Plan Review Notes
Plan Review Notes For Permit 22041543
Permit Number 22041543
Review Stop G
Sequence Number 2
Notes
Date Text
2022-07-22 11:31:04 
 2ND REVIEW FBC-2020 RES. GAS
 PERMIT- 22041543
 7/21/2022
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS #1, 3, 4,
 5, & 6 FROM THE 1ST REVIEW STILL EXIST AND ARE COPIED
 BELOW.
 PLEASE NOTE I HAVE RESEARCHED APPROVED PLANS FOR THE
 RESIDENCE UNDER PERMITS- 18050348, 19040921, & 2110973
 AND THE SPECS REQUESTED IN MY COMMENTS ARE NOT IN THE
 FILES. FURTHER IT WAS NOTED UNDER MASTER PERMIT
 18050348 THAT GAS APPLIANCES WERE TO BE INSTALLED UNDER
 SEPARATE PERMIT. THOSE SEPARATE PERMITS INCLUDE
 19040921 AND 2110973 WHICH HAVE WATER HEATER SPECS, BUT
 NO OTHERS SPECS. ALSO PLEASE NOTE YOUR PREVIOUS RISER
 DRAWINGS INDICATE A 2-INCH MAIN PE GAS PIPE AND NOT AN
 1-1/4 PE PIPE WHICH YOU SHOW ON THIS RISER AND WHICH IS
 QUESTIONED IN MY COMMENT #1. PLEASE COMPLY WITH THE
 COMMENTS.
  
 1) GAS RISER: THE 1-1/4-INCH PE IS UNDERSIZED FOR THE
 NEW 2,216,000 BTU LOAD AT A TOTAL DEVELOPED LENGTH OF
 225 FT.- TABLE 402.4(22) FBC FG. PLEASE SEE SEC. 402.3
 FOR ALTERNATIVE PIPE SIZING METHODS IF APPLICABLE.
  
 3) PROVIDE A PLAN THAT SHOWS THE ACTUAL PHYSICAL
 LOCATIONS OF THE APPLIANCES- SEC. 107.2.1 WPB.
  
 4) SUBMIT MANUFACTURER' SPECIFICATIONS FOR THE RANGE,
 GRILL, AND FIREPLACE THAT SHOW THE BTU GAS LOADS, INPUT
 PRESSURES, AND LISTINGS OF THE APPLIANCES- SECS.
 G2447.1 & G2432- G2435 FBC RES.
  
 5) FIREPLACE: A COMPLETE REVIEW OF THE GAS PLANS CANNOT
 BE ACCOMPLISHED AT THIS TIME BECAUSE OF A LACK OF
 INFORMATION FOR THE FIREPLACE INCLUDING REQUIRED
 COMBUSTION AIR AND VENTING REQUIREMENTS- SEC. 107.2.1
 WPB. COMBUSTION AIR CALCULATIONS AND A VENTING DIAGRAM
 ARE REQUIRED.
  
 6) GRILL: A COMPLETE REVIEW OF THE GAS PLANS CANNOT BE
 ACCOMPLISHED AT THIS TIME BECAUSE OF A LACK OF
 INFORMATION FOR THE GRILL INCLUDING REQUIRED CLEARANCES
 TO COMBUSTIBLE AND OVERHEAD CONSTRUCTION, COMBUSTION
 AIR AND VENTILATION, AND EXHAUST VENTING GUIDELINES.
 PLEASE NOTE THAT AN EXHAUST HOOD AND DUCT SYSTEM MAY BE
 REQUIRED- SEC. G2448.1 FBC RES. PROVIDE PLAN DETAILS
 THAT REFLECT THE INSTALL MANUAL RECOMMENDATIONS AND
 RESTRICTIONS. A) SHOW THE CLEARANCE DISTANCES FROM THE
 GRILL EXHAUST TO GRAVITY AND MECHANICAL AIR INTAKES
 INTO THE BUILDING- SEC. R303.5.1 FBC RES. MINIMUM 10
 FT. CLEARANCES REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  