Plan Review Notes
Plan Review Notes For Permit 22041501
Permit Number 22041501
Review Stop M
Sequence Number 4
Notes
Date Text
2023-01-10 10:42:12THE REVISED DRAWING STILL SHOWS A/C WALL UNITS. THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS SPECIFY PTAC
 UNITS AND ROOM UNITS. THE DRAWING SHOOULD INDICATE
 THESE PTAC UNITS. THE SPECS FOR THE PTAC UNITS SHOULD
 ALSO BE SUBMITTED ON THE DRAWING. FBC 107.3.5
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER