
  
 13B) ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED UNDER
 SEPARATE PERMIT & SHOP DRAWINGS IN COMPLIANCE WITH AND
 TESTED PER NFPA 24 AND MANUFACTURES SPECIFICATIONS.
  
 DO NOT COVER OVER ANY FIRE LINE PRIOR TO FIRE
 INSPECTION, JOINTS SAHLL BE LEFT EXPOSED FOR
 VERIFICATION & CONFIRMATION,
  
 PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT
  
  
  
 14) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 15) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  
  
  
  
  
  
  
  
  