2022-06-29 06:23:511ST REVIEW FMC
 PERMIT: 22050577
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A MECHANICAL DEMO DRAWING. FBC 107.2.1
  
 2) THE NEW CORRIDOR FOR THIS FLOOR HAS 1-HOUR RATED
 WALLS. SHOW HOW YOU ARE PROTECTING THE PENETRATIONS
 WHERE THE DUCTWORK PASSES THROUGH THESE NEW WALLS. FMC
 607
  
 3) SHOW THE RETURN AIR PATH FOR THE RETURN GRILLS IN
 THE CORRIDORS NEAR THE ELEVATORS. FMC 607
  
 4) PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH TENANT
 AND EACH SPACE IN THE TENANT SPACE. YOU MUST PROVIDE
 THE OUTDOOR AIR CALCULATIONS BASED ON EACH USE OF SPACE
 IN EACH TENANT SPACE ACCORDING TO FMC 403.3.1.1 AND
 TABLE 403.3.1.
  
 5) THE VAV BOX SCHEDULE IS ONLY SHOWING VAV-1, PROVIDE
 INFORMATION ON ALL VAV?S USED IN THIS PROJECT. FBC
 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  