2023-03-01 13:10:41 | 6TH BUILDING REVIEW |
| RESULTS: CORRECTIONS NEEDED |
| |
| CHRISTOPHER S. THROOP, CBO, BN, PX, CFM |
| PLANS EXAMINER II |
| CITY OF WEST PALM BEACH |
| (561) 805-6726 |
| [email protected] |
| |
| CODES IN EFFECT: |
| 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| NFPA 70 2017 EDITION NEC 2017 |
| |
| ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT: |
| |
| NOTICE: |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED OR REMOVED. |
| PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN |
| PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER |
| PREVIOUS COMMENTS. |
| |
| COMMENTS FROM 5TH BUILDING REVIEW: (SEE BELOW) |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. FBC R 301, THE STRUCTURAL DETAIL IS TO INCLUDE WIND |
| DESIGN CRITERIA. CALCULATIONS MAY BE REQUIRED. |
| (NOTE ON PLAN PAGE W1 STATES WALL HAS BEEN DESIGNED IN |
| GENERAL ACCORDANCE WITH THE 2020 FBC 7TH ED) (PROVIDE |
| SITE SPECIFIC WIND DESIGN CALC'S) |
| |
| THE DETAIL IS NOT CLEAR - IT STATES THAT THE WALL WILL |
| BE FILLED WITH "CEMENT". SPECIFY THE "CEMENT" FOR THE |
| WALL. IT IS NOT CLEAR WHERE CEMENT IS PROPOSED - ENTIRE |
| WALL? CELLS WITH REBAR? |
| (FREE STANDING WALL DETAIL SPECIFIES 5/8 REBAR EVERY |
| 12" AND TO FILL BLOCK WALL WITH "CEMENT". SPECIFY |
| CONCRETE STRENGTH FOR WALLS) |
| |
| SPECIFY CONCRETE STRENGTH FOR THE FOOTING. |
| (NOT ADDRESSED) |
| |
| SPECIFY THE SOIL PREP. |
| (PLAN PAGE W1 SHOWS A GRANULAR BASE. PROVIDE THE |
| BEARING CAPACITY OF THE SOILS) |
| |
| HOW WILL THE CAP BE INSTALLED? |
| (NOTE ON PLAN PAFE W1 STATES STRUCTURE BOND ADHESIVE |
| WILL BE USED TO INSTALL COLUMN CAPS. PROVIDE PRODUCT |
| SPECIFICATIONS OF BONDING AGENT) |
| |
| 2. FBC 107, THERE ARE SEVERAL REFERENCES TO "RETAINING |
| WALL" - ON THE DETAIL, THE APPLICATION, THE CONTRACT. |
| AN EMAIL FROM APPLICANT STATED THAT THIS IS NOT A |
| RETAINING WALL. REMOVE ALL REFERENCES TO "RETAINING". |
| THE CONTRACT WILL BE REMOVED (DOES NOT NEED TO BE |
| REVISED), I WILL REDLINE THE APPLICATION. |
| (SEE PAGE W1, SIGNED PROPOSAL AND FREE STANDING WALL |
| DETAIL) |
| |
| 3. (REDLINED SURVEY: WALL, INCLUDING FOOTING MAY NOT |
| ENCROACH ONTO ADJACENT PROPERTY). |
| |
| 4. FBC 107, INCLUDE THE PRINTED NAME AND SIGNATURE OF |
| THE INDIVIDUAL TAKING RESPONSIBLITY FOR THE STRUCTURAL |
| DESIGN. |
| (FREE STANDING WALL DETAIL) |
| |
| ADDITIONAL COMMENTS: |
| |
| 5. FOUNDATION DETAILS ARE MISSING ON PLAN PAGE W1. |
| WALLS ARE SHOWN BEARING ON A GRAVEL BASE. SEE WALL |
| DETAIL ON FREESTANDING WALL DETAIL IN SUPPORTING DOCS. |
| 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| |
| 6. IDENTIFY THE VERTICAL ENFORCEMENT OF WALLS AND |
| COLUMNS ON PLAN PAGE W1. |
| 107.2 CONSTRUCTION DOCUMENTS SHALL BE IN ACCORDANCE |
| WITH SECTIONS107.2.1 THROUGH 107.2.5. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| |
| |
| |
| |
| |
| |