Plan Review Notes For Permit 22041581 |
Permit Number |
22041581 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-05-18 08:43:34 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT SIGNED AND SEALED DRAWINGS TO SHOW ANCHORING | | OF THE ANTENNA TO THE BUILDING TO RESIST WINDLOADS. FBC | | 1609 | | | | 2) PROVIDE DETAILS TO SHOW HOW THE PENETRATIONS OF THE | | BUILDINGS WALLS AND ROOF WILL BE MADE WEATHER PROOF. | | FBC 1403.2 AND 1503.1 | | | | 3) PROVIDE DETAILS FOR THE PROTECTION OF PENETRATIONS | | OF FIRE-RATED WALLS AND HORIZONTAL ASSEMBLIES. FBC 714 | | | | 4) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
|