2022-05-23 11:00:10 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-22050166 |
| 5/23/2022 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET PF1.0: PROVIDE A LIST OF CURRENT CODES AND |
| STANDARDS USED IN THE DESIGN OF THE FOUNTAIN. |
| |
| 2) PF1.0: PLACE A NOTE TO INDICATE THE USE OF THE |
| FOUNTAIN- BATHING OR NON-BATHING- SEC 107.2.1 WPB. |
| CLARIFY IF SIGNAGE WILL BE POSTED TO CLARIFY THE USE |
| FOR OCCUPANTS OF THE FACILITY. |
| |
| 3) PF2.0: A BACKFLOW PREVENTER IS REQUIRED AT THE AT |
| WATER SUPPLY LINE TO THE AUTOFILL- SEC. 608.3 FBC P, |
| AND SECS. C, D, & E WPB CROSS-CONNECTION MANUAL. |
| INDICATE THE TYPE OF DEVICE TO BE INSTALLED. |
| |
| 4) PF2.0 & PF2.2: THE PLUMBING DIAGRAM SHOWS A 3-INCH |
| MAIN DRAIN LINE BUT THE DRAIN ASSEMBLY FLOW RATES ARE |
| BASED ON 2-1/2-INCH OUTLET- SEC. 107.2.1 WPB. |
| |
| 4) PF2.0 & PF2.2: PLEASE REVIEW THE POOL WASTE WATER |
| GUIDELINES BELOW WHICH ARE ALSO APPLICABLE TO FOUNTAIN |
| WASTE WATER. |
| SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY |
| SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES |
| DEPARTMENT. |
| SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER?S |
| SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW |
| AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| -THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO |
| KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| INLET). |
| - NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| INLET TO DISCHARGE EFFLUENT. |
| - WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS |
| PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. DISCHARGE |
| SHALL NOT FLOOD STREETS OR NEIGHBORING PROPERTY. |
| - FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT |
| STEPHON HARRIS AT [email protected] OR 561-822-2168. |
| - FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE |
| CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| 822-2062 OR [email protected]. |
| |
| 5) PF2.2: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE |
| PUMPS, FILTER, AND SKIMMER- SECS. 107.2.1 & 107.3.4.1 |
| WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |