Plan Review Notes
Plan Review Notes For Permit 22050377
Permit Number 22050377
Review Stop P
Sequence Number 1
Notes
Date Text
2022-05-21 10:02:281ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. P701-DETAIL 6 - 2020 FRC P2709.1 - THE SHOWER FLOOR
 SHALL HAVE A MINIMUM SLOPE OF 1/4" PER FOOT. CURRENTLY
 IT SAYS 1/8" PER FOOT.
  
 2. 2020 FRC P2713.3 - IT APPEARS YOU INTEND TO USE A
 TWO HANDLE TUB VALVE. HOT WATER SUPPLIED TO A TUB IS
 REQUIRED TO BE LIMITED TO A TEMPERATURE OF LESS THAN
 120 BY A DEVICE CONFORMING TO ASSE 1070. PLEASE SHOW A
 DETAIL FOR COMPLIANCE TO THIS OR SHOW A COMPLIANT TUB
 VALVE.
  
 3. 2020 FRC P3105.1 - THE LENGTH OF YOUR FIXTURE DRAINS
 FOR THE TUB AND SHOWER APPEAR TO BE MORE THAN 8 FEET.
 THE LIMIT FOR A 2" FIXTURE DRAIN IS 8' FROM THE TRAP TO
 THE VENT CONNECTION.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  