2022-05-16 21:48:14ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. 2/0 AL CONDUCTORS NOT RATED FOR 200AMP RESIDENTIAL
 SERVICE. PROVIDE CORRECTION. NEC 230.23A NEC 310.15B16
  
 2. PROVIDE LOAD CALCULATION INCLUDING ALL LOADS, BOTH
 NEW AND EXISTING. NEC 220 FBC 107.2.1
  
  
  
 END OF COMMENTS.
  