Plan Review Notes
Plan Review Notes For Permit 22041264
Permit Number 22041264
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-07-01 14:57:0807/01/22 FAILED
  
 NEED TO SHOW HOW FAR SET BACK THE PROPOSED POOL
 EQUIPMENT IS FROM THE PROPERTY LINE. PER CITY CODE,
 MECHANICAL EQUIPMENT CANNOT PROTRUDE MORE THAN 4 FT
 INTO ANY SETBACK.
  
 ADDITIONALLY, EVERY SWIMMING POOL SHALL BE ENCLOSED BY
 A FENCE OR SIMILAR STRUCTURE WHICH IS INSTALLED TO
 OBSTRUCT ACCESS BY PERSONS OTHER THAN THE OWNERS OR
 OCCUPANTS OF THE RESIDENCE WITHIN WHICH A SWIMMING POOL
 IS LOCATED. BARRIERS OR FENCES SHALL BE AT LEAST FOUR
 FEET IN HEIGHT ABOVE GRADE. ACCESS TO AN ACCESSORY
 SWIMMING POOL MUST BE THROUGH A BUILDING OR THROUGH A
 SELF-CLOSING AND SELF-LATCHING GATE OR THROUGH A SCREEN
 ENCLOSURE DOOR WITH LATCHES PLACED AT LEAST 54 INCHES
 ABOVE BOTTOM OF GATE. AT LEAST 90 PERCENT OF THE
 SURFACE AREA OF ALL SCREEN ENCLOSURES SHALL BE
 SCREENING MATERIAL THROUGH WHICH AIR SHALL FLOW. ALL
 POOLS LOCATED ON A CORNER LOT SHALL BE SCREENED AT THE
 CORNER LOT LINE BY AT LEAST A 42-INCH HIGH LANDSCAPE
 BUFFER, AS MEASURED FROM GRADE, AT THE PROPERTY LINE,
 TO ENSURE PRIVACY.
  