Plan Review Notes For Permit 22041501
Permit Number 22041501
Review Stop M
Sequence Number 3
Notes
Date Text
2022-10-11 08:46:093RD REVIEW FMC
 PERMIT: 22041501
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 01 NOW INDICATES EACH UNIT TO HAVE AN A/C WALL
 UNIT IN EACH AREA. PLEASE SHOW THAT THESE THROUGH THE
 WALL UNITS MEET THE HEATING REQUIREMENTS OF FMC 309.1
 309.1 SPACE-HEATING SYSTEMS.
 INTERIOR SPACES INTENDED FOR HUMAN OCCUPANCY SHALL BE
 PROVIDED WITH ACTIVE OR PASSIVE SPACE-HEATING SYSTEMS
 CAPABLE OF MAINTAINING AN INDOOR TEMPERATURE OF NOT
 LESS THAN 68??F (20??C) AT A POINT 3 FEET (914 MM)
 ABOVE FLOOR ON THE DESIGN HEATING DAY. THE INSTALLATION
 OF PORTABLE SPACE HEATERS SHALL NOT BE USED TO ACHIEVE
 COMPLIANCE WITH THIS SECTION.
  
 EXCEPTIONS:
 1. INTERIOR SPACES WHERE THE PRIMARY PURPOSE IS NOT
 ASSOCIATED WITH HUMAN COMFORT.
 2. GROUP F, H, S AND U OCCUPANCIES.
  
  
 2) THE ENERGY CALCULATIONS WILL NEED TO BE UPDATED TO
 REFLECT THE NEWLY REVISED MECHANICAL SYSTEMS. FEC
 101.5.1.1 AND C403.2.1
  
 3) SHEET M1 STILL SHOWS THE AHU???S AND DUCTWORK. THE
 MECHANICAL DRAWING SHOULD REFLECT THE SYSTEMS BEING
 INSTALLED. IF THIS M1 SHEET IS NOT WHAT IS TO BE
 INSTALLED THEN RESUBMIT SHEET M1 THAT REFLECTS THE
 DESIGN THAT WILL BE USED TO INSTALL ALL OF THE
 MECHANICAL WORK BEING COMPLETED UNDER THIS PERMIT.
 PLEASE INCLUDE THE BATH EXHAUST DUCT, DRYER DUCT AND
 KITCHEN HOODS FOR EACH UNIT. IF THESE ARE TO BE
 EXISTING TO REMAIN PLEASE ADD A NOTE STATING THIS. FBC
 107.3.5
  
 4) SHEET M1 ALSO REFLECTS THAT AHU???S 3 AND 4 ARE
 INSTALLED IN THE ATTIC OF THIS COMMERCIAL BUILDING.
 THIS IS PROHIBITED IN A COMMERCIAL BUILDING. PLEASE
 CORRECT THIS IF AHU???S ARE TO BE USED.
  
 C403.2.9.6 AIR-HANDLING UNITS. AIR-HANDLING UNITS SHALL
 NOT BE ALLOWED IN ATTICS OF COMMERCIAL BUILDINGS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  