2022-05-21 08:13:13PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
 RESULTS: DENIED
  
 NOTICE: THE FOLLOWING CHECKLIST WAS PROVIDED BY ROBERT
 BROWN, B.O., FOR A FOUNDATION ONLY PERMIT:
 I HAVE ADDED TWO ADDITIONAL REQUIRED DOCUMENTS - AN
 ELECTRICAL PLAN (IF REQUIRED) AND A PLUMBING PLAN.
  
 1) PROPOSED BOUNDARY LINE SURVEY
 2) SITE PLAN
 3) FOUNDATION PLAN
 4) FIRST FLOOR PLAN
 5) CROSS-SECTION DRAWING OR ELEVATION DRAWING
 6) STORMWATER POLLUTION PREVENTION PLAN DETAILS (SILT
 FENCE, ETC.)
 7) GEOTECHNICAL REPORT (SOILS)
 8) AN UNDERGROUND ELECTRICAL PLAN (IF REQUIRED). A
 GROUNDING ELECTRODE SYSTEM DETAIL (UFER)
 9) AN UNDERGROUND PLUMBING PLAN (ISO) PER FLOOR PLAN
 LAYOUT OF PLUMBING FIXTURES
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE A STORMWATER POLUTION PREVENTION PLAN (SILT
 FENCE). YOU MAY SHOW THE LOCATION ON THE SITE PLAN OR
 SURVEY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. PROVIDE AN UNDERGROUND ELECTICAL PLAN (IF REQUIRED).
 PROVIDE A DETAIL OF THE ELECTRICAL GROUNDING SYSTEM
 CONNECTION TO THE BUILDING STEEL (UFER CLAMP) OR (TWO
 GROUND RODS) SIX FEET APART.
 E3607.2 LOCATION OF GROUNDING ELECTRODE CONDUCTOR
 CONNECTION.
  
 3. PROVIDE AN UNDERGROUND PLUMBING PLAN (ISO) PER FLOOR
 PLAN LAYOUT.
 P2601.2 CONNECTIONS TO DRAINAGE SYSTEM
  
 NOTICE: PLAN SHEETS S1.0 AND S4.0 ARE LOCATED IN THE
 SIGNATURE FOLDER. THESE PLAN SHEETS NEED TO BE
 RE-LOCATED TO THE DRAWINGS FOLDER.
  
 NOTICE: PLAN SHEET 002, LABELED A-1 CONSTRUCTION PLAN
 AND PLAN SHEET 004, LABELED D-1 EXISTING-DEMO PLANS ARE
 FOR A DIFFERENT PROJECT, (1701 S. FLAGLER DR #509).
 PLEASE REMOVE THESE FROM YOUR SUBMITTAL.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  
  