Plan Review Notes
Plan Review Notes For Permit 22050479
Permit Number 22050479
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-08-25 14:26:30FIRE PROVISO COMMENTS:
  
 ALL INSTALLED EQUIPMENT SHALL FUNCTION AS PER THE
 REQUIREMENTS OF NFPA 101, CHAPTER 7, MEANS OF EGRESS AS
 APPLICABLE FOR EACH DOOR/ENTRY/EXIT.
 7.2.1.5.6 ELECTRICALLY CONTROLLED EGRESS DOOR
 ASSEMBLIES.
 DOOR ASSEMBLIES IN THE MEANS OF EGRESS SHALL BE
 PERMITTED TO
 BE ELECTRICALLY LOCKED IF EQUIPPED WITH APPROVED,
 LISTED HARDWARE,
 PROVIDED THAT ALL OF THE FOLLOWING CONDITIONS ARE MET:
 (1) THE HARDWARE FOR OCCUPANT RELEASE OF THE LOCK IS
 AFFIXED TO
 THE DOOR LEAF.
 (2) THE HARDWARE HAS AN OBVIOUS METHOD OF OPERATION
 THAT IS
 READILY OPERATED IN THE DIRECTION OF EGRESS.
 (3) THE HARDWARE IS CAPABLE OF BEING OPERATED WITH ONE
 HAND
 IN THE DIRECTION OF EGRESS.
 (4) OPERATION OF THE HARDWARE INTERRUPTS THE POWER
 SUPPLY
 DIRECTLY TO THE ELECTRIC LOCK AND UNLOCKS THE DOOR
 ASSEMBLY
 IN THE DIRECTION OF EGRESS.
 (5)*LOSS OF POWER TO THE LISTED RELEASING HARDWARE
 AUTOMATICALLY
 UNLOCKS THE DOOR ASSEMBLY IN THE DIRECTION OF EGRESS.
 (6) HARDWARE FOR NEW INSTALLATIONS IS LISTED IN
 ACCORDANCE WITH
 ANSI/UL 294, STANDARD FOR ACCESS CONTROL SYSTEM UNITS.
 7.2.1.6.1 DELAYED-EGRESS LOCKING SYSTEMS.
 7.2.1.6.1.1 APPROVED, LISTED, DELAYED-EGRESS LOCKING
 SYSTEMS
 SHALL BE PERMITTED TO BE INSTALLED ON DOOR ASSEMBLIES
 SERVING
 LOW AND ORDINARY HAZARD CONTENTS IN BUILDINGS PROTECTED
 THROUGHOUT BY AN APPROVED, SUPERVISED AUTOMATIC FIRE
 DETECTION
 SYSTEM IN ACCORDANCE WITH SECTION 9.6 OR AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE
 WITH SECTION
 9.7, AND WHERE PERMITTED IN CHAPTERS 11 THROUGH 43,
 PROVIDED
 THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (1) THE DOOR LEAVES SHALL UNLOCK IN THE DIRECTION OF
 EGRESS
 UPON ACTUATION OF ONE OF THE FOLLOWING:
 (A) APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7
 (B) NOT MORE THAN ONE HEAT DETECTOR OF AN APPROVED,
 SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN
 ACCORDANCE
 WITH SECTION 9.6
 (C) NOT MORE THAN TWO SMOKE DETECTORS OF AN APPROVED,
 SUPERVISED AUTOMATIC FIRE DETECTION SYSTEM IN
 ACCORDANCE
 WITH SECTION 9.6
 (2) THE DOOR LEAVES SHALL UNLOCK IN THE DIRECTION OF
 EGRESS UPON
 LOSS OF POWER CONTROLLING THE LOCK OR LOCKING
 MECHANISM.
 (3)*AN IRREVERSIBLE PROCESS SHALL RELEASE THE LOCK IN
 THE DIRECTION
 OF EGRESS WITHIN 15 SECONDS, OR 30 SECONDS WHERE
 APPROVED
 BY THE AUTHORITY HAVING JURISDICTION, UPON APPLICATION
 OF A FORCE TO THE RELEASE DEVICE REQUIRED IN 7.2.1.5.10
 UNDER ALL OF THE FOLLOWING CONDITIONS:
 (A) THE FORCE SHALL NOT BE REQUIRED TO EXCEED 15 LBF
 (67 N).
 (B) THE FORCE SHALL NOT BE REQUIRED TO BE CONTINUOUSLY
 APPLIED FOR MORE THAN 3 SECONDS.
 (C) THE INITIATION OF THE RELEASE PROCESS SHALL
 ACTIVATE AN
 AUDIBLE SIGNAL IN THE VICINITY OF THE DOOR OPENING.
 (D) ONCE THE LOCK HAS BEEN RELEASED BY THE APPLICATION
 OF FORCE TO THE RELEASING DEVICE, RELOCKING SHALL BE BY
 MANUAL MEANS ONLY.
 (4)*A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN.
 (25 MM) HIGH AND NOT LESS THAN 1?8 IN. (3.2 MM) IN
 STROKE
 WIDTH ON A CONTRASTING BACKGROUND SHALL BE LOCATED ON
 THE DOOR LEAF ADJACENT TO THE RELEASE DEVICE IN THE
 DIRECTION
 OF EGRESS, AND SHALL READ AS FOLLOWS:
 (A) PUSH UNTIL ALARM SOUNDS, DOOR CAN BE
 OPENED IN 15 SECONDS, FOR DOORS THAT SWING IN
 THE DIRECTION OF EGRESS TRAVEL
 (B) PULL UNTIL ALARM SOUNDS, DOOR CAN BE
 OPENED IN 15 SECONDS, FOR DOORS THAT SWING
 AGAINST THE DIRECTION OF EGRESS TRAVEL
 (5) THE EGRESS SIDE OF DOORS EQUIPPED WITH
 DELAYED-EGRESS
 LOCKS SHALL BE PROVIDED WITH EMERGENCY LIGHTING IN
 ACCORDANCE
 WITH SECTION 7.9.
 7.2.1.6.1.2 THE PROVISIONS OF 7.2.1.6.2 FOR
 ACCESS-CONTROLLED
 EGRESS DOOR ASSEMBLIES SHALL NOT APPLY TO DOOR
 ASSEMBLIES WITH
 DELAYED-EGRESS LOCKING SYSTEMS.
 7.2.1.6.2* ACCESS-CONTROLLED EGRESS DOOR ASSEMBLIES.
 WHERE
 PERMITTED IN CHAPTERS 11 THROUGH 43, DOOR ASSEMBLIES IN
 THE
 MEANS OF EGRESS SHALL BE PERMITTED TO BE EQUIPPED WITH
 ELECTRICAL
 LOCK HARDWARE THAT PREVENTS EGRESS, PROVIDED THAT ALL
 OF
 THE FOLLOWING CRITERIA ARE MET:
 (1) A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO
 UNLOCK THE DOOR LEAF IN THE DIRECTION OF EGRESS UPON
 DETECTION
 OF AN A (2) DOOR LEAVES SHALL AUTOMATICALLY UNLOCK IN
 THE DIRECTION OF
 EGRESS UPON LOSS OF POWER TO THE SENSOR OR TO THE PART
 OF
 THE ACCESS CONTROL SYSTEM THAT LOCKS THE DOOR LEAVES.
 (3) DOOR LOCKS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF
 EGRESS FROM A MANUAL RELEASE DEVICE COMPLYING WITH ALL
 OF
 THE FOLLOWING CRITERIA:
 (A) THE MANUAL RELEASE DEVICE SHALL BE LOCATED ON THE
 EGRESS SIDE, 40 IN. TO 48 IN. (1015 MM TO 1220 MM)
 VERTICALLY ABOVE THE FLOOR, AND WITHIN 60 IN.
 (1525 MM) OF THE SECURED DOOR OPENINGS.
 (B) THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE
 AND CLEARLY IDENTIFIED BY A SIGN THAT READS AS FOLLOWS:
 PUSH TO EXIT.
 (C) WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT
 IN DIRECT INTERRUPTION OF POWER TO THE LOCK ?
 INDEPENDENT OF THE LOCKING SYSTEM ELECTRONICS?AND
 THE LOCK SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 (4) ACTIVATION OF THE BUILDING FIRE-PROTECTIVE
 SIGNALING SYSTEM,
 IF PROVIDED, SHALL AUTOMATICALLY UNLOCK THE DOOR LEAVES
 IN
 THE DIRECTION OF EGRESS, AND THE DOOR LEAVES SHALL
 REMAIN
 UNLOCKED UNTIL THE FIRE-PROTECTIVE SIGNALING SYSTEM HAS
 BEEN MANUALLY RESET.
 (5) THE ACTIVATION OF MANUAL FIRE ALARM BOXES THAT
 ACTIVATE THE
 BUILDING FIRE-PROTECTIVE SIGNALING SYSTEM SPECIFIED IN
 7.2.1.6.2(4) SHALL NOT BE REQUIRED TO UNLOCK THE DOOR
 LEAVES. (6) ACTIVATION OF THE BUILDING AUTOMATIC
 SPRINKLER OR FIRE DETECTION
 SYSTEM, IF PROVIDED, SHALL AUTOMATICALLY UNLOCK THE
 DOOR LEAVES IN THE DIRECTION OF EGRESS, AND THE DOOR
 LEAVES
 SHALL REMAIN UNLOCKED UNTIL THE FIRE-PROTECTIVE
 SIGNALING
 SYSTEM HAS BEEN MANUALLY RESET.
 7) THE EGRESS SIDE OF ACCESS-CONTROLLED EGRESS DOORS,
 OTHER THAN
 EXISTING ACCESS-CONTROLLED EGRESS DOORS, SHALL BE
 PROVIDED
 WITH EMERGENCY LIGHTING IN ACCORDANCE WITH SECTION 7.9.
  