2022-12-27 19:13:12 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. FBC R 301, THE STRUCTURAL DETAIL IS TO INCLUDE WIND |
| DESIGN CRITERIA. CALCULATIONS MAY BE REQUIRED. |
| |
| THE DETAIL IS NOT CLEAR - IT STATES THAT THE WALL WILL |
| BE FILLED WITH "CEMENT". SPECIFY THE "CEMENT" FOR THE |
| WALL. IT IS NOT CLEAR WHERE CEMENT IS PROPOSED - ENTIRE |
| WALL? CELLS WITH REBAR? |
| |
| SPECIFY CONCRETE STRENGTH FOR THE FOOTING. |
| |
| SPECIFY THE SOIL PREP. |
| |
| HOW WILL THE CAP BE INSTALLED? |
| |
| 2. FBC 107, THERE ARE SEVERAL REFERENCES TO "RETAINING |
| WALL" - ON THE DETAIL, THE APPLICATION, THE CONTRACT. |
| AN EMAIL FROM APPLICANT STATED THAT THIS IS NOT A |
| RETAINING WALL. REMOVE ALL REFERENCES TO "RETAINING". |
| THE CONTRACT WILL BE REMOVED (DOES NOT NEED TO BE |
| REVISED), I WILL REDLINE THE APPLICATION. |
| |
| 3. FBC 107, THE FOOTING CANNOT ENCROACH THE PROPERTY |
| LINE. SINCE NO DIMENSIONS WERE PROVIDED, IT IS NOT |
| CLEAR HOW FAR FROM THE PROPERTY LINE THE FOOTING WILL |
| BE. ADVISORY, THE PLAN WILL BE REDLINED TO INDICATE |
| THAT THE FOOTING CANNOT ENCROACH THE PROPERTY LINE. |
| |
| 4. FBC 107, INCLUDE THE PRINTED NAME AND SIGNATURE OF |
| THE INDIVIDUAL TAKING RESPONSIBLITY FOR THE STRUCTURAL |
| DESIGN. |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |