Date |
Text |
2022-07-19 12:09:52 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL16709-R10 SELECTED SYSTEM NO W-5; EXPOSURE |
| (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT (30 < H < 40); |
| ULTIMATE WIND SPEED (160), IS NOT CORRECT. THE CORRECT |
| WIND SPEED FOR THE LISTED ADDRESS IS 170. WHEN USING |
| THE CORRECT WIND SPEED; ZONE 3 IS MARKED ?N/A? WHICH |
| INDICATES SYSTEM CANNOT BE USED WITHIN THE PRESSURE |
| ZONE. PLEASE PROVIDE A SYSTEM THAT MEETS OR EXCEEDS ALL |
| CRITERIA FOR THE LISTED ADDRESS. PRODUCT APPROVAL |
| FL16709-R10 WILL NOT SATISFY ALL NECESSARY CRITERIA FOR |
| THIS PROJECT. |
| 2. FBC EB 706.8. SHOW THAT THE VALUE OF THE STRUCTURE |
| IS LESS THAN $300,000.00 OR SPECIFY HOW THE ROOF TO |
| WALL CONNECTIONS WILL BE IMPROVED. FOURTH REQUEST. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| |