Plan Review Notes
Plan Review Notes For Permit 22050166
Permit Number 22050166
Review Stop P
Sequence Number 1
Notes
Date Text
2022-05-23 11:00:101ST REVIEW FBC-2020 PLUMBING
 PERMIT-22050166
 5/23/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET PF1.0: PROVIDE A LIST OF CURRENT CODES AND
 STANDARDS USED IN THE DESIGN OF THE FOUNTAIN.
  
 2) PF1.0: PLACE A NOTE TO INDICATE THE USE OF THE
 FOUNTAIN- BATHING OR NON-BATHING- SEC 107.2.1 WPB.
 CLARIFY IF SIGNAGE WILL BE POSTED TO CLARIFY THE USE
 FOR OCCUPANTS OF THE FACILITY.
  
 3) PF2.0: A BACKFLOW PREVENTER IS REQUIRED AT THE AT
 WATER SUPPLY LINE TO THE AUTOFILL- SEC. 608.3 FBC P,
 AND SECS. C, D, & E WPB CROSS-CONNECTION MANUAL.
 INDICATE THE TYPE OF DEVICE TO BE INSTALLED.
  
 4) PF2.0 & PF2.2: THE PLUMBING DIAGRAM SHOWS A 3-INCH
 MAIN DRAIN LINE BUT THE DRAIN ASSEMBLY FLOW RATES ARE
 BASED ON 2-1/2-INCH OUTLET- SEC. 107.2.1 WPB.
  
 4) PF2.0 & PF2.2: PLEASE REVIEW THE POOL WASTE WATER
 GUIDELINES BELOW WHICH ARE ALSO APPLICABLE TO FOUNTAIN
 WASTE WATER.
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER?S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 -THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO
 KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 - NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 - WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. DISCHARGE
 SHALL NOT FLOOD STREETS OR NEIGHBORING PROPERTY.
 - FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 - FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 5) PF2.2: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PUMPS, FILTER, AND SKIMMER- SECS. 107.2.1 & 107.3.4.1
 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  