Plan Review Notes For Permit 22041498 |
Permit Number |
22041498 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-06-28 13:09:49 | COMMERCIAL ALTERATION | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE PROVIDE THE CANOPY DETAILS THAT COMPLY WITH | | THE WIND LOADS FBC 1609 | | | | 2) PLEASE PROVIDE HANDRAIL DETAILS COMPLYING WITH FBC | | 1014 | | | | 3) PLEASE SHOW THE WIND DESIGN DATA USED FOR THE DESIGN | | - FBC 1603.1.4 | | | | 4) DRAWING A201 = PLEASE SHOW THE TYPE OF WINDOW ON THE | | WINDOW SCHEDULE. | | | | 5) A PRODUCT APPROVAL HAS BEEN PROVIDED FOR CASEMENT | | WINDOWS - PLEASE SHOW WINDOW SIZE AND LOCATION FOR THE | | CASEMENT WINDOWS. | | | | 6) PRODUCT APPROVALS NOA 20-0406.03, NOA 20-1118.02 AND | | FL25574-R1 - NEED TO BE REVIEWED AND MARKED APPROVED BY | | THE ARCHITECT DESIGNER OF RECORD OR BE LISTED ON THE | | DRAWINGS FBC WPB 107.3.4 | | | | 7) PLEASE SHOW ALL ATTACHMENT TYPE, SIZE, AND OC. | | SPACING - PLYWOOD TO FRAMING MEMBERS, FRAMING TO | | FRAMING, SIDING ATTACHMENTS ETC. FBC WPB 107.2 | | | | 8) ONE ACCESSIBLE PARKING SPACE AND ACCESS AISLE PER | | FBC ACCESSIBILITY 502 IS REQUIRED FOR THE FIRST 25 | | ELECTRICAL VEHICLE CHARGING STATIONS - FBC 406.1.7 | | | | 9) PARKING LOT NEEDS TO BE ON A SEPARATE PERMIT. |
|