Plan Review Notes For Permit 22050377 |
Permit Number |
22050377 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-05-21 10:02:28 | 1ST PLUMBING REVIEW | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. P701-DETAIL 6 - 2020 FRC P2709.1 - THE SHOWER FLOOR | | SHALL HAVE A MINIMUM SLOPE OF 1/4" PER FOOT. CURRENTLY | | IT SAYS 1/8" PER FOOT. | | | | 2. 2020 FRC P2713.3 - IT APPEARS YOU INTEND TO USE A | | TWO HANDLE TUB VALVE. HOT WATER SUPPLIED TO A TUB IS | | REQUIRED TO BE LIMITED TO A TEMPERATURE OF LESS THAN | | 120 BY A DEVICE CONFORMING TO ASSE 1070. PLEASE SHOW A | | DETAIL FOR COMPLIANCE TO THIS OR SHOW A COMPLIANT TUB | | VALVE. | | | | 3. 2020 FRC P3105.1 - THE LENGTH OF YOUR FIXTURE DRAINS | | FOR THE TUB AND SHOWER APPEAR TO BE MORE THAN 8 FEET. | | THE LIMIT FOR A 2" FIXTURE DRAIN IS 8' FROM THE TRAP TO | | THE VENT CONNECTION. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | |
|