2022-05-05 13:29:16FIRE PROVISO:
  
 FIRE SPRINKLER PIPE INSPECTION ALSO REQUIRED
 CODE: 603
  
 TEST AT WORKING PRESSURE FOR 2 HOURS PER NFPA 13
  
 CONTRACTOR TO PROVIDE FOR WORKING PRESSURE VERIFICATION
 (I.E. PRESSURE GAUGE 2HRS) AND/OR SYSTEM IS
 CHARGED/DISCHARGED
 UNDER WORKING PRESSURE. (I.E. VISUAL FOR LEAKS &
 INSPECTOR DRAIN AFTER 2 HRS)
  
  