Plan Review Notes For Permit 22041540 |
Permit Number |
22041540 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-06-30 14:57:33 | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | | | 1) VALUE OF PERMIT SHOWN IS LOW PLEASE SUBMIT A COST | | BREAK DOWN OF ALL MATERIALS AND LABOR FOR THE COMPLETRE | | JOB. | | | | 2) CONFERENCE ROOM OUTLETS AND FLOOR OUTLETS NOT PER | | 210.71 | | | | 210.71(B) RECEPTACLE OUTLETS REQUIRED. THE TOTAL NUMBER | | OF RECEPTACLE OUTLETS, INCLUDING FLOOR OUTLETS AND | | RECEPTACLE OUTLETS IN FIXED FURNITURE, SHALL NOT BE | | LESS THAN AS DETERMINED IN (1) AND (2). THESE | | RECEPTACLE OUTLETS SHALL BE PERMITTED TO BE LOCATED AS | | DETERMINED BY THE DESIGNER OR BUILDING OWNER. | | (1) RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE | | OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH | | 210.52(A)(1) THROUGH (A)(4). | | (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM THAT IS AT | | LEAST 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF | | AT LEAST 20 M2 (215 FT2) SHALL HAVE AT LEAST ONE | | RECEPTACLE OUTLET LOCATED IN THE FLOOR AT A DISTANCE | | NOT LESS THAN 1.8 M (6 FT) FROM ANY FIXED WALL FOR EACH | | 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR SPACE. | | |
|