Plan Review Notes For Permit 22041501 |
Permit Number |
22041501 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-05-27 16:00:25 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THERE IS AN INDICATION OF NEW FLOORING, BUT NO | | INDICATION OF WHAT TYPE OF FLOORING. | | | | PER NFPA 101, CH 30 | | | | 30.3.3.3 INTERIOR FLOOR FINISH. | | 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN | | ACCORDANCE WITH | | SECTION 10.2. | | | | 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH | | 10.2.2.2 | | ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL | | HAVE A | | MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2. | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE TYPE OF | | FINISH FLOORING PRODUCT AND PRODUCT NAME AND SPEC SHEET | | THAT INDICATES THE FIRE BEHAVIOR RATING. | | | | FYI.....IF THE PROPOSED IS PORCELAIN OR CERAMIC TILE, | | NATURAL STONE TILE, CONCRETE TILES, SPEC SHEETS WOULD | | NOT BE REQUIRED. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|