2022-05-27 11:13:49 | FIRE COMMENTS, SECOND REVIEW, NOT ADDRESSED: | | THE CONSTRUCTION PLAN INDICATES A NEW DOOR TO BE | | INSTALLED AT THE A/C CLOSET. IF THE IS DOOR IS IN A | | FIRE RATED CORRIDOR, THE DOOR AND FRAME WILL NEED TO BE | | RATED TO MAINTAIN THE FIRE RATING. THERE WAS NO | | INDICATION OF A RATING ON THE PLAN OR THE DOOR | | SCHEDULE. NFPA 101 8.3.4 | | THE PLAN INDICATES NEW TILE FLOORING TO BE INSTALLED. | | PROVIDE THE TYPE OF TILE FLOORING TO BE INSTALLED TO | | ENSURE COMPLIANCE WITH NFPA 101 10.2.7 | | | | C. WALKER | | 561-804-4762 | | [email protected] | | |
|