2022-05-03 08:26:33 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22041348 |
| 5/3/22 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) A1.1.1. & A201: SHOW THE CLEAR FLOOR SPACE DIAGRAMS |
| W/ DIMENSIONS AT THE ACCESSIBLE SINK, DISHWASHER, |
| REFRIGERATOR AND ICE MAKER- SEC. 606.2 & 804.6 FBC ACC. |
| |
| 2) P0.1: SHOW THE LOCATION OF THE REQUIRED DEDICATED |
| SHUT OFF VALVE FOR THE IWH UNDER THE SINK- SEC 503.1 |
| FBC P. |
| |
| 3) P0.1: REMOVE THE PUBLIC LAVATORY LABELING AT THE |
| SINK AND LABEL IT ACCORDING TO THE PLANS WHICH |
| INDICATES A COFFEE ROOM SINK- SEC. 107.2.1 WPB. |
| |
| 4) P0.1: HOT WATER, NOT TEMPERED WATER IS REQUIRED AT |
| THE COFFEE ROOM SINK. REMOVE THE TEMPERED WATER MIXING |
| VALVE AND ALL REFERENCES TO TEMPERED WATER- SECS 419.5 |
| AND 607.1.2 FBC. PROVIDE A MIXING VALVE THAT WILL LIMIT |
| THE HOT WATER TEMPERATURE IN ACCORDANCE WITH SEC. |
| 607.1.1. |
| |
| 5) P1.1: INSTALLATION OF THE NEW FLOOR DRAIN WILL |
| REQUIRE THE FLOOR TO BE X-RAYED TO IN ORDER TO LOCATE |
| REINFORCING STEEL OR POST STRESSED FLOOR TENDONS. |
| PLEASE PLACE A NOTE ON THE PLANS TO VERIFY COMPLIANCE |
| WILL BE MET- SECTION 107.2.1 WPB. |
| |
| 6) P.1.1: NEW DRAIN PIPE PENETRATIONS OF THE EXISTING |
| SLAB WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR |
| SPACE AROUND THE PIPING. PROVIDE A UL TESTED AND |
| APPROVED FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- |
| SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |