Plan Review Notes For Permit 22041235 |
Permit Number |
22041235 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-07-01 11:37:05 | PETER E VALENTI | | BUILDING PLANS EXAMINER II | | [email protected] | | 561 805 6673 | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC M = FBC MECHANICAL | | FBC FG = FBC FUEL GAS | | | | BUILDING REVIEW DENIED: | | | | PLEASE PROVIDE A CLEAR LIST OF ALL WORK TO BE COMPLETED | | UNDER THIS PERMIT. IT APPEARS TO BE THAT THE FOLLOWING | | WILL BE REQUIRED IN ADDITION TO THE COMPLETE & CLEAR | | LIST OF WORK TO BE COMPLETED: | | | | 1.) FBC B 107.2.1, PROVIDE THE PRODUCT APPROVALS FOR | | MATERIALS TO BE USED INCLUDING HARDI BOARD SIDING & ALL | | WINDOWS. | | 2.) FBC R 703.2, PROVIDE DETAILS AS TO MOISTURE | | BARRIERS TO BE INSTALLED. | | 3.) FBC R (TABLE) 703.3.(1) & FBC R 703.10.2, PROVIDE | | DETAILS FOR SIDING INSTALLATION. | | 4.) FBC R 302.10, INDICATE ON PLAN THE INSULATION THAT | | WILL BE USED IN WALLS, CRAWL SPACES, & ATTIC SPACE. | | 5.) FBC R 703.4, INDICATE ON PLAN THE FLASHING DETAILS | | THAT WILL BE USED AT WINDOW OPENINGS PRIOR TO | | INSTALLATION OF WINDOWS. | | |
|