2022-05-04 13:53:47 | 1ST REVIEW FBC-2020 RES. FUEL GAS |
| PERMIT- 22041590 |
| 5/4/2022 |
| |
| CODES IN EFFECT: |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET A-2: PROVIDE A GAS RISER DRAWING THAT INCLUDES |
| THE NEW PIPING TO THE RANGE AND THE EXISTING GAS PIPING |
| AND APPLIANCES AT THE RESIDENCE- SECTION G2412.3 & |
| G2412.4 FBC RES. REFER TO FBC RES. CHAPTER 24 FUEL GAS- |
| THE RISER SHALL INDICATE: |
| A) TYPE OF GAS- NATURAL OR LP. |
| B) DELIVERY PRESSURE AT THE METER. |
| C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. |
| D) TYPES AND SIZES OF PIPING. |
| E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER |
| TO THE MOST REMOTE APPLIANCE OUTLET. |
| F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. |
| G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE |
| UNIONS. |
| H) OUTLET PRESSURES AT REGULATORS. |
| I) LOCATIONS AND TYPES OF PIPE SLEEVES. |
| K) PIPE SIZING TABLES. |
| |
| 2) A-2: SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| RANGE- SEC. G2447.1 FBC RES. |
| |
| 3) A-2: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| RANGE AND INDICATE HOW THE AIR WILL BE PROVIDED- SEC. |
| G2407.1 FBC RES. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |