Plan Review Notes For Permit 22050616 |
Permit Number |
22050616 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-05-16 09:43:54 | 1ST PLUMBING REVIEW | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. V7 FRC P3108.1 - BATHROOM NEAR LAUNDRY - THE WATER | | CLOSET AND THE SHOWER ARE BOTH UPSTREAM OF THE VENT | | CONNECTION. ONLY ONE VENT IS ALLOWED ON THE HIGH SIDE | | OF THE VENT CONNECTION. | | | | 2. V7 FRC P3108.1 - OPPOSITE BATHROOM - THE WATER | | CLOSET AND THE SHOWER DRAIN BOTH CONNECT TO THE | | HORIZONTAL BRANCH WITHOUT VENT. BATHROOM GROUP FIXTURES | | CANNOT BE WET VENTED THIS WAY. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | |
|