| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR EMAIL [email protected]. |
| |
| 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL16709-R9 HAS BEEN REVISED TO FL16709-R10. |
| PLEASE PROVIDE THE FOLLOWING: INCLUDE COVER PAGE, |
| EVALUATION REPORT PAGES 1-4 AND INSTALLATION |
| INSTRUCTIONS FOR SYSTEM USED. ALL APPLICABLE DETAILS |
| AND ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE |
| PRODUCT APPROVAL DRAWINGS. |
| 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL16709-R9 SELECTED SYSTEM NO W-5; EXPOSURE |
| (C; ENCLOSURE (ENCLOSED); ROOF HEIGHT (H < 15); |
| ULTIMATE WIND SPEED 180 IS NOT CORRECT. THE CORRECT |
| EXPOSURE CATEGORY FOR THE LISTED ADDRESS IS EXPOSURE D, |
| WIND SPEED IS 170 MPH. PLEASE SELECT THE CORRECT |
| OPTIONS. PRODUCT APPROVAL FL16709-R9 WILL NOT SATISFY |
| EXPOSURE CATEGORY D ENCLOSED AREAS WITHOUT USING |
| INSULATION OR PROVIDING ENGINEERED ENHANCED NAILING. |
| 3. FBC R 905.1.1 ASPHALT SHINGLE, METAL, MINERAL |
| SURFACE, SLATE AND SLATE-TYPE ROOFING MUST COMPLY WITH |
| NEW 2020 BUILDING CODE UNDERLAYMENT REQUIREMENTS. |
| PROVIDE METHOD OF COMPLIANCE. (IF USING DOUBLE 30# FELT |
| INDICATE ON ROOF DRAWING/SKETCH). |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. |
| |