2022-07-27 11:53:08 | THE PREVIOUS FAILED FIRE COMMENTS DO NOT SEEM TO BE |
| ADDRESSED ION THE RESUBMITTAL. |
| |
| THE IS A NOTE # 5 ON THE 1ST AND 2ND FLOOR PLANS |
| STATING NEW FLOORING AND PAINT. |
| |
| THERE IS NO INDICATION OF WHAT THAT FLOORING TYPE(S) IS |
| NOR WHERE IT WILL BE LOCATED. |
| |
| PLEASE REVIEW AND ADDRESS THE COMMENTS. |
| |
| THE COMMENTS ARE RESUBMITTED BELOW: |
| |
| |
| |
| ******************************************************* |
| ************************** |
| |
| THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| 1) THERE IS AN INDICATION OF NEW FLOORING, BUT NO |
| INDICATION OF WHAT TYPE OF FLOORING. |
| |
| PER NFPA 101, CH 30 |
| |
| 30.3.3.3 INTERIOR FLOOR FINISH. |
| 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN |
| ACCORDANCE WITH |
| SECTION 10.2. |
| |
| 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH |
| 10.2.2.2 |
| ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL |
| HAVE A |
| MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. |
| |
| FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE TYPE OF |
| FINISH FLOORING PRODUCT AND PRODUCT NAME AND SPEC SHEET |
| THAT INDICATES THE FIRE BEHAVIOR RATING. |
| |
| FYI.....IF THE PROPOSED IS PORCELAIN OR CERAMIC TILE, |
| NATURAL STONE TILE, CONCRETE TILES, SPEC SHEETS WOULD |
| NOT BE REQUIRED. |
| |
| |
| 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |