2022-08-25 14:26:30 | FIRE PROVISO COMMENTS: |
| |
| ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE |
| REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS |
| APPLICABLE FOR EACH DOOR/ENTRY/EXIT. |
| 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR |
| ASSEMBLIES. |
| DOOR ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE |
| PERMITTED TO |
| BE ELECTRICALLY LOCKED IF EQUIPPED WITH APPROVED, |
| LISTED HARDWARE, |
| PROVIDED THAT ALL OF THE FOLLOWING CONDITIONS ARE MET: |
| (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS |
| AFFIXED TO |
| THE DOOR LEAF. |
| (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION |
| THAT IS |
| READILY OPERATED IN THE DIRECTION OF EGRESS. |
| (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE |
| HAND |
| IN THE DIRECTION OF EGRESS. |
| (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER |
| SUPPLY |
| DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE DOOR |
| ASSEMBLY |
| IN THE DIRECTION OF EGRESS. |
| (5)*LOSS OF POWER TO THE LISTED RELEASING HARDWARE |
| AUTOMATICALLY |
| UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS. |
| (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN |
| ACCORDANCE WITH |
| ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS. |
| 7.2.1.6.1 DELAYED-EGRESS LOCKING SYSTEMS. |
| 7.2.1.6.1.1 APPROVED, LISTED, DELAYED-EGRESS LOCKING |
| SYSTEMS |
| SHALL BE PERMITTED TO BE INSTALLED ON DOOR ASSEMBLIES |
| SERVING |
| LOW AND ORDINARY HAZARD CONTENTS IN BUILDINGS PROTECTED |
| THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC FIRE |
| DETECTION |
| SYSTEM IN ACCORDANCE WITH SECTION 9.6 OR AN APPROVED, |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE |
| WITH SECTION |
| 9.7, AND WHERE PERMITTED IN CHAPTERS 11 THROUGH 43, |
| PROVIDED |
| THAT ALL OF THE FOLLOWING CRITERIA ARE MET: |
| (1) THE DOOR LEAVES SHALL UNLOCK IN THE DIRECTION OF |
| EGRESS |
| UPON ACTUATION OF ONE OF THE FOLLOWING: |
| (A) APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH SECTION 9.7 |
| (B) NOT MORE THAN ONE HEAT DETECTOR OF AN APPROVED, |
| SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN |
| ACCORDANCE |
| WITH SECTION 9.6 |
| (C) NOT MORE THAN TWO SMOKE DETECTORS OF AN APPROVED, |
| SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN |
| ACCORDANCE |
| WITH SECTION 9.6 |
| (2) THE DOOR LEAVES SHALL UNLOCK IN THE DIRECTION OF |
| EGRESS UPON |
| LOSS OF POWER CONTROLLING THE LOCK OR LOCKING |
| MECHANISM. |
| (3)*AN IRREVERSIBLE PROCESS SHALL RELEASE THE LOCK IN |
| THE DIRECTION |
| OF EGRESS WITHIN 15 SECONDS, OR 30 SECONDS WHERE |
| APPROVED |
| BY THE AUTHORITY HAVING JURISDICTION, UPON APPLICATION |
| OF A FORCE TO THE RELEASE DEVICE REQUIRED IN 7.2.1.5.10 |
| UNDER ALL OF THE FOLLOWING CONDITIONS: |
| (A) THE FORCE SHALL NOT BE REQUIRED TO EXCEED 15 LBF |
| (67 N). |
| (B) THE FORCE SHALL NOT BE REQUIRED TO BE CONTINUOUSLY |
| APPLIED FOR MORE THAN 3 SECONDS. |
| (C) THE INITIATION OF THE RELEASE PROCESS SHALL |
| ACTIVATE AN |
| AUDIBLE SIGNAL IN THE VICINITY OF THE DOOR OPENING. |
| (D) ONCE THE LOCK HAS BEEN RELEASED BY THE APPLICATION |
| OF FORCE TO THE RELEASING DEVICE, RELOCKING SHALL BE BY |
| MANUAL MEANS ONLY. |
| (4)*A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| THAN 1 IN. |
| (25 MM) HIGH AND NOT LESS THAN 1?8 IN. (3.2 MM) IN |
| STROKE |
| WIDTH ON A CONTRASTING BACKGROUND SHALL BE LOCATED ON |
| THE DOOR LEAF ADJACENT TO THE RELEASE DEVICE IN THE |
| DIRECTION |
| OF EGRESS, AND SHALL READ AS FOLLOWS: |
| (A) PUSH UNTIL ALARM SOUNDS, DOOR CAN BE |
| OPENED IN 15 SECONDS, FOR DOORS THAT SWING IN |
| THE DIRECTION OF EGRESS TRAVEL |
| (B) PULL UNTIL ALARM SOUNDS, DOOR CAN BE |
| OPENED IN 15 SECONDS, FOR DOORS THAT SWING |
| AGAINST THE DIRECTION OF EGRESS TRAVEL |
| (5) THE EGRESS SIDE OF DOORS EQUIPPED WITH |
| DELAYED-EGRESS |
| LOCKS SHALL BE PROVIDED WITH EMERGENCY LIGHTING IN |
| ACCORDANCE |
| WITH SECTION 7.9. |
| 7.2.1.6.1.2 THE PROVISIONS OF 7.2.1.6.2 FOR |
| ACCESS-CONTROLLED |
| EGRESS DOOR ASSEMBLIES SHALL NOT APPLY TO DOOR |
| ASSEMBLIES WITH |
| DELAYED-EGRESS LOCKING SYSTEMS. |
| 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES. |
| WHERE |
| PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR ASSEMBLIES IN |
| THE |
| MEANS OF EGRESS SHALL BE PERMITTED TO BE EQUIPPED WITH |
| ELECTRICAL |
| LOCK HARDWARE THAT PREVENTS EGRESS, PROVIDED THAT ALL |
| OF |
| THE FOLLOWING CRITERIA ARE MET: |
| (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE, |
| ARRANGED TO |
| UNLOCK THE DOOR LEAF IN THE DIRECTION OF EGRESS UPON |
| DETECTION |
| OF AN A (2) DOOR LEAVES SHALL AUTOMATICALLY UNLOCK IN |
| THE DIRECTION OF |
| EGRESS UPON LOSS OF POWER TO THE SENSOR OR TO THE PART |
| OF |
| THE ACCESS CONTROL SYSTEM THAT LOCKS THE DOOR LEAVES. |
| (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE |
| DIRECTION OF |
| EGRESS FROM A MANUAL RELEASE DEVICE COMPLYING WITH ALL |
| OF |
| THE FOLLOWING CRITERIA: |
| (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE |
| EGRESS SIDE, 40 IN. TO 48 IN. (1015 MM TO 1220 MM) |
| VERTICALLY ABOVE THE FLOOR, AND WITHIN 60 IN. |
| (1525 MM) OF THE SECURED DOOR OPENINGS. |
| (B) THE MANUAL RELEASE DEVICE SHALL BE READILY |
| ACCESSIBLE |
| AND CLEARLY IDENTIFIED BY A SIGN THAT READS AS FOLLOWS: |
| PUSH TO EXIT. |
| (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL |
| RESULT |
| IN DIRECT INTERRUPTION OF POWER TO THE LOCK ? |
| INDEPENDENT OF THE LOCKING SYSTEM ELECTRONICS?AND |
| THE LOCK SHALL REMAIN UNLOCKED FOR NOT LESS THAN |
| 30 SECONDS. |
| (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE |
| SIGNALING SYSTEM, |
| IF PROVIDED, SHALL AUTOMATICALLY UNLOCK THE DOOR LEAVES |
| IN |
| THE DIRECTION OF EGRESS, AND THE DOOR LEAVES SHALL |
| REMAIN |
| UNLOCKED UNTIL THE FIRE-PROTECTIVE SIGNALING SYSTEM HAS |
| BEEN MANUALLY RESET. |
| (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT |
| ACTIVATE THE |
| BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM SPECIFIED IN |
| 7.2.1.6.2(4) SHALL NOT BE REQUIRED TO UNLOCK THE DOOR |
| LEAVES. (6) ACTIVATION OF THE BUILDING AUTOMATIC |
| SPRINKLER OR FIRE DETECTION |
| SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY UNLOCK THE |
| DOOR LEAVES IN THE DIRECTION OF EGRESS, AND THE DOOR |
| LEAVES |
| SHALL REMAIN UNLOCKED UNTIL THE FIRE-PROTECTIVE |
| SIGNALING |
| SYSTEM HAS BEEN MANUALLY RESET. |
| 7) THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS, |
| OTHER THAN |
| EXISTING ACCESS-CONTROLLED EGRESS DOORS, SHALL BE |
| PROVIDED |
| WITH EMERGENCY LIGHTING IN ACCORDANCE WITH SECTION 7.9. |
| |