2022-05-11 13:55:32 | FIRE COMMENTS: | | THE CONSTRUCTION PLAN INDICATES A NEW DOOR TO BE | | INSTALLED AT THE A/C CLOSET. IF THIS DOOR IS IN A FIRE | | RATED CORRIDOR, THE DOOR AND FRAME WILL NEED TO BE | | RATED TO MAINTAIN THE RATING. THE DOOR SCHEDULE DID NOT | | INDICATE A RATING. NFPA 101 8.3.4 | | THE PLAN INDICATES NEW TILE FLOORING TO BE INSTALLED. | | PROVIDE THE TYPE OF TILE TO BE INSTALLED TO ENSURE | | COMPLIANCE WITH NFPA 101, 10.2.7 | | EXISTING LIFE SAFETY SYSTEMS (FIRE ALARM) SHALL BE | | PROTECTED FROM DAMAGE DURING CONSTRUCTION AND | | RENOVATION. | | | | C. WALKER, SENIOR FIRE INSPECTOR | | 561-804-4762 | | [email protected] | | |
|