Date |
Text |
2022-06-09 09:19:31 | ELECTRIC REVIEW FAILED |
| |
| 1)VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| LOW. PLEASE PROVIDE A BREAKDOWN OF ALL MATERIALS AND |
| LABOR, OR, AT YOUR DISCRETION, PROVIDE A SIGNED |
| CONTRACTOR OR PROVIDE A REASONABLE VALUE. WPB F.B.C. |
| 109.3 |
| 2) APARTMENT RISER DIAGRAMS DETAIL (4) INDIVIDUAL |
| SERVICES. THIS DOES NOT COMPLY WITH NEC 230.2 A |
| BUILDING OR OTHER STRUCTURE SERVED |
| SHALL BE SUPPLIED BY ONLY ONE SERVICE. PLEASE CORRECT |
| AS APPLICABLE. |
| 3) SMOKE ALARMS ARE NOT DETAILED AS PER FBC R314.3 |
| LOCATION AND FBC 314.3.1 INSTALLATION NEAR COOKING |
| APPLIANCES. PLEASE CORRECT AS APPLICABLE. |
| 4) COMMON AREA ELECTRIC (LIGHTING, WASHER, DRYER ETC.) |
| POWER SUPPLY IS NOT SHOWN ON PLANS OR PANEL SCHEDULES. |
| FBC 107.2. PLEASE CORRECT AS APPLICABLE. |
| 5)PLEASE PROVIDE LOCATION OF MAIN ELECTRIC SERVICE ON A |
| SITE PLAN. FBC 107.2 |
| 6) EXTERIOR LIGHT AT DOOR WAY ON UNIT B DOES NOT DETAIL |
| ANY CONTROLLING SWITCH. PLEASE CORRECT AS APPLICABLE. |
| 7) PLEASE PROVIDE A SITE AND FLOOR PLAN DETAILING |
| EXISTING CONDITIONS. FBC 107.2 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| MICHAEL PETERSON |
| ELECTRICAL PLANS EXAMINER |
| [email protected] |
| 561-805-6746 |
| |
| |