Plan Review Notes For Permit 22050577 |
Permit Number |
22050577 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-06-14 13:22:56 | FIRE PROVISO COMMENTS: | | ALL DOOR HARDWARE WITH LOCKS SHALL NOT REQUIRE THE USE | | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR | | OPERATION FROM THE SIDE OF EGRESS. NFPA 101, 7.2.1.5.3 | | FINISH FLOOR MATERIALS (CARPET AND LVT) SHALL MEET | | ESTABLISHED REQUIREMENTS FOR FIRE PERFORMANCE. NFPA | | 101, 10.2.7 | | |
|