2022-06-07 12:42:41 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THE SMOKE CONTROL RATIONAL ANALYSIS AND SEQUENCE OF |
| OPERATION ARE NOT ATTACHED |
| |
| NFPA 101 CH 11 |
| |
| 11.8.2.3 ALL NEW VERTICAL EXIT ENCLOSURES SERVING THE |
| HIGH-RISE PORTION |
| OF THE BUILDING SHALL BE SMOKEPROOF ENCLOSURES IN |
| ACCORDANCE WITH 7.2.3. |
| |
| 9.3 SMOKE CONTROL |
| 9.3.1 INSTALLATION. WHERE REQUIRED BY ANOTHER SECTION |
| OF THIS CODE, |
| SMOKE CONTROL SYSTEMS SHALL BE DESIGNED, INSTALLED, |
| INSPECTED, TESTED, |
| AND MAINTAINED IN ACCORDANCE WITH NFPA 92, NFPA 204, OR |
| NATIONALLY |
| RECOGNIZED STANDARDS, ENGINEERING GUIDES, OR |
| RECOMMENDED PRACTICES, |
| AS APPROVED BY THE AUTHORITY HAVING JURISDICTION |
| |
| PLEASE PROVIDE SPECIFIC DETAILS. |
| |
| |
| |
| 2) SHEET LS 01.1 - THE FIRE COMMAND CENTER DOES NOT |
| HAVE ACCESS FROM AN EXTERIOR WALL. |
| |
| THE FIRE COMMAND CENTER SHOULD HAVE DIRECT UNIMPEDED |
| ACCESS FROM AN EXTERIOR WALL AND IN A LOCATION APPROVED |
| BY THE AHJ |
| |
| PER NFPA 101 CH 11 |
| |
| 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED |
| IN A LOCATION |
| APPROVED BY THE FIRE DEPARTMENT. |
| |
| |
| PLEASE REVIEW AND CORRECT WITH COORDINATION WITH THE |
| OFFICE OF THE FIRE MARSHAL. |
| |
| |
| |
| 3) SHEET LS 01.1 - THERE IS AN INDICATION OF EXIT |
| TRAVEL ACCESS DOOR THROUGH AN OUTDOOR STORAGE AREA, # |
| 113 AND OUTDOOR TERRACE # 112 |
| |
| IT DOES INDICATE THAT AREA LEADS TO A PUBLIC WAY NOR |
| EXIT SIGNAGE FROM THAT AREA. |
| |
| PER NFPA 101 CH 7 |
| |
| 7.5 ARRANGEMENT OF MEANS OF EGRESS |
| 7.5.1 GENERAL. |
| 7.5.1.1 EXITS SHALL BE LOCATED, AND EXIT ACCESS SHALL |
| BE ARRANGED, SO THAT |
| EXITS ARE READILY ACCESSIBLE AT ALL TIMES. |
| 7.5.1.1.1* WHERE EXITS ARE NOT IMMEDIATELY ACCESSIBLE |
| FROM AN OPEN |
| FLOOR AREA, CONTINUOUS PASSAGEWAYS, AISLES, OR |
| CORRIDORS LEADING DIRECTLY |
| TO EVERY EXIT SHALL BE MAINTAINED AND SHALL BE ARRANGED |
| TO PROVIDE ACCESS |
| FOR EACH OCCUPANT TO NOT LESS THAN TWO EXITS BY |
| SEPARATE WAYS OF TRAVEL, |
| UNLESS OTHERWISE PROVIDED IN 7.5.1.1.3 AND 7.5.1.1.4 |
| |
| 7.10.1.5 EXIT ACCESS. |
| 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, |
| READILY VISIBLE |
| SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE |
| EXIT IS NOT READILY |
| APPARENT TO THE OCCUPANTS |
| |
| 7.7 DISCHARGE FROM EXITS |
| 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE |
| DIRECTLY, AT A PUBLIC |
| WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE |
| PROVIDED IN 7.7.1.2 |
| THROUGH 7.7.1.4. |
| |
| |
| PLEASE REVIEW AND CORRECT OR BETTER DEFINE THE EIXT |
| PATH TO THE PUBLIC WAY. |
| |
| |
| 3A) SHEET LS 01.1 - THERE IS AN INDICATION OF EXIT |
| STAIRS INTO THE OUTDOOR TERRACE # 112 |
| |
| THE EXIT STARI DISCHARGE IS TO LEAD TO A PUBLIC WAY OR |
| TO A PROTECTED AREA LEADING TO A PUBLIC WAY. |
| |
| IT DOES INDICATE THAT AREA LEADS TO A PUBLIC WAY NOR |
| EXIT SIGNAGE FROM THAT AREA. |
| |
| PER NFPA 101 CH 7 |
| |
| 7.2.3.5 DISCHARGE. |
| 7.2.3.5.1 EVERY SMOKEPROOF ENCLOSURE SHALL DISCHARGE |
| INTO A PUBLIC WAY, |
| INTO A YARD OR COURT HAVING DIRECT ACCESS TO A PUBLIC |
| WAY, OR INTO AN EXIT |
| PASSAGEWAY. SUCH EXIT PASSAGEWAYS SHALL BE WITHOUT |
| OPENINGS, OTHER |
| THAN THE ENTRANCE TO THE SMOKEPROOF ENCLOSURE AND THE |
| DOOR OPENING TO |
| THE OUTSIDE YARD, COURT, OR PUBLIC WAY. THE EXIT |
| PASSAGEWAY SHALL BE |
| SEPARATED FROM THE REMAINDER OF THE BUILDING BY A |
| 2-HOUR FIRE RESISTANCE |
| RATING. |
| 7.2.3.5.2 THE SMOKEPROOF ENCLOSURE SHALL BE PERMITTED |
| TO DISCHARGE |
| THROUGH INTERIOR BUILDING AREAS, PROVIDED THAT ALL OF |
| THE FOLLOWING CRITERIA |
| ARE MET: |
| (1) THE BUILDING SHALL BE PROTECTED THROUGHOUT BY AN |
| APPROVED, SUPER VISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH SECTION 9.7. |
| (2) THE DISCHARGE FROM THE SMOKEPROOF ENCLOSURE SHALL |
| LEAD TO A FREE |
| AND UNOBSTRUCTED WAY TO AN EXTERIOR EXIT, AND SUCH WAY |
| SHALL BE |
| READILY VISIBLE AND IDENTIFIABLE FROM THE POINT OF |
| DISCHARGE FROM |
| THE SMOKEPROOF ENCLOSURE. |
| (3) NOT MORE THAN 50 PERCENT OF THE REQUIRED NUMBER AND |
| CAPACITY OF |
| EXITS COMPRISED OF SMOKEPROOF ENCLOSURES SHALL |
| DISCHARGE THROUGH |
| INTERIOR BUILDING AREAS IN ACCORDANCE WITH 7.7.2. |
| |
| 7.7 DISCHARGE FROM EXITS |
| 7.7.1* EXIT TERMINATION. EXITS SHALL TERMINATE |
| DIRECTLY, AT A PUBLIC |
| WAY OR AT AN EXTERIOR EXIT DISCHARGE, UNLESS OTHERWISE |
| PROVIDED IN 7.7.1.2 |
| THROUGH 7.7.1.4. |
| |
| 7.10.1.5 EXIT ACCESS. |
| 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, |
| READILY VISIBLE |
| SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE |
| EXIT IS NOT READILY |
| APPARENT TO THE OCCUPANTS |
| |
| PLEASE REVIEW AND CORRECT OR BETTER DEFINE THE EIXT |
| PATH TO THE PUBLIC WAY. |
| |
| |
| |
| |
| |
| 4) THERE ARE INDICATIONS OF CARD READERS/ACCESS CONTROL |
| THROUGHOUT THE OCCUPANCY. |
| |
| ALL CARD READER/ACCESS CONTROL SHALL BE INSTALLED UNDER |
| SEPARATE PERMIT & SHOP DRAWINGS AND COMPLY WITH NFPA |
| 101, CH 7 AS APPLICABLE. |
| |
| PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT ON |
| THE LIFE SAFETY & ELECTICAL NOTE SHEETS. |
| |
| |
| |
| |
| 5) SHEET LS 06.1 - THERE IS EXIT DOOR (STAIR B) FROM |
| THE PARKING GARAGE ENTERING INTO THE EXIT PASSAGE WAY. |
| TO AVOID EXIT CONFUSION THERE SHOULD BE A SING ON THE |
| WALL OPPOSITE THAT EXIT DOOR STATING EXIT DOWN(OR |
| EQUAL) WITH AN ARROW POINTING IN THE DIRECTION OF THE |
| STAIR. |
| |
| PER NFPA 101 CH 7 MEANS OF EGRESS |
| |
| 7.10.1.5 EXIT ACCESS. |
| 7.10.1.5.1 ACCESS TO EXITS SHALL BE MARKED BY APPROVED, |
| READILY VISIBLE |
| SIGNS IN ALL CASES WHERE THE EXIT OR WAY TO REACH THE |
| EXIT IS NOT READILY |
| APPARENT TO THE OCCUPANTS |
| |
| THIS WOULD REDUCE THE CONFUSION OF GOING THE WRONG WAY |
| DOWN THE EXIT PASSAGE WAY AND UP TO ANOTHER FLOOR |
| LEVEL. |
| |
| PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT ON |
| THE LIFE SAFETY SHEET. |
| |
| |
| |
| 6) SHEET LS 08.1 - THERE APPEARS TO BE A SINGLE |
| EXIT/SIGN FROM THE COMMON TERRACE # 813 AREA. |
| |
| AS THIS IS AN ASSEMBLY OCCUPANCY SPACE, TWO EXITS ARE |
| REQUIRED PER NFPA 101, CH 12 & CH 7 REMOTELY LOCATED |
| FROM EACH OTHER. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC |
| NARRATIVE AND CODE REFERENCES. |
| |
| |
| |
| |
| 7) SHEET E 1.1.3 & E 4.0.2 - THE ARE INDICATIONS OF |
| FAAP HOWEVER, THERE IS NO INDICATION OF THE FACP THAT |
| IS REQUIRED TO BE THE FIRE COMMAND CENTER |
| |
| SHEET E 4.0.2 SHOWS LIMITED EQUIPMENT. |
| |
| PER NFPA 1 & 101 |
| |
| 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY |
| COMMAND CENTER. |
| |
| (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT. |
| |
| 11.8.6* EMERGENCY COMMAND CENTER. |
| |
| (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION |
| PANELS |
| |
| PLEASE REVIEW AND CORRECT OR PROVIDE A NOTE OF |
| ACKNOWLEDGMENT |
| |
| |
| |
| 7A) SHEET E 1.1.3 - THERE ARE NO INDICATIONS OF ANY |
| EQUIPMENT WITHIN THE FIRE COMMAND CENTER. |
| |
| THE FIRE COMMAND CENTER SHALL COMPLY WITH NFPA 1, |
| CHAPTER 11, BUILDING SERVICES; 11.9 AND SHALL CONTAIN |
| THE FOLLOWING FEATURES: |
| 11.9.1 THE LOCATION, DESIGN, CONTENT, AND FIRE |
| DEPARTMENT ACCESS OF THE EMERGENCY COMMAND CENTER SHALL |
| BE APPROVED BY THE FIRE DEPARTMENT. |
| |
| 11.9.2 THE EMERGENCY COMMAND CENTER SHALL BE SEPARATED |
| FROM THE REMAINDER OF THE BUILDING BY A FIRE BARRIER |
| HAVING A FIRE RESISTANCE RATING OF NOT LESS THAN 1 |
| HOUR. |
| |
| 11.9.3 THE EMERGENCY COMMAND CENTER ROOM SHALL BE A |
| MINIMUM OF 200 FT2 (19 M2) WITH A MINIMUM DIMENSION OF |
| 10 FT (3050 MM). |
| |
| 11.9.4 THE FOLLOWING SHALL BE PROVIDED IN THE EMERGENCY |
| COMMAND CENTER. |
| (1) THE FIRE DEPARTMENT COMMUNICATIONS SYSTEM. |
| (2) A TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| ACCESS TO THE PUBLIC TELEPHONE SYSTEM |
| (3) SCHEMATIC BUILDING PLANS INDICATING THE TYPICAL |
| FLOOR PLAN AND DETAILING THE BUILDING CORE, MEANS OF |
| EGRESS, FIRE PROTECTION SYSTEMS, FIRE-FIGHTING |
| EQUIPMENT AND FIRE DEPARTMENT ACCESS |
| (4) WORK TABLE. |
| (5) IF APPLICABLE, A HAZARDOUS MATERIAL MANAGEMENT PLAN |
| FOR THE BUILDING. |
| 11.9.5 WHERE OTHERWISE REQUIRED, THE FOLLOWING DEVICES |
| OR FUNCTIONS SHALL BE PROVIDED WITHIN THE EMERGENCY |
| COMMAND CENTER. |
| (1) THE EMERGENCY VOICE/ALARM COMMUNICATION SYSTEM |
| CONTROL UNIT. |
| (2) FIRE DETECTION AND ALARM SYSTEM ANNUNCIATOR UNIT. |
| (3) ANNUNCIATOR UNIT VISUALLY INDICATING THE LOCATION |
| OF THE ELEVATORS AND WHETHER THEY ARE OPERATIONAL |
| (4) STATUS INDICATORS AND CONTROLS FOR AIR-HANDLING |
| SYSTEMS. |
| (5) CONTROLS FOR UNLOCKING STAIRWAY DOORS |
| SIMULTANEOUSLY |
| (6) SPRINKLER VALVE AND WATER FLOW DETECTOR DISPLAY |
| PANELS |
| (7) EMERGENCY AND STANDBY POWER STATUS INDICATORS |
| (8) FIRE PUMP STATUS INDICATORS |
| (9) GENERATOR SUPERVISION DEVICES AND MANUAL START AND |
| TRANSFER FEATURES. |
| (10) PUBLIC ADDRESS SYSTEM, WHERE SPECIFICALLY REQUIRED |
| BY OTHER SECTIONS OF THIS CODE |
| (11) CONTROLS REQUIRED FOR SMOKE CONTROL |
| |
| NFPA 101 |
| |
| 11.8.6* EMERGENCY COMMAND CENTER. |
| 11.8.6.1 AN EMERGENCY COMMAND CENTER SHALL BE PROVIDED |
| IN A |
| LOCATION APPROVED BY THE FIRE DEPARTMENT. |
| 11.8.6.2 THE EMERGENCY COMMAND CENTER SHALL CONTAIN THE |
| FOLLOWING: |
| (1) VOICE FIRE ALARM SYSTEM PANELS AND CONTROLS |
| (2) FIRE DEPARTMENT TWO-WAY TELEPHONE COMMUNICATION |
| SERVICE |
| PANELS AND CONTROLS WHERE REQUIRED BY ANOTHER SECTION |
| OF THIS |
| CODE |
| (3) FIRE DETECTION AND FIRE ALARM SYSTEM ANNUNCIATION |
| PANELS |
| (4) ELEVATOR FLOOR LOCATION AND OPERATION ANNUNCIATORS |
| (5) ELEVATOR FIRE RECALL SWITCH IN ACCORDANCE WITH ASME |
| A17.1/CSA B44, SAFETY CODE FOR ELEVATORS AND ESCALATORS |
| (6) ELEVATOR EMERGENCY POWER SELECTOR SWITCH(ES) WHERE |
| PROVIDED |
| IN ACCORDANCE WITH ASME A17.1/CSA B44 |
| (7) SPRINKLER VALVE AND WATERFLOW ANNUNCIATORS |
| (8) EMERGENCY GENERATOR STATUS INDICATORS |
| (9) CONTROLS FOR ANY AUTOMATIC STAIRWAY DOOR UNLOCKING |
| SYSTEM |
| (10) FIRE PUMP STATUS INDICATORS |
| (11) TELEPHONE FOR FIRE DEPARTMENT USE WITH CONTROLLED |
| ACCESS TO THE |
| PUBLIC TELEPHONE SYSTEM |
| (12) STAIRWAY VIDEO MONITORING EQUIPMENT AS REQUIRED BY |
| 11.8.8 |
| |
| PLEASE REVIEW AND ENSURE COMPLIANCE TO INSTALL. |
| |
| PROVIDE A NOTE OF ACKNOWLEDGMENT |
| |
| |
| |
| 8) SHEET E 6.0.5 - THERE ARE INDICATIONS OF A BDA TYPE |
| 2-WAY COMMUNCATIONS SYSTEM. |
| |
| ANY BDA SYSTEM SHALL BE INSTALLED UNDER SEPARATE |
| PERMIT. |
| |
| THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL |
| STRENGTH OF THE RADIO SYSTEM USED BY WEST PALM BEACH |
| FIRE DEPARTMENT. TESTING SHALL BE BY AN ACCEPTABLE |
| NATIONAL STANDARD DOCUMENTING PERCENTAGES NOTED ABOVE |
| AND BY ACTUAL RADIO TESTING BY FIRE PERSONNEL. IF THE |
| MINIMUM CANNOT BE MAINTAINED, A BI-DIRECTIONAL |
| AMPLIFIED SYSTEM SHALL BE INSTALLED WITH A MINIMUM |
| 2-HOUR RUN TIME BATTERY BACK-UP. |
| |
| HOWEVER, A SYSTEM MAY NOT BE REQUIRED. |
| |
| PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC |
| SAFETY RADIO SYSTEMS MANAGER, [email protected], |
| 561-233-0837; AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR |
| DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS. |
| |
| BEFORE SUBMITTING FOR A PERMIT, PLEASE PROVIDE ALL THE |
| TESTING DATA TO MR. FILLA AND THE OFFICE OF THE FIRE |
| MARSHAL FOR REVIEW. |
| |
| PROVIDE A NOTE OF ACKNOWLEDGMENT |
| |
| |
| 9) SHEET E 0.1.1 - THERE ARE INDICATIONS OF A FIRE |
| ALARM SYSTEM AND EQUIPMENT. |
| |
| THE FIRE ALARM SYSTEM SHALL BE MAINTAINED THROUGHOUT |
| DEMO & CONSTRUCTION PERIODS |
| |
| ANY WORK ON THE FIRE ALARM, SHALL BE DONE UNDER |
| SEPARATE PERMITS & SHOP DRAWINGS. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT |
| |
| |
| |
| 10) SHEET F 0.0.1 - THERE ARE INDICATIONS OF A FIRE |
| SPRINKLER SYSTEM AND EQUIPMENT. |
| |
| THE FIRE SPRINKLER SYSTEM SHALL BE MAINTAINED |
| THROUGHOUT DEMO & CONSTRUCTION PERIODS |
| |
| ANY WORK ON THE FIRE SPRINKER SYSTEM, SHALL BE DONE |
| UNDER SEPARATE PERMITS & SHOP DRAWINGS. |
| |
| PER NFPA 14 |
| 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED |
| NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE |
| HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY. |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT |
| |
| |
| |
| 11) SHEET E 5.0.1 - THERE IS AN INDICATION OF A |
| GENERATOR EXHAUST PIPING DIAGRAM. |
| |
| PER NFPA 110 AND 37 |
| |
| PLEASE CONFIRM THE GENERATOR CLASS/TYPE, FUEL SOURCE |
| AND THAT THE ELECTRIC FIRE PUMP IS CONNECTED TO THE |
| GENERATOR WITH AN AUTOMATIC TRANSFER SWITCH. |
| |
| |
| |
| 11A) PER NFPA 110 AND 37, PLEASE ENSURE THAT THE |
| GENERATOR EXHAUST IS LOCATED TO AN AREA THAT THE FUMES |
| DONOT REENTER THE BUILDING THROUGH NEARBY WINDOWS, |
| DOORS, OR INTAKES OF ANY KIND. |
| |
| PROVIDE DETAILS INCLUDING APPLICABLE DIMENSIONS |
| |
| |
| 12) SHEET C 4.1 - THERE IS AN INDICATION OF AN 8" FIRE |
| LINE THAT APPEARS TO GO UNDER THE FOOT PRINT OF THE |
| BUILDING. |
| |
| PER NFPA 24 |
| |
| 10.1.4.1* UNDERGROUND PIPING SHALL BE PERMITTED TO |
| EXTEND |
| INTO THE BUILDING THROUGH THE SLAB OR WALL NOT MORE |
| THAN 24 IN. |
| (600 MM). |
| |
| 10.4.3 PRIVATE FIRE SERVICE MAINS UNDER BUILDINGS. |
| EXCEPT AS |
| ALLOWED BY 10.4.3, PRIVATE FIRE SERVICE MAINS SHALL NOT |
| BE AL LOWED TO RUN UNDER BUILDING |
| |
| 10.4.3.1* PRIVATE FIRE SERVICE MAINS SUPPLYING FIRE |
| PROTECTION |
| SYSTEMS WITHIN THE BUILDING SHALL BE PERMITTED TO |
| EXTEND NO |
| MORE THAN 10 FT (3.0 M), AS MEASURED FROM THE OUTSIDE |
| OF THE |
| BUILDING, UNDER THE BUILDING TO THE RISER LOCATION |
| |
| 10.4.3.1.1* PIPE JOINTS SHALL NOT BE LOCATED DIRECTLY |
| UNDER |
| FOUNDATION FITTINGS. |
| 10.4.3.1.2* PIPING SHALL BE INSTALLED A MINIMUM OF 12 |
| IN. |
| (300 MM) BELOW THE BOTTOM OF BUILDING FOUNDATIONS OR |
| FOOTERS. |
| |
| 10.4.3.2* WHERE APPROVED, PRIVATE FIRE SERVICE MAINS |
| SUPPLY ING SYSTEMS WITHIN THE BUILDING SHALL BE |
| PERMITTED TO EXTEND |
| MORE THAN 10 FT (3.0 M) UNDER THE BUILDING WHEN ALL THE |
| RE QUIREMENTS OF 10.4.3.2.1, THROUGH 10.4.3.2.4 ARE |
| MET. |
| 10.4.3.2.1 WHERE THE PIPING IS INSTALLED UNDER THE |
| BUILDING, ALL |
| FOUNDATIONS OR FOOTERS OVER THE PRIVATE FIRE SERVICE |
| MAIN SHALL BE |
| ARCHED TO CREATE A MINIMUM OF 24 IN (600 MM) CLEARANCE. |
| 10.4.3.2.2 IT SHALL BE ACCEPTABLE TO INSTALL THE PIPING |
| IN COV ERED TRENCHES WHERE THE TRENCHES ARE ACCESSIBLE |
| FROM WITHIN |
| THE BUILDING |
| |
| PLEASE REVIEW AND PROVIDE DEAILS IN COMPLIANCE. |
| |
| |
| 13A) THERE IS A FDC LOCATED ALONG BANYAN BLVD WWITH |
| INDICATIONS OF TWO EXISTING HYDRANT LOCATIONS |
| |
| THERE ARE NO DIMENSIONS TO THOS EXISTING FIRE HYDRANTS |
| SHOWING COMPLIANCE WITH NFPA 14. |
| |
| PER NFPA 14 |
| 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED |
| NOT MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE |
| HYDRANT CONNECTED TO AN APPROVED WATER SUPPLY. |
| |
| |
| PLEASE PROVIDE THE DIMENSIONS AND CORRECT THE FDC |
| LOCATION AS APPLICABLE. |
| |
| |
| |
| 13B) ALL FIRE LINE UNDERGROUND SHALL BE INSTALLED UNDER |
| SEPARATE PERMIT & SHOP DRAWINGS IN COMPLIANCE WITH AND |
| TESTED PER NFPA 24 AND MANUFACTURES SPECIFICATIONS. |
| |
| DO NOT COVER OVER ANY FIRE LINE PRIOR TO FIRE |
| INSPECTION, JOINTS SAHLL BE LEFT EXPOSED FOR |
| VERIFICATION & CONFIRMATION, |
| |
| PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT |
| |
| |
| |
| 14) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 15) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |