2022-07-27 08:21:50 | 2ND REVIEW FMC |
| PERMIT: 22041501 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET 01 INDICATES THAT THE MECHANICAL UNITS FOR |
| THIS 2 STORY 4 UNIT COMMERCIAL APARTMENT BUILDING WILL |
| BE MINI SPLIT SYSTEMS. SHEET M1 INDICATES THAT EACH |
| APARTMENT HAS AN AHU AND A CONDENSING UNIT. THE DUCT |
| WORK APPEARS TO STILL BE IN THE FIRE RATED FLOOR |
| CEILING ASSEMBLY. THE BATH EXHAUST DUCT ALSO STILL |
| APPEARS TO BE IN THE RATED FLOOR CEILING ASSEMBLY. |
| PLEASE ADDRESS 1ST CYCLE COMMENTS AND MAKE SURE THE |
| DRAWINGS ARE CONSISTENT. |
| |
| 2) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS ARE FOR |
| RESIDENTIAL, THE MECHANICAL EQUIPMENT SIZING |
| CALCULATIONS SHOULD BE SIZED IN ACCORDANCE TO FEC |
| C403.2.1. THE CALCULATIONS SHOULD ALSO INCLUDE THE |
| APARTMENT THAT EACH UNIT IS SIZED TO CONDITION. |
| |
| 3) THE COMMON HALL OF THIS COMMERCIAL BUILDING SHOULD |
| HAVE VENTILATION. PLEASE SHOW THE CALCULATIONS FOR THE |
| VENTILATION. FMC TABLE 403.3.1.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |