Plan Review Notes
Plan Review Notes For Permit 22050309
Permit Number 22050309
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2022-05-27 11:13:49FIRE COMMENTS, SECOND REVIEW, NOT ADDRESSED:
 THE CONSTRUCTION PLAN INDICATES A NEW DOOR TO BE
 INSTALLED AT THE A/C CLOSET. IF THE IS DOOR IS IN A
 FIRE RATED CORRIDOR, THE DOOR AND FRAME WILL NEED TO BE
 RATED TO MAINTAIN THE FIRE RATING. THERE WAS NO
 INDICATION OF A RATING ON THE PLAN OR THE DOOR
 SCHEDULE. NFPA 101 8.3.4
 THE PLAN INDICATES NEW TILE FLOORING TO BE INSTALLED.
 PROVIDE THE TYPE OF TILE FLOORING TO BE INSTALLED TO
 ENSURE COMPLIANCE WITH NFPA 101 10.2.7
  