2022-05-19 13:30:21 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS AN INDICATION OF A CHANGE OF OCCUPANCY BUT |
| THERE IS NO INDICATION OF WHAT THE PREVIOUS OCCUPANCY |
| WAS AND THE TYPE / CLASSIFICATION OF THIS PROPOSED |
| DAYCARE. |
| |
| 16.1.2.1 GENERAL. OCCUPANCIES THAT INCLUDE PRESCHOOLS, |
| KINDERGARTENS, |
| AND OTHER SCHOOLS WHOSE PURPOSE IS PRIMARILY |
| EDUCATIONAL FOR CHILDREN |
| 24 MONTHS OF AGE OR OLDER, EVEN THOUGH THE CHILDREN WHO |
| ATTEND SUCH |
| SCHOOLS ARE OF PRESCHOOL AGE, SHALL COMPLY WITH THE |
| PROVISIONS OF |
| CHAPTER 14 |
| |
| THE REQUIREMENTS OF CHAPTER 16 ARE BASED ON THE NEED TO |
| ADEQUATELY |
| PROTECT THE OCCUPANTS IN CASE OF FIRE. THE REQUIREMENTS |
| ASSUME THAT |
| ADEQUATE STAFFING WILL BE AVAILABLE AND ARE BASED ON |
| STAFFING SIMILAR TO |
| THAT OUTLINED IN TABLE A.16.1.1. |
| |
| PLEASE PROVIDE THE CLASSIFICATION OF DAYCARE AND AGE |
| GROUPS IF APPLICABLE. |
| |
| |
| |
| 2) THIS PROPOSED LOCATION APPEARS TO HAVE A FEW |
| SUITES/UNITS THAT ARE NOT INDICATED ON THE BUILDING |
| PLAN. |
| |
| 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.) |
| 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED, |
| EACH PART OF THE |
| BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED |
| IN THIS CHAPTER, |
| SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY |
| FIRE BARRIERS, |
| AS SPECIFIED IN TABLE 6.1.14.4.1(A), TABLE |
| 6.1.14.4.1(B), AND 6.1.14.4.2 |
| THROUGH 6.1.14.4.4, UNLESS SEPARATION IS PROVIDED BY |
| APPROVED EXISTING |
| SEPARATIONS OR AS OTHERWISE PERMITTED BY 6.1.14.4.6. |
| |
| PLEASE PROVIDE THE ADJACENT OCCUPANCY(IES) WITH THE |
| LOCATION OF THIS PROPOSED OCCUPANCY AND THE REQUIRED |
| FIRE RATED SEPARATION PER THE TABLE. |
| |
| |
| 3) THERE ARE DOORS INDICATED ON THE FLOOR PLAN HOWEVER, |
| THERE ARE NO IDNCATIONS OF DOOR HARDWARE COMPLYING WITH |
| THE REQUIREMENTS. |
| |
| 16.2.2.2.4* DOOR LATCHES. EVERY DOOR LATCH TO CLOSETS, |
| STORAGE AREAS, |
| KITCHENS, AND OTHER SIMILAR SPACES OR AREAS SHALL BE |
| SUCH THAT CLIENTS CAN |
| OPEN THE DOOR FROM INSIDE THE SPACE OR AREA |
| |
| 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK |
| SHALL BE |
| DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR FROM THE |
| OUTSIDE BY AN |
| OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE TO THE |
| STAFF. |
| |
| PLEASE PROVIDE A DOOR SCHEDULE SHOWING COMPLIANCE WHERE |
| APPLICABLE. |
| |
| |
| 3A) THEE ARE NO INDICATIONS OF DDOR LOCKS/LATCHES OF |
| THE 2 EXTERIOR EXIT DOORS. |
| |
| 16.2.2.2 DOORS. |
| 16.2.2.2.1 GENERAL. DOORS COMPLYING WITH 7.2.1 SHALL BE |
| PERMITTED. |
| |
| 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| OF A KEY, A TOOL, |
| OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE |
| EGRESS SIDE |
| |
| 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR |
| LEAF SHALL BE |
| PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS |
| METHOD OF OPERATION |
| AND THAT IS READILY OPERATED UNDER ALL LIGHTING |
| CONDITIONS |
| |
| PLEASE PROVIDE A DOOR SCHEDULE SHOWING COMPLIANCE WHERE |
| APPLICABLE. |
| |
| |
| |
| 4) THERE ARE INDICATIONS OF EXIT SIGNS ON THE FLOOR |
| PLAN OVER HTE REQUIRED EXITS. |
| |
| 16.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS |
| SHALL BE |
| ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. |
| 16.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE |
| PROVIDED IN |
| ACCORDANCE WITH SECTION 7.9 IN THE FOLLOWING AREAS: |
| (1) INTERIOR STAIRS AND CORRIDORS |
| (2) ASSEMBLY USE SPACES |
| (3) FLEXIBLE AND OPEN PLAN BUILDINGS |
| (4) INTERIOR OR LIMITED ACCESS PORTIONS OF BUILDINGS |
| (5) SHOPS AND LABORATORIES |
| |
| |
| 16.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS |
| SHALL HAVE |
| SIGNS IN ACCORDANCE WITH SECTION 7.10 |
| |
| PLEASE PROVIDE PER THE REQUIREMENTS |
| |
| |
| 5) THERE ARE NO INDICATIONS OF SMOKE ALARMS. |
| |
| 6.6.3.4.4 SINGLE-STATION OR MULTIPLE-STATION SMOKE |
| ALARMS OR SMOKE |
| DETECTORS SHALL BE PROVIDED IN ALL ROOMS USED FOR |
| SLEEPING IN ACCORDANCE |
| WITH 9.6.2.10 |
| |
| PLEASE PROVIDE DETAILS IF THERE WILL BE A PROPOSED |
| SLEEPING AREA AND FOR THE REQUIRED SMOKE ALARMS. |
| |
| |
| |
| 6) THERE ARE NO INDICATIONS OF ELECTRICAL OUTLETS NOR |
| FOR THEIR PROTECTION. |
| |
| 16.5.1.2 SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL |
| RECEPTACLES SHALL BE |
| INSTALLED IN ALL AREAS OCCUPIED BY CLIENTS. |
| |
| |
| PLEASE PROVIDE DETAILS OF THE LOCATIONS AND |
| REQUIREMENT. |
| |
| |
| 7) THERE ARE NO INDICATIONS OF WHAT THE WALL AND FLOOR |
| FINISHES WILL BE. |
| |
| 16.3.3 INTERIOR FINISH. |
| 16.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| ACCORDANCE WITH |
| SECTION 10.2. |
| 16.3.3.2 INTERIOR WALL AND CEILING FINISH. INTERIOR |
| WALL AND CEILING |
| FINISH MATERIALS COMPLYING WITH SECTION 10.2 SHALL BE |
| CLASS A IN STAIR WAYS, CORRIDORS, AND LOBBIES; IN ALL |
| OTHER OCCUPIED AREAS, INTERIOR WALL |
| AND CEILING FINISH SHALL BE CLASS A OR CLASS B. |
| |
| 16.3.3.3 INTERIOR FLOOR FINISH. |
| 16.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| SECTION 10.2. |
| 16.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND |
| EXIT ACCESS COR RIDORS AND SPACES NOT SEPARATED FROM |
| THEM BY WALLS COMPLYING WITH |
| 14.3.6 SHALL BE NOT LESS THAN CLASS II. |
| 16.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| 10.2.7.1 OR 10.2.7.2, |
| AS APPLICABLE |
| |
| PLEASE PROVIDE DETAILS FOR THE FINISH MATERIAL |
| REQUIREMENTS. |
| |
| |
| |
| 8) THERE ARE NO INDICATIONS OF FIRE EXTINGUISHERS. |
| |
| F.A.C. 69A - 36 |
| |
| (2) PORTABLE FIRE EXTINGUISHERS. THE SELECTION, |
| PLACEMENT, DISTRIBUTION, MAINTENANCE AND SERVICING OF |
| PORTABLE FIRE EXTINGUISHERS SHALL COMPLY WITH NFPA 10 |
| AS ADOPTED BY CHAPTER 69A-3, F.A.C., AND WITH THE |
| PROVISIONS OF CHAPTER 69A-21, F.A.C., EXCEPT THAT THE |
| MINIMUM RATING OF ANY EXTINGUISHER INSTALLED IN A CHILD |
| CARE FACILITY SHALL NOT BE LESS THAN 2A-10B:C. |
| |
| PLEASE PROVIDE THE LOCATIONS(S) AND SIZES OF REQUIRED |
| FIRE EXTINGUISHERS. |
| |
| |
| 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |