Plan Review Notes
Plan Review Notes For Permit 22050617
Permit Number 22050617
Review Stop P
Sequence Number 1
Notes
Date Text
2022-05-26 14:10:08CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 22050617 3514 BROADWAY
  
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.AS REQUIRED WPB FBC 107.2.1 AND WPB FBC 107.3.5.1.3,
 THE FOLLOWING ITEMS SHALL BE ADDRESSED AS IS APPLICABLE
 TO YOUR FACILITY:
 ***A) MINIMUM PLUMBING FACILITIES
 ***B) FIXTURE REQUIREMENTS
 ***C) WATER SUPPLY PIPING
 ***D) SANITARY DRAINAGE
 ***E) WATER HEATERS
 ***F) VENTS
 ***G) ROOF DRAINAGE
 ***H) BACKFLOW PREVENTION
 ***I) IRRIGATION
 ***J) LOCATION OF WATER SUPPLY LINE
 ***K) GREASE TRAPS
 ***L) ENVIRONMENTAL REQUIREMENTS
 ***M) PLUMBING RISER (SANITARY AND WATER)
 ***N) DESIGN FLOOD ELEVATION
 SEE BELOW FOR MORE CLARIFICATION.
  
 2. DUE TO CHANGE IN OCCUPANCY, THE FACILITY SHALL
 COMPLY WITH THE 2020 FLORIDA BUILDING CODES. PER WPB
 FBC 107.2.1 PROVIDE THE CURRENT OCCUPANCY AND THE NEW
 OCCUPANCY OF THIS PROPOSED FACILITY.
  
 3. THE SUBMITTED FLOOR PLAN DOES NOT MATCH THE
 FOOTPRINT OF THE BUILDING. IT APPEARS THAT THE BUILDING
 HAS BEEN DIVIDED INTO UNITS IN THE PAST (RE: PERMIT
 03090129). PERMIT12070469 INDICATES THE ENTIRE BUILDING
 WAS DEVOTED TO A SINGLE OCCUPANT. PER WPB FBC 107.2.1,
 PROVIDE AN OVERALL PLAN OF THE BUILDING AND INDICATE
 THE SPACE THE SUBMITTED PLAN SPACE WILL OCCUPY. THERE
 IS RECORD OF MASTER PERMIT 20081406 WITH SUB PERMITS
 THAT INDICATES BATHROOM ADDITION(S) AND OTHER WORK,
 HOWEVER I CAN FIND NO PLANS ASSOCIATED WITH THAT WORK.
  
 4. THERE IS A KITCHEN SPACE NOTED. PER WPB FBC 107.2.1,
 PROVIDE LAYOUT NOTING ALL PLUMBING FIXTURES AND
 APPLIANCES. INCLUDE REQUIRED CLEAR FLOOR SPACES FOR
 ACCESSIBLE FIXTURES/APPLIANCES. PLEASE NOTE THAT IF
 THERE ARE COOKING FACILITIES, PER FBC PL 1003.1, A
 GREASE INTERCEPTOR WILL BE REQUIRED.
  
 5. PER WPB FBC 107.2.1, PROVIDE THE FOLLOWING:
 ***A) PLUMBING FIXTURE SCHEDULE LISTING THE REQUIRED
 PLUMBING FIXTURES, QUANTITY REQUIRED AS REQUIRED BY FBC
 PL TABLE 403.1 AND ACTUAL FURNISHED.
 ***B) EXISTING/DEMO FLOOR PLAN PLUMBING SHOWING THE
 PLUMBING FACILITIES AND ANY DEMO REQUIREMENTS OF
 EXISTING FIXTURES AND PIPING.
 ***C) PROPOSED PLUMBING AND ARCHITECTURAL FLOOR PLAN
 SHOWING ALL PROPOSED PLUMBING FIXTURES AND PIPING
 ***D) PROVIDE PLUMBING RISER DIAGRAMS OF NEW WATER AND
 SANITARY PIPING
 ***E) PROVIDE HOT WATER SOURCE. COMPLY WITH FBC PL
 CHAPTERS 5 AND 6.
 ***F) PROVIDE BATHROOM AND JANITOR ROOM WALL FINISHES
 ADJACENT TO WATER CLOSETS AND SERVICE SINKS SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING CODE 2020 7TH
 EDITION, SECTION 1210.2.2. IF A BATHTUB OR SHOWER IS
 PROVIDED, SHOW COMPLIANCE WITH SECTION 1210.2.3.
 ***G) INDICATE ACCESSIBLE RESTROOM(S) COMPLYING WITH
 THE FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 ***H) PROVIDE DETAILS, PLAN VIEW AND ELEVATION OF
 ACCESSIBLE PLUMBING FIXTURES SHOWING COMPLIANCE WITH
 FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION, CHAPTERS
 2, 3, 6 AND 8. A FULLY DIMENSIONED FLOOR PLAN OF
 ACCESSIBLE BATHROOM WITH DIMENSIONED CLEAR FLOOR SPACES
 AND TURNING SPACE IS REQUIRED.
 ***I) IF NEW UNDERGROUND PIPING IS REQUIRED, THEN A
 SLAB REPAIR DETAIL IS REQUIRED. SHOW THE WIDTH OF THE
 REPAIR, THE MINIMUM THICKNESS AND PSI OF THE CONCRETE
 TO BE REPLACED. SHOW SIZE, LENGTH, SPACING (ON CENTER),
 MINIMUM EMBEDMENT AND ANCHORING/ADHESIVE MATERIAL FOR
 DOWELS. THE REPAIR SHALL ALSO INCLUDE TERMITE TREATMENT
 OF THE SOIL AS WELL AS THE REQUIRED VAPOR BARRIER OVER
 WELL COMPACTED SOIL.
 ***J) PROVIDE PIPING MATERIAL SPEC FOR EACH SYSTEM TO
 INCLUDE PIPE, VALVES, FITTINGS AND JOINTS. COMPLY WITH
 FBC PL CHAPTERS 3, 6, 7, 9 AND 11. ALL COMPONENTS IN
 THE DOMESTIC WATER SYSTEM SHALL BE LEAD FREE IN
 ACCORDANCE WITH FBC PL 605.2 AND 605.2.1.
  
 6. PER 107.1, PLANS SHALL BE SIGNED AND SEALED BY A
 REGISTERED DESIGN OFFICIAL IN ACCORDANCE WITH A
 REGISTERED DESIGN PROFESSIONAL WHERE REQUIRED BY
 CHAPTER 471, FLORIDA STATUTES AND 61G15, FLORIDA
 ADMINISTRATIVE CODE OR CHAPTER 481, FLORIDA STATUTES
 AND 61G1, FLORIDA ADMINISTRATIVE CODE.
 IF THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 IN ACCORDANCE WITH WPB FBC 107.3.4.3 SHALL BEAR THE
 PRINTED NAME, THE SIGNATURE AND THE CERTIFICATION
 NUMBER OF THE DESIGNER WHO SHALL BE A CONTRACTOR
 LICENSED IN THAT TRADE.
  
 7. WPB FBC 109.1; THE VALUATION APPEARS LOW. PROVIDE AN
 ACCURATE VALUATION OF ALL WORK AND COST. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE
 TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL,
 ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH,
 RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES,
 MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY
 LAND VALUE.
  
 END OF COMMENTS.
  
 A COMPREHENSIVE REVIEW COULD NOT BE ACCOMPLISHED AT
 THIS TIME. COMMENTS ABOVE ARE PRELIMINARY AND MAY NOT
 BE ALL INCLUSIVE. PLEASE RESUBMIT CLEARLY LEGIBLE PLANS
 AND A RESPONSE NARRATIVE ADDRESSING THE PLUMBING
 COMMENTS FROM THE FIRST REVIEW.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved