Plan Review Notes
Plan Review Notes For Permit 22041501
Permit Number 22041501
Review Stop M
Sequence Number 1
Notes
Date Text
2022-05-27 08:45:421ST REVIEW FMC
 PERMIT: 22041501
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REVISE THE MECHANICAL PLAN TO PROVIDE DETAIL
 DRAWINGS OF ALL MECHANICAL SYSTEMS INSIDE THE
 FLOOR/CEILING ASSEMBLY AND HOW THE FIRE SEPARATION WILL
 BE PROTECTED. FMC 607.6.2
  
 2) REVISE MECHANICAL DRAWING TO SHOW HOW THE COMMON
 HALL WILL BE VENTILATED. FMC TABLE 403.3.1.1
  
 3) REVISE THE MECHANICAL DRAWING TO SHOW HOW THE
 BATHROOM EXHAUST DUCT THAT IS SHARED BETWEEN TENANTS
 WILL NOT RECIRCULATE BACK INTO TENANT SPACES. FMC
 403.3.1.1 FOOTNOTE G
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  