Plan Review Notes
Plan Review Notes For Permit 22041625
Permit Number 22041625
Review Stop B
Sequence Number 5
Notes
Date Text
2022-12-27 19:13:12****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC R 301, THE STRUCTURAL DETAIL IS TO INCLUDE WIND
 DESIGN CRITERIA. CALCULATIONS MAY BE REQUIRED.
  
 THE DETAIL IS NOT CLEAR - IT STATES THAT THE WALL WILL
 BE FILLED WITH "CEMENT". SPECIFY THE "CEMENT" FOR THE
 WALL. IT IS NOT CLEAR WHERE CEMENT IS PROPOSED - ENTIRE
 WALL? CELLS WITH REBAR?
  
 SPECIFY CONCRETE STRENGTH FOR THE FOOTING.
  
 SPECIFY THE SOIL PREP.
  
 HOW WILL THE CAP BE INSTALLED?
  
 2. FBC 107, THERE ARE SEVERAL REFERENCES TO "RETAINING
 WALL" - ON THE DETAIL, THE APPLICATION, THE CONTRACT.
 AN EMAIL FROM APPLICANT STATED THAT THIS IS NOT A
 RETAINING WALL. REMOVE ALL REFERENCES TO "RETAINING".
 THE CONTRACT WILL BE REMOVED (DOES NOT NEED TO BE
 REVISED), I WILL REDLINE THE APPLICATION.
  
 3. FBC 107, THE FOOTING CANNOT ENCROACH THE PROPERTY
 LINE. SINCE NO DIMENSIONS WERE PROVIDED, IT IS NOT
 CLEAR HOW FAR FROM THE PROPERTY LINE THE FOOTING WILL
 BE. ADVISORY, THE PLAN WILL BE REDLINED TO INDICATE
 THAT THE FOOTING CANNOT ENCROACH THE PROPERTY LINE.
  
 4. FBC 107, INCLUDE THE PRINTED NAME AND SIGNATURE OF
 THE INDIVIDUAL TAKING RESPONSIBLITY FOR THE STRUCTURAL
 DESIGN.
  
  
  
  
  
  
  
  
  
  
  