Plan Review Notes For Permit 22050542 |
Permit Number |
22050542 |
|
Review Stop |
THRESHOLD |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-05-31 14:52:55 | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | | | THRESHOLD REVIEW DENIED: | | | | 1.) THE PAGES TITLED RESIDENT/SPECIAL INSPECTORS | | AGREEMENT OF UNDERSTANDING AT TOP OF PAGES ARE NOT | | APPLICABLE. | | 2.) THE (4) STATE LICENSED FS 468 INSPECTORS (BN 3909, | | BN6096, BN 6390, & BN 7899) HAVE COMPLETED THE CORRECT | | SECTIONS OF THRESHOLD/SPECIAL INSPECTORS AGREEMENT OF | | UNDERSTANDING. (OK) | | 3.) THRESHOLD INSPECTOR RODOLFO A. GONZEMBACH, PE | | 45226/SI 1065, DID NOT PROVIDE ENGINEER'S SEAL UNDER | | HIS SIGNATURE AS REQUIRED ON THRESHOLD/SPECIAL | | INSPECTOR AGREEMENT OF UNDERSTANDING. PLEASE PROVIDE | | CORRECT INFORMATION. | | 4.) THRESHOLD INSPECTOR HECTOR VERGARA, PE 25764/SI | | 0283, DID NOT DID NOT PROVIDE ENGINEER'S SEAL UNDER HIS | | SIGNATURE AS REQUIRED ON THRESHOLD/SPECIAL INSPECTOR | | AGREEMENT OF UNDERSTANDING. ALSO, THE RESIDENT/SPECIAL | | INSPECTOR FORM IS NOT APPLICABLE. PLEASE PROVIDE | | CORRECT INFORMATION. | | 5.) THE FLORIDA LICENSED CONTRACTOR SECTION ON THE | | THRESHOLD/SPECIAL INSPECTOR AGREEMENT OF UNDERSTANDING | | MUST BE COMPLETED BY THE CONTRACTOR. | | | | |
|