Plan Review Notes For Permit 22050617
Permit Number 22050617
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-05-19 13:30:21THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE IS AN INDICATION OF A CHANGE OF OCCUPANCY BUT
 THERE IS NO INDICATION OF WHAT THE PREVIOUS OCCUPANCY
 WAS AND THE TYPE / CLASSIFICATION OF THIS PROPOSED
 DAYCARE.
  
 16.1.2.1 GENERAL. OCCUPANCIES THAT INCLUDE PRESCHOOLS,
 KINDERGARTENS,
 AND OTHER SCHOOLS WHOSE PURPOSE IS PRIMARILY
 EDUCATIONAL FOR CHILDREN
 24 MONTHS OF AGE OR OLDER, EVEN THOUGH THE CHILDREN WHO
 ATTEND SUCH
 SCHOOLS ARE OF PRESCHOOL AGE, SHALL COMPLY WITH THE
 PROVISIONS OF
 CHAPTER 14
  
 THE REQUIREMENTS OF CHAPTER 16 ARE BASED ON THE NEED TO
 ADEQUATELY
 PROTECT THE OCCUPANTS IN CASE OF FIRE. THE REQUIREMENTS
 ASSUME THAT
 ADEQUATE STAFFING WILL BE AVAILABLE AND ARE BASED ON
 STAFFING SIMILAR TO
 THAT OUTLINED IN TABLE A.16.1.1.
  
 PLEASE PROVIDE THE CLASSIFICATION OF DAYCARE AND AGE
 GROUPS IF APPLICABLE.
  
  
  
 2) THIS PROPOSED LOCATION APPEARS TO HAVE A FEW
 SUITES/UNITS THAT ARE NOT INDICATED ON THE BUILDING
 PLAN.
  
 6.1.14.4 SEPARATED OCCUPANCIES. (SEE ALSO 6.1.14.1.2.)
 6.1.14.4.1 WHERE SEPARATED OCCUPANCIES ARE PROVIDED,
 EACH PART OF THE
 BUILDING COMPRISING A DISTINCT OCCUPANCY, AS DESCRIBED
 IN THIS CHAPTER,
 SHALL BE COMPLETELY SEPARATED FROM OTHER OCCUPANCIES BY
 FIRE BARRIERS,
 AS SPECIFIED IN TABLE 6.1.14.4.1(A), TABLE
 6.1.14.4.1(B), AND 6.1.14.4.2
 THROUGH 6.1.14.4.4, UNLESS SEPARATION IS PROVIDED BY
 APPROVED EXISTING
 SEPARATIONS OR AS OTHERWISE PERMITTED BY 6.1.14.4.6.
  
 PLEASE PROVIDE THE ADJACENT OCCUPANCY(IES) WITH THE
 LOCATION OF THIS PROPOSED OCCUPANCY AND THE REQUIRED
 FIRE RATED SEPARATION PER THE TABLE.
  
  
 3) THERE ARE DOORS INDICATED ON THE FLOOR PLAN HOWEVER,
 THERE ARE NO IDNCATIONS OF DOOR HARDWARE COMPLYING WITH
 THE REQUIREMENTS.
  
 16.2.2.2.4* DOOR LATCHES. EVERY DOOR LATCH TO CLOSETS,
 STORAGE AREAS,
 KITCHENS, AND OTHER SIMILAR SPACES OR AREAS SHALL BE
 SUCH THAT CLIENTS CAN
 OPEN THE DOOR FROM INSIDE THE SPACE OR AREA
  
 16.2.2.2.5 BATHROOM DOORS. EVERY BATHROOM DOOR LOCK
 SHALL BE
 DESIGNED TO ALLOW OPENING OF THE LOCKED DOOR FROM THE
 OUTSIDE BY AN
 OPENING DEVICE THAT SHALL BE READILY ACCESSIBLE TO THE
 STAFF.
  
 PLEASE PROVIDE A DOOR SCHEDULE SHOWING COMPLIANCE WHERE
 APPLICABLE.
  
  
 3A) THEE ARE NO INDICATIONS OF DDOR LOCKS/LATCHES OF
 THE 2 EXTERIOR EXIT DOORS.
  
 16.2.2.2 DOORS.
 16.2.2.2.1 GENERAL. DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
  
 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE
 OF A KEY, A TOOL,
 OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE
 EGRESS SIDE
  
 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR
 LEAF SHALL BE
 PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS
 METHOD OF OPERATION
 AND THAT IS READILY OPERATED UNDER ALL LIGHTING
 CONDITIONS
  
 PLEASE PROVIDE A DOOR SCHEDULE SHOWING COMPLIANCE WHERE
 APPLICABLE.
  
  
  
 4) THERE ARE INDICATIONS OF EXIT SIGNS ON THE FLOOR
 PLAN OVER HTE REQUIRED EXITS.
  
 16.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL BE
 ILLUMINATED IN ACCORDANCE WITH SECTION 7.8.
 16.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE
 PROVIDED IN
 ACCORDANCE WITH SECTION 7.9 IN THE FOLLOWING AREAS:
 (1) INTERIOR STAIRS AND CORRIDORS
 (2) ASSEMBLY USE SPACES
 (3) FLEXIBLE AND OPEN PLAN BUILDINGS
 (4) INTERIOR OR LIMITED ACCESS PORTIONS OF BUILDINGS
 (5) SHOPS AND LABORATORIES
  
  
 16.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS
 SHALL HAVE
 SIGNS IN ACCORDANCE WITH SECTION 7.10
  
 PLEASE PROVIDE PER THE REQUIREMENTS
  
  
 5) THERE ARE NO INDICATIONS OF SMOKE ALARMS.
  
 6.6.3.4.4 SINGLE-STATION OR MULTIPLE-STATION SMOKE
 ALARMS OR SMOKE
 DETECTORS SHALL BE PROVIDED IN ALL ROOMS USED FOR
 SLEEPING IN ACCORDANCE
 WITH 9.6.2.10
  
 PLEASE PROVIDE DETAILS IF THERE WILL BE A PROPOSED
 SLEEPING AREA AND FOR THE REQUIRED SMOKE ALARMS.
  
  
  
 6) THERE ARE NO INDICATIONS OF ELECTRICAL OUTLETS NOR
 FOR THEIR PROTECTION.
  
 16.5.1.2 SPECIAL PROTECTIVE COVERS FOR ALL ELECTRICAL
 RECEPTACLES SHALL BE
 INSTALLED IN ALL AREAS OCCUPIED BY CLIENTS.
  
  
 PLEASE PROVIDE DETAILS OF THE LOCATIONS AND
 REQUIREMENT.
  
  
 7) THERE ARE NO INDICATIONS OF WHAT THE WALL AND FLOOR
 FINISHES WILL BE.
  
 16.3.3 INTERIOR FINISH.
 16.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
 16.3.3.2 INTERIOR WALL AND CEILING FINISH. INTERIOR
 WALL AND CEILING
 FINISH MATERIALS COMPLYING WITH SECTION 10.2 SHALL BE
 CLASS A IN STAIR WAYS, CORRIDORS, AND LOBBIES; IN ALL
 OTHER OCCUPIED AREAS, INTERIOR WALL
 AND CEILING FINISH SHALL BE CLASS A OR CLASS B.
  
 16.3.3.3 INTERIOR FLOOR FINISH.
 16.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 SECTION 10.2.
 16.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND
 EXIT ACCESS COR RIDORS AND SPACES NOT SEPARATED FROM
 THEM BY WALLS COMPLYING WITH
 14.3.6 SHALL BE NOT LESS THAN CLASS II.
 16.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH
 10.2.7.1 OR 10.2.7.2,
 AS APPLICABLE
  
 PLEASE PROVIDE DETAILS FOR THE FINISH MATERIAL
 REQUIREMENTS.
  
  
  
 8) THERE ARE NO INDICATIONS OF FIRE EXTINGUISHERS.
  
 F.A.C. 69A - 36
  
 (2) PORTABLE FIRE EXTINGUISHERS. THE SELECTION,
 PLACEMENT, DISTRIBUTION, MAINTENANCE AND SERVICING OF
 PORTABLE FIRE EXTINGUISHERS SHALL COMPLY WITH NFPA 10
 AS ADOPTED BY CHAPTER 69A-3, F.A.C., AND WITH THE
 PROVISIONS OF CHAPTER 69A-21, F.A.C., EXCEPT THAT THE
 MINIMUM RATING OF ANY EXTINGUISHER INSTALLED IN A CHILD
 CARE FACILITY SHALL NOT BE LESS THAN 2A-10B:C.
  
 PLEASE PROVIDE THE LOCATIONS(S) AND SIZES OF REQUIRED
 FIRE EXTINGUISHERS.
  
  
 9) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 10) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  