Plan Review Notes For Permit 22050714 |
Permit Number |
22050714 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-07-18 09:20:16 | NEW HI RISE OFFICE BLDG. | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | PLEASE PROVIDE THE REVISED DRAWINGS THAT ARE IN PERMIT | | - 22020521 - WHICH MAY ANSWER MANY OF THE COMMENTS HERE | | - | | | | 1) PLEASE SHOW PARKING GARAGE OPEN OR CLOSED AND | | PROVIDE THE CALCULATIONS FOR THE OPEN GARAGE FBC | | 406.5.2 | | | | 2) PLEASE SHOW DISTANCE FROM PROPERTY LINES (WEST SIDE | | APPEARS CLOSE) FBC 602 | | | | 3) THE NAMING OF DRAWINGS IN PROJECTDOX DOES NOT MATCH | | THE DRAWING NAME - PLEASE CORRECT - SEE DRAWINGS | | A3.3.2, A3.3.3, A3.3.4, A3.4.2 AND A3.4.3 CHECK ALL. | | | | 4) PLEASE SHOW THE EV CHARGING STATION AT THE VAN | | ACCESSIBLE PARKING SPACE FBC 406.1.7 | | | | 5) PLEASE SHOW THE HEIGHT CLEARANCE AT THE VAN | | ACCESSIBLE PARKING - FBC 502.5 | | | | 6) DOOR 105 SHOULD BE SHOWN AS FIRE RATED AND SELF | | CLOSING (PLEASE CHECK ALL DOORS) - FBC 716 | | | | 7) ELEVATOR HOISTWAY FOR ELEVATOR #3 AND #4 REQUIRES | | HOISTWAY PROTECTION ( A SINGLE SHAFT WHICH APPEARS TO | | RUN FROM GROUND TO THE 11TH FLOOR) FBC 3006.2 |
|