Plan Review Notes For Permit 22050577 |
Permit Number |
22050577 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-07-27 10:22:28 | SHEET A-3. BUILDING PROVISO: MICROWAVES MUST MEET 2020 | | FBC- | | ACCESSIBILITY REQUIREMENTS: 308 REACH RANGES. | | 308.2 FORWARD REACH. / 308.2.1 UNOBSTRUCTED/ 308.2.2 | | OBSTRUCTED HIGH REACH | | . 308.3 SIDE REACH. / 308.3.1 UNOBSTRUCTED/ 308.3.2 | | OBSTRUCTED HIGH REACH. | | 309 OPERABLE PARTS. 309.3 HEIGHT. OPERABLE PARTS SHALL | | BE PLACED WITHIN | | ONE OR MORE OF THE REACH RANGES SPECIFIED IN 308. 309.4 | | OPERATION. OPERABLE | | PARTS SHALL BE OPERABLE WITH ONE HAND AND SHALL NOT | | REQUIRE TIGHT GRASPING, | | PINCHING, OR TWISTING OF THE WRIST. THE FORCE REQUIRED | | TO ACTIVATE OPERABLE PARTS | | SHALL BE 5 POUNDS MAXIMUM. | | JAMES A. WITMER BN, PX, SFP, CBO 7/27/2022 | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | |
|