Plan Review Notes For Permit 22050577 |
Permit Number |
22050577 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-07-13 15:05:48 | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | RISER DIAGRAM IS INCOMPLETE | | | | PLEASE SHOW SIZE OF CONDUCTORS SIZES, OVER CURRENT | | PROTECTION. | | | | PANELBOARDS FED BY TRANSFORMERS SHALL HAVE A MAIN | | DICONNECT OR MAIN CIRCUIT BREAKER ON THE LSECONDARY | | SIDE PER 408.36 |
|