Plan Review Notes
Plan Review Notes For Permit 22041540
Permit Number 22041540
Review Stop E
Sequence Number 1
Notes
Date Text
2022-06-30 14:57:33 
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 1) VALUE OF PERMIT SHOWN IS LOW PLEASE SUBMIT A COST
 BREAK DOWN OF ALL MATERIALS AND LABOR FOR THE COMPLETRE
 JOB.
  
 2) CONFERENCE ROOM OUTLETS AND FLOOR OUTLETS NOT PER
 210.71
  
 210.71(B) RECEPTACLE OUTLETS REQUIRED. THE TOTAL NUMBER
 OF RECEPTACLE OUTLETS, INCLUDING FLOOR OUTLETS AND
 RECEPTACLE OUTLETS IN FIXED FURNITURE, SHALL NOT BE
 LESS THAN AS DETERMINED IN (1) AND (2). THESE
 RECEPTACLE OUTLETS SHALL BE PERMITTED TO BE LOCATED AS
 DETERMINED BY THE DESIGNER OR BUILDING OWNER.
 (1) RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE
 OUTLETS SHALL BE INSTALLED IN ACCORDANCE WITH
 210.52(A)(1) THROUGH (A)(4).
 (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM THAT IS AT
 LEAST 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF
 AT LEAST 20 M2 (215 FT2) SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET LOCATED IN THE FLOOR AT A DISTANCE
 NOT LESS THAN 1.8 M (6 FT) FROM ANY FIXED WALL FOR EACH
 20 M2 (215 FT2) OR MAJOR PORTION OF FLOOR SPACE.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved