2022-06-28 16:39:29FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 THE FOLLOWING SYSTEMS ARE TO BE PERMITTED SEPARATLEY
 FROM MASTER PERMIT. DATA/ PHONE, FIRE ALARM, BDA,
 GENERATOR, SITE LIGHTING.
  
 PAGES E7.0.1 THROUGH E7.0.5 LOAD CALCULATIONS NOT PER
 220 OF THE NEC FOR FEEDERS AND SERVICE. CONTINOUS LOAD
 FACTORS MISSING FROM MOST LOAD CALCS, LARGEST MOTOR
 CONTRIBUTION, CAR CHARGERS AT 125% PER 625.41.
  
 PAGE E6.0.1 GENERATOR NOT IN CONFORMANCE TO 700.3(F)
 FIRE PUMP MISSING SURGE ARRESTOR PER 695.15