2022-05-26 07:31:281) PROVIDE THE ANCHORAGE DETAIL FOR THE CONDENSING
 UNIT. FRC M1307.2
 2) PROVIDE THE CONDENSATE DRAINAG PIPE SIZE, MATERIAL
 AND TERMINATION LOCATION. FRC M1411.3
 3) PROVIDE A BATH EXHAUST FAN AND DUCT TERMINATION
 LOCATION. FRC M1507.4
  