Plan Review Notes For Permit 22050188 |
Permit Number |
22050188 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-06-24 09:58:48 | 1ST PLUMBING REVIEW | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | V7 FGC - 2020 FLORIDA FUEL GAS | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | 2021 F.S. - 2021 FLORIDA STATUTES | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | FBC CHAPTER 1 | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | 1. 2017 WPB AMENDS 107.2.1 - THE DESCRIPTION OF WORK | | SAYS "RELOCATE AND PLUMB BATHROOM". BOTH PAGES | | SUBMITTED SHOW THE SAME LAYOUT. PLEASE SHOW A CLEAR | | EXISTING AND PROPOSED LAYOUT. IF YOU ARE RECONFIGURING | | YOUR BATHROOM, YOU CANNOT DO IT ON A PLUMBING PERMIT. A | | MASTER PERMIT AND A GENERAL CONTRACTOR IS NEEDED. | | | | 2. 2017 WPB AMENDS 107.2.1 - IF YOU ARE PUTTING THEM | | BACK IN THE SAME LOCATION, INDICATE THAT ON THE PLANS | | AND SUBMIT A PLUMBING RISER FOR REVIEW. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | | | RYAN W. BROWN | | CHIEF PLUMBING INSPECTOR | | OFFICE: 561-805-6692 | | CELL: 561-517-4293 | | EMAIL: [email protected] | | |
|