Plan Review Notes
Plan Review Notes For Permit 22050169
Permit Number 22050169
Review Stop E
Sequence Number 3
Notes
Date Text
2022-09-19 13:28:50FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 OUTLET SPACING ON WINDOW WALLS NEEDS TO BE PER 210.52
  
 210.52 (2) WALL SPACE.
  
 AS USED IN THIS SECTION, A WALL SPACE SHALL INCLUDE THE
 FOLLOWING:
  
 (1) ANY SPACE 600 MM (2 FT) OR MORE IN WIDTH (INCLUDING
 SPACE MEASURED AROUND CORNERS) AND UNBROKEN ALONG THE
 FLOOR LINE BY DOORWAYS AND SIMILAR OPENINGS,
 FIREPLACES, AND FIXED CABINETS THAT DO NOT HAVE
 COUNTERTOPS OR SIMILAR WORK SURFACES
  
 (2) THE SPACE OCCUPIED BY FIXED PANELS IN WALLS,
 EXCLUDING SLIDING PANELS