2022-07-27 08:21:502ND REVIEW FMC
 PERMIT: 22041501
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 01 INDICATES THAT THE MECHANICAL UNITS FOR
 THIS 2 STORY 4 UNIT COMMERCIAL APARTMENT BUILDING WILL
 BE MINI SPLIT SYSTEMS. SHEET M1 INDICATES THAT EACH
 APARTMENT HAS AN AHU AND A CONDENSING UNIT. THE DUCT
 WORK APPEARS TO STILL BE IN THE FIRE RATED FLOOR
 CEILING ASSEMBLY. THE BATH EXHAUST DUCT ALSO STILL
 APPEARS TO BE IN THE RATED FLOOR CEILING ASSEMBLY.
 PLEASE ADDRESS 1ST CYCLE COMMENTS AND MAKE SURE THE
 DRAWINGS ARE CONSISTENT.
  
 2) THE MECHANICAL EQUIPMENT SIZING CALCULATIONS ARE FOR
 RESIDENTIAL, THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS SHOULD BE SIZED IN ACCORDANCE TO FEC
 C403.2.1. THE CALCULATIONS SHOULD ALSO INCLUDE THE
 APARTMENT THAT EACH UNIT IS SIZED TO CONDITION.
  
 3) THE COMMON HALL OF THIS COMMERCIAL BUILDING SHOULD
 HAVE VENTILATION. PLEASE SHOW THE CALCULATIONS FOR THE
 VENTILATION. FMC TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  